Why ProAgent is not available for TIA Portal V13

HMI and touchscreens Published 6 min read

Short answer

No ProAgent package exists for TIA Portal V13, or for any later TIA Portal version: ProAgent stayed with the WinCC flexible generation. The successor is ProDiag, which needs TIA Portal V14 as a minimum and offers a GRAPH overview object for the current step. If the project must stay on V13, build the sequence display yourself from the state the GRAPH block writes into its instance data block.

On this page
  1. Is there a ProAgent version for TIA Portal V13?
  2. Why was ProAgent never ported to TIA Portal?
  3. Why does the migrated WinCC flexible 2008 example show no GRAPH form?
  4. Does ProDiag in TIA Portal V14 replace the ProAgent GRAPH display?
  5. How do you visualize a GRAPH sequence when the project must stay on V13?
  6. Is the V14 upgrade with ProDiag worth it, or is the custom screen the smaller job?
  7. Questions asked

There is no ProAgent for TIA Portal V13, and no separate download adds it: ProAgent was never ported to the TIA platform and stayed with the WinCC flexible generation. That is why the V13 installer offers no ProAgent package to choose — there is nothing to install. The decision for the TP1200 Comfort on your bench splits in two. If the project must stay on V13, you build the GRAPH sequence display yourself from the state the sequence block already writes to the controller. If you may upgrade, ProDiag is the successor option: it needs TIA Portal V14 as a minimum and provides a GRAPH overview object for exactly this job.

Is there a ProAgent version for TIA Portal V13? #

No. ProAgent was never ported to the TIA Portal platform, so the V13 installer offers no ProAgent package to select, no service pack for V13 adds one, and no separate ProAgent download exists for it.

ProAgent is the process-diagnostics option of the WinCC flexible generation: it gave operators a ready-made view of a GRAPH sequence and guided them from the stopped machine to the cause of the fault. On the TIA platform that option does not exist, so the missing entry in the installer is not an installation problem — it is a platform boundary. Stop searching the setup media and the download portal; the time is better spent on one of the two real paths below.

Why was ProAgent never ported to TIA Portal? #

Because the vendor replaced it rather than moved it: on the TIA platform, machine and plant diagnostics became ProDiag, an option package that needs TIA Portal V14 as a minimum and was built for newer devices such as S7-1500 controllers and Comfort Panels.

The split follows the tool generations. ProAgent belongs to the WinCC flexible world; the TIA Portal releases up to V13 shipped without any equivalent diagnostics option, and from V14 that slot is filled by ProDiag. The same dividing line appears when WinCC V7.4, WinCC flexible 2008 and TIA Portal are compared: diagnostics is one of the functions that changed generation together with the engineering tool.

Why does the migrated WinCC flexible 2008 example show no GRAPH form? #

Because migration translates only what exists on both platforms: the ProAgent form is a ProAgent runtime object, the TIA platform has no ProAgent runtime, so the converted project arrives without it and nothing you select during migration brings it back.

Treat that as normal, not as a broken migration — dropping platform-specific objects is the known part of the move, the same behavior covered in how to migrate a WinCC flexible project to TIA Portal. Keep the flexible example usable on an old engineering PC as a functional reference, and write down exactly what the operator saw: the step number, the step name, the status of the sequence, and how a fault was displayed. That list is the requirement you build against on either path.

Reinstalling WinCC flexible 2008 next to the new project is no way around the gap: on one engineering PC the two packages conflict, which is why installing WinCC flexible breaks TIA Portal V13.

Does ProDiag in TIA Portal V14 replace the ProAgent GRAPH display? #

It is the successor, not a copy: ProDiag provides a GRAPH overview object that displays the current status, the current step number and the name of the current step, but it is built from configured supervisions rather than the ProAgent screens of the flexible generation.

The working principle differs from ProAgent. With ProDiag you configure supervisions as their own engineering objects and monitor the machine without changing the user program code; the sequence view and the diagnostic results are shown on the HMI device. The core need carried over from the flexible example — see where the sequence stands — is covered by that GRAPH overview object, so the upgrade is a real path for a TP1200 Comfort.

Two checks belong to the upgrade. First, put your recorded requirements against a small test project with one real sequence before the production project is converted; the displayed items either cover your list or they do not. Second, licensing shows up at runtime too: a TP1200 Comfort can raise a ProDiag license popup at startup even when the project contains no ProDiag objects, and the cause with its documented fix is described in why a TP1200 shows a ProDiag license popup without ProDiag objects.

How do you visualize a GRAPH sequence when the project must stay on V13? #

Build the display from the sequence's own state: map HMI tags to the current step number and the status that the GRAPH function block updates in its instance data block each cycle, then show them with an I/O field, a text list for step names and one reusable faceplate.

The recipe, applied per sequence:

  • Two HMI tags with symbolic references into the sequence's instance data block: the current step number and the status.
  • One text list that maps each step number of that sequence to its step name.
  • One faceplate that shows the step number, the step name and a status indication driven by the status tag.
  • One instance of that faceplate per sequence, placed on the machine's overview screen.

The object types are the standard ones described in what HMI programming covers from screens to controller tags. Keep the screen display-only: it adds no writes to the sequence, so the control logic and the PLC validation stay untouched.

Is the V14 upgrade with ProDiag worth it, or is the custom screen the smaller job? #

For one or two sequences the custom screen is the smaller job; once a machine runs several sequences with fault supervisions, the ProDiag upgrade is the smaller one because its GRAPH overview is configured, not drawn.

Put numbers on it. Worked example, with example values: a line with 6 sequences of 10 steps each, displayed the V13 way.

  • HMI tags: 2 per sequence, so 6 × 2 = 12 tags.
  • Text-list entries: 10 per sequence, so 6 × 10 = 60 entries.
  • Faceplates: 1, instantiated 6 times.

Twelve tags, sixty text entries and one faceplate is a bounded job — that is the whole engineering effort of the V13 path in this example, apart from checking it against the real panel. With ProDiag the shape changes: the supervisions and the sequence view are configured once per sequence, the step display is not drawn at all, and the effort moves to the upgrade itself — converting the project, licensing the option and regression-testing the converted machine program.

The decisions:

  • Project fixed on V13: build the custom screen from the instance data block tags; record the operator's view from the flexible example first, then build the faceplate once.
  • Upgrade allowed and several sequences to cover: go to V14 or later with ProDiag, verify the sequence view in a test project against your recorded list, and settle the option license before the production conversion.
  • ProAgent itself written into the specification: strike it out — no TIA Portal version carries it, and ProDiag plus a custom screen is what the platform offers instead.

Questions asked

Can you keep the old ProAgent display by engineering the TP1200 Comfort in WinCC flexible 2008?

No. WinCC flexible 2008 predates the Comfort Panels, so it cannot create or load a project for a TP1200 Comfort; the panel is engineered in TIA Portal only. The old example stays usable as a reference for what the operator must see, not as a deliverable.

Does the custom V13 sequence screen require changes to the PLC program?

No. The GRAPH function block already writes the current step and the status into its instance data block on every cycle, so the screen needs only new HMI tags that read those entries. You do not open, edit or recompile the sequence block, and its control logic stays exactly as validated.

Does ProDiag need its own license on the Comfort Panel?

Yes. ProDiag is a separately licensed option: the engineering seat needs the ProDiag option in TIA Portal as well as the runtime license on the panel, and the runtime checks for it at startup. The documented fix for a missing license is the matching option license, so arrange both before converting the production project.

Keep reading

  • Troubleshooting

    Why Installing WinCC Flexible Breaks TIA Portal V13

    No — TIA Portal V13 does not bundle WinCC Flexible; the Root Screen editor you already opened is its integrated WinCC editor, and that is where KTP panels are engineered. WinCC Flexible 2008 is the separate previous-generation tool, and installing it on the V13 machine is what stops TIA Portal starting, so uninstall it, run the V13 repair, and keep the two tools on separate machines or migrate the project.

    HMI and touchscreens

  • Explainer

    PowerTags vs the variables per device limit in TIA Portal HMI

    The variables per device limit in a panel's technical data counts every entry in the HMI tag tables, internal tags and PLC-linked tags together. A PowerTag is only a tag with an external link and is a PC runtime licensing counter, so size the project from the compile log's total tag count. The compiler can finish an over-limit build without a warning, so compare the counts yourself.

    HMI and touchscreens

  • How-to

    Unified Comfort Panel image updates when two versions are needed

    TIA Portal can hold only one installed panel image per major version and device type, so installing the V21 Update 2 image overwrites Update 1 on the engineering PC. Upgrade every affected panel to Update 1 first, then install Update 2, or extract image packages to separate folders and install them per panel through ProSave or USB.

    HMI and touchscreens