IMDTouchKnowledge BaseShop main store

Explainer

Why Step 7 asks for the WinCC Component Object Manager package

HMI and touchscreens Published 8 min read

Short answer

The missing WinCC (Component Object Manager) message means the Step 7 project contains a WinCC V7 SCADA station whose COM server only a WinCC V7 installation or PCS 7 registers; WinCC flexible 2008 cannot supply it. Install the matching WinCC V7 version, or delete the leftover station and rebuild the project with Save As and reorganization; if the object sits on a WinCC flexible station, repair the Integration in Step 7 option instead.

On this page
  1. What is the WinCC Component Object Manager package?
  2. Why does an MP377 project ask for a WinCC SCADA package?
  3. How do I check what in the project needs the package?
  4. Can I still compile and download the MP377 while the message shows?
  5. How do I remove the leftover WinCC station with Save As?
  6. How do I install the Component Object Manager from WinCC V7?
  7. When is the real fault the WinCC flexible integration in Step 7?
  8. Which fix applies to your case?
  9. Questions asked

When SIMATIC Manager opens a Step 7 V5.x project and shows Missing software package > WinCC (Component Object Manager), it reports one specific thing: the project contains an object created with WinCC V7, the PC SCADA product, and your engineering PC has no WinCC V7 to serve it. WinCC flexible 2008 does not contain that component, so reinstalling Step 7 and then WinCC flexible with all its updates ends at the same dialog — a reinstall cannot add a package that neither setup contains. Two fixes close the message for good: install the WinCC V7 version the station needs, or remove the leftover station and rebuild the project with Save As and reorganization. A third, rarer case is a damaged WinCC flexible integration, repaired through its own setup option.

What is the WinCC Component Object Manager package? #

It is not an add-on for WinCC flexible: the Component Object Manager is the COM component that the WinCC V7 SCADA product registers on the engineering PC, and SIMATIC Manager reports it missing whenever a project holds an object created with that product. The name describes the job — it is the registered Windows component through which other engineering tools reach the objects of a WinCC station; when the registration is absent, those tools cannot resolve the station, and the dialog says so at project open.

Two products register it: WinCC V7.x, in both its Runtime and its Configuration packages, and PCS 7, which embeds the WinCC runtime. WinCC flexible 2008 registers nothing of the kind, and the WinCC generation inside TIA Portal does not stand in for it either. For the split between the three names, see WinCC V7.4, WinCC Flexible 2008 and TIA Portal compared: V7 is the SCADA that runs on a PC station, flexible 2008 is panel software, and the WinCC in TIA Portal is a different generation.

Why does an MP377 project ask for a WinCC SCADA package? #

Because the project still carries a WinCC V7 station: the panel backup was saved from a plant project that once included a SCADA PC station, and every open re-checks which packages each station in the project was edited with. At open, SIMATIC Manager walks the object list and asks Windows whether every required component is registered; everything absent lands in the dialog, line by line. The documented consequence: a project with missing software packages opens, but cannot be used to its full extent.

That is also why the reinstall loop fails. The setup of Step 7 V5.x registers its own components, the setup of WinCC flexible registers its own, and the Component Object Manager belongs to neither — the same software set reproduces the same message on a new PG and on an old one alike. Step 7 V5.x with the SIMATIC Manager is the pre-TIA project environment; what STEP 7 is in a PLC project and which one you need covers that background.

How do I check what in the project needs the package? #

Open the project despite the dialog and look at the component view: the objects under the SIMATIC PC station show which station keeps the requirement alive, and Programs and Features shows whether any WinCC V7 exists on the PC at all.

  • Read the dialog before dismissing it. The line WinCC (Component Object Manager) names the absent component; every further line names another missing package.
  • Expand the SIMATIC PC station in the component view. A WinCC station object there — the one with the CC symbol — is what keeps the requirement alive. Note at the same time which stations your machine actually uses.
  • Open Control Panel → Programs and Features and search for WinCC. Only WinCC flexible entries means the Component Object Manager is not installed; an entry for SIMATIC WinCC Runtime means it is installed, possibly without the Object Manager option.
  • Ask the plant whether a SCADA PC serves this machine and who maintains it. That answer picks the fix.

The behavior is documented as Siemens Industry Online Support entry 109815085, and it matches the cause described here.

Can I still compile and download the MP377 while the message shows? #

Yes, with care: the dialog is a warning, not a lockout, so the project opens and the WinCC flexible station can be compiled and transferred on its own — compile each station separately and you see which errors belong where. What the missing package costs you is the WinCC station itself: it sits in the tree as a placeholder you can neither open nor compile, while the rest of the project stays readable.

If the transfer is urgent, compile the WinCC flexible station on its own and transfer it to the panel; a clean compile there shows the missing package did not touch the panel data. Errors inside the panel station are a separate fault with its own cause — first check that the WinCC flexible build matches the one the backup was made with, before blaming this dialog. The message costs you the WinCC station, not the panel transfer.

How do I remove the leftover WinCC station with Save As? #

Work on a copy, delete the unneeded WinCC station from the tree, then run Save As with the reorganization option in its slow form and reopen the saved result: the leftover fragments go and the dialog with them.

  1. Copy the complete project folder and work only on the copy; the original stays untouched as the fallback for the running machine.
  2. Open the copy in SIMATIC Manager.
  3. Delete the WinCC station object under the PC station — and the whole PC station with it when nothing else on your machine uses it.
  4. Choose Save As, activate the reorganization (slow) option, and save into a new folder.
  5. Open the reorganized project: the missing-package dialog must be gone. Compile the WinCC flexible station and compare against the program on the running panel before any transfer.

If the component view shows no WinCC object and the message still appears, the project carries fragments of a station that was removed — the same Save As with reorganization is the tool for that state, because the reorganization rebuilds the project data and drops references whose objects no longer exist.

How do I install the Component Object Manager from WinCC V7? #

Install the WinCC V7 version the station was created with — from V7.0 up to V7.5, the setup of each registers the Component Object Manager — or, if WinCC is already installed, switch the option on through the Modify path.

  1. Find out which WinCC V7 version maintains the plant's SCADA; that version created the station and is the version to install. Your Windows must support it.
  2. Install from the plant's installation media. The Runtime package is enough to open and compile the station; Configuration is needed only when you must edit the SCADA project itself.
  3. Keep the Object Manager component enabled during setup — a custom setup with the box cleared installs WinCC without the very component SIMATIC Manager asks for.
  4. If SIMATIC WinCC Runtime already appears in Programs and Features and the message persists: right-click the entry, choose Change, then Modify, and enable the Object Manager check box; restart the PC when the setup finishes.

When the PC's Windows is newer than that WinCC version supports, do not force the install — take the reorganization path instead and leave the SCADA station to an engineering environment with a supported combination.

When is the real fault the WinCC flexible integration in Step 7? #

When no WinCC V7 object exists in the project at all: then the missing registration sits in the Integration in Step 7 option of WinCC flexible 2008, which a service pack or an update can overwrite or leave damaged. The tell-tale is a component view without any WinCC station, a WinCC flexible HMI station, and a dialog that still carries its WinCC line. The repair runs through the WinCC flexible setup:

  1. Start the setup of WinCC flexible 2008 and choose Modify.
  2. Set Integration in Step 7 to Will not be installed and let the setup finish.
  3. Start the setup again and set Integration in Step 7 to Installed on this PC.
  4. Restart the PG, reopen the project, and compile the WinCC flexible station.

A missing integration has a second symptom — no SIMATIC HMI Station in the insert-station dialog — covered in why the SIMATIC HMI Station is missing in STEP 7 Insert Station.

Which fix applies to your case? #

Match what the component view and Programs and Features showed to one row, and the fix follows directly — no project needs two of the three procedures.

What you found What it means Fix
WinCC station under the PC station, no SCADA on this machine Leftover from the plant project the backup came from Delete it, then Save As with reorganization
WinCC station, and the plant runs a WinCC V7 SCADA The station is live and needs its product Install the matching WinCC V7 with Object Manager enabled
No WinCC object, panel station integrated in WinCC flexible Damaged Integration in Step 7 Remove the integration, then install it again

A worked case, from a panel maintenance PC: Step 7 V5.6 with SP1 (K5.6.1.0), WinCC flexible 2008 SP5 Update 2, and a backup for an MP377 12 inch panel with order number 6AV6 644-0AA01-2AX0, with the dialog at every open. The component view shows 2 stations — 1 SIMATIC PC station holding a WinCC object and 1 WinCC flexible station for the panel — and the machine runs 0 SCADA PCs. Stations the machine needs: 1. Stations to remove: 2 − 1 = 1. After the copy was reorganized, the dialog stayed away and the panel station compiled clean, so the transfer to the new MP377 went ahead.

One dialog, two questions — is there a WinCC object, and does the plant run SCADA — and the fix follows from the answers.

Questions asked

Can I copy the Component Object Manager files from another engineering PC instead of installing WinCC?

No. The package is a COM registration that only the WinCC V7 setup writes into Windows, so copied files leave the registration incomplete and the message stays. Install the matching WinCC V7 version from the plant's installation media, or, where SIMATIC WinCC Runtime already appears in Programs and Features, run Change, then Modify, and enable the Object Manager check box.

Why does the missing-package dialog also list entries like S7-SCL?

The dialog shows one line per package that some object in the project was last edited with. An S7-SCL line means the PLC station carries source code that needs the S7-SCL option; a WinCC line means a WinCC V7 object sits somewhere in the project. Every line offers the same two ways out: install that package, or delete the objects that need it and reorganize.

Does opening and compiling the project on my PG consume a WinCC V7 license?

No. Installing WinCC V7 registers the Component Object Manager without a license key, and WinCC licenses are consumed where the runtime actually runs, on the plant's server. Engineering access from the PG needs no WinCC runtime license, so adding WinCC V7 for project maintenance leaves your WinCC flexible license as it is.

Can WinCC V7 and WinCC flexible 2008 share one engineering PC?

Yes. They are separate products with separate setup programs, and a PC that maintains both SCADA stations and panels carries both side by side, which is the normal engineering layout. The combination with documented trouble is WinCC flexible against TIA Portal V13 on one PC, which can break the TIA installation; WinCC V7 beside WinCC flexible is not that case.

Keep reading

  • Troubleshooting

    Why SIMATIC HMI Station Is Missing in STEP 7 Insert Station

    The SIMATIC HMI Station entry under Insert > Station appears only when WinCC flexible is installed with its Integration in STEP 7 component while STEP 7 is already on the PC. Reinstall WinCC flexible with that option ticked and restart; STEP 7 V5.4 with WinCC flexible 2008 SP2 is a working pair, while STEP 7 V5.7 is not supported.

    HMI and touchscreens

  • Explainer

    Why KTP400 Basic Color PN is missing in WinCC flexible

    The KTP400 Basic Color PN (6AV6647-0AK11-3AX0) is not configurable in WinCC flexible 2008 in any service pack; the missing catalog entry is a support boundary, not a fault in your installation. Engineering starts in TIA Portal V11 SP2. A STEP 7 V5.6 controller project is either migrated into TIA Portal or kept separate behind a PLC proxy.

    HMI and touchscreens

  • Comparison

    WinCC V7.4, WinCC Flexible 2008 and TIA Portal Compared

    WinCC V7.x is PC-based SCADA software, WinCC Flexible 2008 engineers operator panels and single PC stations and is discontinued as a standalone tool, and WinCC inside TIA Portal is the successor engineering platform alongside STEP 7. Decide by the target device and the exact project files on your engineering workstation, not by the shared WinCC name. STEP 7 is the PLC tool, not a WinCC product.

    HMI and touchscreens

How to build an A and not B visibility condition in EasyBuilder Pro