Why SIMOTION technology alarms stay missing on a TIA HMI

HMI and touchscreens Published 6 min read By IMDTouch engineering team

Short answer

Technology alarms are raised in the SIMOTION controller, never configured in the HMI, and reach the panel over an HMI connection once the SIMOTION TO alarms option is enabled in the runtime message settings. Basic Panels do not expose that option; Comfort Panels do. When events arrive without text, updating SCOUT TIA to SP1 HF5 or later and downloading again is the fix.

On this page
  1. Why does my HMI show no SIMOTION technology alarms?
  2. Does the panel have an HMI connection to the SIMOTION controller?
  3. Is the SIMOTION TO alarms option switched on?
  4. Why is the SIMOTION TO alarms option missing from the messages settings?
  5. Why do alarm events arrive without any alarm text?
  6. How do I test the fix with a real technology alarm?
  7. Which decision applies to which case?
  8. Questions asked

SIMOTION technology alarms never reach a TIA HMI until two conditions hold: an HMI connection whose partner is the SIMOTION controller, and the SIMOTION TO alarms option enabled in the panel's runtime settings. Only Comfort Panels expose that option; a Basic Panel cannot show these alarms at all. When alarm events arrive but carry no text, the engineering software is at fault, and a specific SCOUT TIA hotfix fixed that case. None of these messages is configured in the HMI alarm editor, because the controller raises them and delivers them automatically. The checks below run in the order that finds the failure fastest, and the last section gives the decision for each symptom.

Why does my HMI show no SIMOTION technology alarms? #

Two gates decide it: the panel needs an HMI connection whose partner is the SIMOTION controller, and the SIMOTION TO alarms option switched on in its runtime settings, plus on older engineering builds the update that makes the text arrive.

Technology alarms are raised on the SIMOTION side, not in the HMI project. In the case this article is built around, a SIMOTION D425-2 was engineered with SCOUT TIA inside a WinCC Professional V13 project; an axis raised alarm 20005 there, visible in the controller's online views, while the panel showed nothing. The panel's only job is to display what arrives; there is no discrete alarm, message number or trigger tag for these messages anywhere in the HMI alarm editor. The vendor's support documentation draws the same line for Alarm_S messages: they are configured in STEP 7 or in SIMOTION, never in the HMI engineering. Delivery is automatic once the routing is right, so a silent panel means one of the gates is shut, not an alarm you forgot to build.

Does the panel have an HMI connection to the SIMOTION controller? #

One connection in the connections editor must name the SIMOTION controller as partner; tags that read and write perfectly to another PLC prove nothing here, because the alarms follow the connection to the device that raises them.

Open the connections editor and confirm a connection between the HMI device and the SIMOTION CPU. If your panel already exchanges tags with the SIMOTION controller, that connection exists and this gate is open. If the tags run only to an S7 PLC on the same network, the SIMOTION's alarms have no route, so create the connection, then compile and download the panel. This is the same connection that carries operator commands, as running and stopping a SIMOTION CPU from a Comfort Panel HMI relies on. If you want the panel itself to report when that connection drops, showing a PLC connection fault on a Comfort Panel alarm display covers the setup.

Is the SIMOTION TO alarms option switched on? #

That is settled in one dialog, the HMI device's Runtime settings under Messages, where SIMOTION TO alarms must be enabled before the panel displays a single technology alarm, with every related message checkbox set on the affected project.

  1. Select the HMI device in the project tree and open its Runtime settings.
  2. Open the Messages settings.
  3. Enable SIMOTION TO alarms; in the case that later produced textless events, three related message checkboxes in this dialog all had to be set, so switch on every SIMOTION-related entry you find.
  4. Compile and download to the panel.

The option lives on the HMI device, not in the SIMOTION project and not in the controller's configuration, and it gates alarm delivery separately from tag traffic, which is why a panel can pass every tag test and still stay silent.

Why is the SIMOTION TO alarms option missing from the messages settings? #

The panel family decides whether the option exists at all: Comfort Panels expose the SIMOTION alarm checkboxes in the runtime settings, Basic Panels such as the KTP400 Basic do not, so on a Basic Panel the search never ends.

Panel family SIMOTION TO alarms option Technology alarms on the panel
Basic Panel, for example the KTP400 Basic Not offered Cannot be displayed
Comfort Panel Offered; must be enabled Shown once enabled and connected

Changing the HMI device in the project to a Comfort Panel makes the SIMOTION options appear in that same dialog; that device change is exactly how the constraint was pinned down in the field, after the same runtime settings had been searched in vain on the Basic unit. So the decision reads: if these alarms must be seen at the panel, the panel must be a Comfort Panel, and retargeting, recompiling and downloading are part of the job. Which Comfort Panel pairs with a given SIMOTION controller depends on the engineering tool versions on both sides, a question Comfort Panel and SIMOTION D compatibility: the tools decide works through.

Why do alarm events arrive without any alarm text? #

The engineering software is the culprit in that case: update SCOUT TIA to SP1 HF5 or later, rebuild the project and download it to the panel again, because that update is exactly what cleared events-without-text while every setting was already correct.

This is the deceptive case, because everything checks out: the option is on, the connection is up, and the panel visibly reacts when a technology alarm is raised, yet the alarm view shows no string. The fault sits in the engineering build, not in your configuration, so leave the connection and the alarm setup alone. Two practical points while you apply it. First, confirm which SIMOTION engineering package is actually installed, since difference between SIMOTION SCOUT, Drive ES, STARTER and S7 Technology is easy to mix up on an older engineering station. Second, if the hotfix installer aborts on the way, resolving extract failures during a SIMOTION SCOUT TIA hotfix installation covers that failure mode.

How do I test the fix with a real technology alarm? #

Raise one genuine alarm with the machine in a safe state, and judge the result on the alarm entry itself: number and wording both present means the chain works end to end, and nothing further is configured on the HMI side.

  • Bring the machine to a condition that produces a real technology alarm; the field case used the axis fault 20005 described earlier. Do this on the bench or with motion secured, never by provoking a fault on a running machine.
  • Confirm the new entry carries both its number and its wording in the alarm view.
  • Acknowledge it on the panel and confirm it clears like any other alarm in the view.
  • If the wording is still absent, verify the SCOUT TIA version actually installed on the engineering station before changing configuration again; the settings were never the problem.

Which decision applies to which case? #

Match the symptom to one of four rows: a missing option means a Basic Panel, a present-but-off option means enable it, silence despite healthy tags means a missing SIMOTION connection, and textless events mean the SCOUT TIA update.

What you observe Cause Decision
No SIMOTION entry anywhere in the messages settings The target is a Basic Panel Change the HMI device to a Comfort Panel; the options then appear
SIMOTION entries present but off Option disabled Enable SIMOTION TO alarms and the related checkboxes, compile, download
Option on, panel connected only to a PLC No HMI connection to the SIMOTION controller Create the connection in the connections editor, compile, download
Indicator reacts, no text in the alarm view Pre-fix engineering build Update SCOUT TIA to SP1 HF5 or later, rebuild, download

In every row the HMI alarm editor stays untouched, because technology alarms are never configured there; once the applicable decision is carried out, the controller's alarms keep appearing on the panel on their own.

Questions asked

Do I have to program Alarm_S messages to see technology alarms on the panel?

No. Technology alarms come from the SIMOTION technology objects and travel to the panel on their own once the option is enabled; Alarm_S is a separate mechanism programmed on the controller side. Neither kind is configured in the HMI project, so there is no alarm number to create in the panel's alarm editor for either.

Where are SIMOTION technology alarms configured if not in the HMI project?

On the controller side, with the technology objects in the SIMOTION engineering tool. The HMI project only decides whether the panel displays what the controller already raises. When an axis or another technology object produces an alarm, its number and wording originate there, which is why editing or recreating alarms in the panel leads nowhere.

The alarm indicator reacts but the alarm view stays empty, so is the connection broken?

No, and that symptom saves testing time: a reacting indicator proves the events already reach the panel, so the connection and the option are working and only the text transfer fails. That is the defect the SCOUT TIA SP1 HF5 update cleared, so install that update or later, rebuild and download instead of rewiring the network path.

Do I lose my configured screens when I change the Basic Panel for a Comfort Panel?

The project content carries over to the extent the Comfort Panel supports it: change the HMI device type in the project, recompile and download, and the SIMOTION options then appear in the runtime settings. Read the compile output for anything the new device handles differently, then retest the alarm view and your screens on the panel itself.

Keep reading

  • Troubleshooting

    Why Report System Error alarms are missing on Comfort Panels

    Report System Error alarms from a STEP 7 V5.x CPU reach an integrated WinCC flexible HMI directly, but a TIA Portal Comfort Panel reads them through a PLC proxy snapshot. Enable RSE in SIMATIC Manager, initialize the proxy data again in the TIA Portal HMI project, download to the panel, and the diagnostic alarms appear under HMI alarms > Controller alarm.

    HMI and touchscreens

  • How-to

    Showing a PLC Connection Fault on a Comfort Panel Alarm Display

    Enable the Comfort Panel's connection and disconnection system alarms, add an alarm buffer view, and drive a persistent HMI-local status tag from their events, because the system message shows for about 2 seconds and then leaves the screen while values freeze; a PLC clock heartbeat adds a stale-data check.

    HMI and touchscreens

  • Troubleshooting

    Getting Unconfirmed Alarm Status Out of a C-More Panel

    No tag on the EA9 exports alarm-confirmation state to the PLC, so the buzzer cannot follow the C-more confirm action. Latch the alarms in the PLC, acknowledge them with a panel pushbutton that writes a PLC bit, and run the buzzer while any alarm stays unacknowledged; the PLC to Panel Beep ON/OFF tag can mirror the same state onto the panel beep.

    HMI and touchscreens