Troubleshooting
Fix RSLinx Not Seeing a PanelView 550 on the 1747-UIC
Short answer
The PanelView Standard DH-485 port is DCE and the 1747-UIC RS-232 port is DTE, so the link between them is straight-through, never null modem. Set the UIC switch to RS232 (DH485), run the DH-485 UIC Devices driver on the COM number Device Manager shows (COM 8 at address 00 in the working case), and the panel appears in RSWho in about 10 seconds, ready for the PanelBuilder 32 upload.
On this page
- Why won't RSLinx see the PanelView 550 through the 1747-UIC?
- Which 1747-UIC switch position does a PanelView 550 need?
- Does the PanelView 550 need a null modem adapter?
- Which RSLinx driver and COM port do I configure?
- How do I prepare the PanelView 550 for the upload?
- What if the PanelView still does not appear in RSWho?
- Should I upload from this terminal or replace it?
- Questions asked
When RSLinx will not show a PanelView 550 at all, the terminal is usually innocent: the fault is the 1747-UIC switch, the serial wiring, the COM number in the driver, or the panel's mode. The PanelView Standard DH-485 port is DCE and the UIC's RS-232 port is DTE, so that link is wired straight-through and a null modem belongs nowhere in it. The sequence that worked on a 2711-T5A5L1 Series B, FRN 4.20: switch at RS232 (DH485), every old RSLinx driver deleted, the DH-485 UIC Devices driver on the COM number Device Manager reports, terminal in configuration mode, and the upload completed in PanelBuilder 32. Walk the checks below in order; each one is a fault that has stopped this exact upload.
Why won't RSLinx see the PanelView 550 through the 1747-UIC? #
Four faults cover nearly every dead link: the UIC switch is set for the other connector, the serial path is crossed where it must be straight-through, RSLinx holds a COM number the adapter no longer has, or the terminal is not in configuration mode.
- The switch on the side of the UIC selects the RJ45 socket instead of the DB9 socket, so nothing plugged into the DB9 side can be seen.
- A null-modem adapter or crossed cable swaps transmit and receive on a link that needs them pin-for-pin.
- The driver sits on a COM number that Device Manager stopped assigning to the UIC after it moved USB sockets or the virtual machine restarted.
- The terminal is running its application instead of sitting in configuration mode, so it never answers the browse.
Check them in that order, because each is cheaper to read than the one after it: a switch costs a glance, wiring costs a continuity check, the COM number costs a Device Manager look, and the mode costs one trip to the terminal.
Which 1747-UIC switch position does a PanelView 550 need? #
RS232 (DH485), the down position on the side of the adapter, which selects the DB9 socket; the up position selects the RJ45 socket for an RS-485 network drop, and while it is up the DB9 socket is dead.
Read the switch before you plug anything in. It is small, it sits on the side, and it is exactly the kind of thing left over from the last job that used the RJ45 side. The rule is one sentence: the switch position names the connector you are actually using. The terminal's DH-485 port is a DB9, so the DB9 side is the one in play for this upload.
Does the PanelView 550 need a null modem adapter? #
No: the PanelView Standard DH-485 port is DCE, the UIC's RS-232 port is DTE, and DTE-to-DCE is wired straight-through, so use a 2711-NC13 or equivalent cable, and any gender changer in the path must itself be straight-through.
A null modem exists to connect two DTE devices, swapping transmit and receive so each talks into the other's ear. That is the correct cable from a computer or UIC to an SLC-500 or PLC-5 channel 0, and it is the wrong cable here, because the PanelView Standard port is the DCE device in the pair. Rockwell's cable guidance draws the same line: straight-through for uploading to a PanelView from a computer COM port, null modem for those controller channels. The UIC documentation names the 2711-NC13 or an equivalent straight-through cable for exactly this connection.
The gender changer is the trap. The UIC's DB9 is male, the panel socket may need the physical adapter, and changers come in both wirings, so meter it: on a straight-through changer every pin number maps to the same pin number. If you swap changers in the field, meter the new one too. When a PanelView 600 serial connection fails, this same DTE-versus-DCE decision is usually what broke it.
Which RSLinx driver and COM port do I configure? #
The DH-485 UIC Devices driver, on the exact COM number Device Manager shows inside the environment that runs RSLinx, with COM 8 and station address 00 as the working values, and only after deleting every other driver.
- Open Configure Drivers in RSLinx Classic and remove the existing drivers, including any DF1 or DH-485 driver from earlier attempts. A stale driver holding the port will stop the new one from starting.
- Add the DH-485 UIC Devices driver and select the COM number you just read from Device Manager.
- Leave the station address at 00 for the first browse.
- Confirm the driver reports running, and set it to start automatically so the next session does not open with a stopped driver.
The working environment was RSLinx Classic Lite 3.51.00 DPR 9 SR 5.1 on Windows XP Professional Version 2002 SP3 in a virtual machine. Two virtual-machine traps came with it. Moving the UIC to a different USB socket can change its COM number, so re-read Device Manager on every visit instead of trusting last week's note. And an intermittent COM failure inside the VM was cleared only after restarting the virtual machine. Those readings, not memory, are what the driver must match.
How do I prepare the PanelView 550 for the upload? #
Put the terminal in configuration mode by its documented procedure, connect the UIC to the DH-485 port, the only communications port this terminal has, and leave the MicroLogix 1500 entirely out of the path, because it does not pass communications through.
Configuration mode is the terminal's documented setup state, reached by the procedure in its manual; from the running application it is not reached by browsing harder. The upload path is three devices: PC, UIC, terminal. The controller in the cabinet is a separate link on its own connector and plays no part in this transfer.
One safety note: in configuration mode the terminal's operator screens are gone, so put the machine in a stopped state or brief the operator before you switch it over.
What if the PanelView still does not appear in RSWho? #
Wait a full minute before touching hardware: in the working case the workstation itself appeared in RSWho immediately while the PanelView showed up about 10 seconds later, and shorter waits read as dead links that are not.
The wait is discovery, not wire time. Illustrative check with this terminal's displayed rate of 19,200 baud: one character frame is 10 bits, meaning 1 start, 8 data, and 1 stop, so the line carries 19,200 ÷ 10 = 1,920 characters per second. A 20-character frame occupies the wire for 20 ÷ 1,920 ≈ 0.010 s, about 10 ms, and the frame gap adds only character-times more. The seconds you wait are the driver discovering nodes, so let the browse finish.
- Driver stopped, or a port error on start: it is a COM or USB problem. Restart the VM, re-read Device Manager, reselect the COM number.
- Driver running, workstation visible, panel absent after a full minute: it is wiring. Recheck the switch position and meter the gender changer pin-for-pin.
- Driver running, nothing at all visible: the terminal left configuration mode.
- Switch, wiring, COM number and mode all verified and still silent: read the node and baud shown on the terminal's configuration screens, cross-check the controller project's channel configuration, and configure the driver to that network. Do not move the station address to chase a silent port; the address is a network setting, not a cable fix.
Should I upload from this terminal or replace it? #
Upload now: the machine runs, the requested change is an input-field limit edit in PanelBuilder 32, and the procedure above is a repeatable path, so replacement becomes the decision only when the terminal or the controller actually fails.
Keep what the upload gives you. Archive the application file with the machine's documentation, and ask the machine builder for the original source file so the next edit does not depend on a terminal upload at all. When the panels do reach end of life, replacing a fleet of PanelView 550 terminals on DH-485 is the HMI-side path. The controller side is its own project, and migrating a MicroLogix 1500 machine to a current PLC covers it. Treat them as two decisions: one working terminal's limit change is not a migration trigger.
Questions asked
Can I upload through the MicroLogix 1500 instead of connecting to the panel?
No. The MicroLogix 1500 does not pass communications through to the panel link, so the upload path is PC, 1747-UIC, panel, and nothing else. The controller talks on its own round mini-DIN-8 connector; if you also need to go online with it, that is a separate cable, a separate RSLinx driver, and a separate session. Getting the controller online first changes nothing about the panel upload.
Why did a null modem cable work when I connected to an SLC-500?
Because an SLC-500 or MicroLogix serial channel is DTE, like the PC and the UIC, so that link needs transmit and receive crossed on pins 2 and 3, which is exactly how the 1747-CP3 and 1761-CBL-PM02 are built. The PanelView Standard port is DCE, so its cable runs pin-for-pin straight through. Same UIC on the desk, opposite adapter in the link.
Which software edits the application after the upload?
PanelBuilder 32 creates, uploads, and edits PanelView Standard applications. The newer families do not share it: PanelView 800 terminals are programmed from Connected Components Workbench, PanelView Plus from FactoryTalk View Studio for Machine Edition, and PanelView 5000 from Studio 5000 View Designer. An uploaded PanelView Standard file is of no use in those tools.
Does the 1747-UIC baud rate have to match the terminal?
The 1747-UIC auto-bauds to the network, so a mismatch is uncommon. Read the rate shown on the terminal configuration screen, 19,200 in the working case, and only reconfigure the UIC with its gateway configuration utility after you confirm a real mismatch. A driver that will not open the port at all is a COM-number or USB problem, and no baud change fixes that.