Short answer

New DB symbols stay out of WinCC Flexible's tag selection because the integrated project serves stale stored symbol data; rebuild, reconnect and compile do not refresh it. Save the STEP 7 project with File > Save as and the With reorganization (slow) option, open the renamed copy, and recompile the HMI configuration before any download.

On this page
  1. Why are new STEP 7 symbols missing in WinCC Flexible tag lists?
  2. Is the symbol actually saved in the STEP 7 project?
  3. Is the WinCC Flexible project really the one integrated in this STEP 7 project?
  4. Does the panel connection still point at the right PLC?
  5. How do I force STEP 7 to rebuild its symbol data?
  6. What proves a recovered tag before I download to the panel?
  7. Why are the HMI screens not synchronized with the project either?
  8. Questions asked

New data-block symbols that you have saved in SIMATIC Manager stay invisible in WinCC Flexible's tag selection even though rebuild, reconnect and compile all run clean. The cause is stale stored project data, not a wrong declaration: an integrated S7-300 project that has grown through many save cycles keeps serving the old symbol table to the HMI editor. The fix is a reorganized save of the STEP 7 project — File > Save as with the With reorganization (slow) option, under a new project name — then reopen the copy and recompile the HMI. Work the checks in order: confirm the declaration, confirm the project identity, reconnect the panel, then reorganize. Each check rules out a different fault, and the reorganized save is the only step that reaches data the others cannot touch.

Why are new STEP 7 symbols missing in WinCC Flexible tag lists? #

WinCC Flexible reads its symbol selection from the engineering data stored inside the STEP 7 project, and a project that has been saved through many edit-and-save cycles keeps serving the old stored table until the project is reorganized on save.

A symbol is a PLC-project name for an operand or data address; an HMI tag is the operator-side variable that points at it. The declarations belong to the PLC side, so a correctly extended DB is stored with the PLC project while the HMI editor keeps drawing its selection list from the stored project data as last delivered. Rebuild, reconnect and compile all act on data the editor already holds, which is why none of them brought the new members in — and the signature confirms it: symbols stored earlier stay selectable, the new ones are absent, both in the same DB. If you are sorting out which tool owns which half of the project, what STEP 7 is in a PLC project and which one you need covers that division.

Is the symbol actually saved in the STEP 7 project? #

Confirm the member exists in the saved declaration before any repair: open the DB in STEP 7, read each missing member's name, data type and offset — a member at byte 20, bit 0 shows as 20.0, for example.

Read the declaration line by line: each missing member needs a name, a data type and an offset, and the project must have been saved after the last edit, because an unsaved edit exists nowhere for the HMI editor to find. Then widen the check. A member inside a structure or array is reached only through its full path, and the HMI editor has to expand that hierarchy before the member appears — the same trap hides members from HMI tag import on other controller families, as why structure tags are missing from HMI tag import on an NJ describes. Last, look at the object you are configuring: a button, field or alarm accepts particular tag types, and a filtered selection list quietly hides a valid member of the wrong type. Correct any declaration or type error in STEP 7 before the recovery below — no save operation repairs a wrong declaration.

Is the WinCC Flexible project really the one integrated in this STEP 7 project? #

Open the HMI station from its object inside the SIMATIC Manager project you are editing; if your editor is working on a standalone copy, nothing you change in the PLC project will ever reach its tag lists.

Copied stations and similar project names make an old configuration look current, so compare objects rather than window titles. Open the WinCC Flexible station from the project tree, confirm the device is the one wired to the machine, and check that the connection object the tags use points at the PLC that holds the DB. Then browse one long-standing symbol and one new member through the same selection dialog. The old one resolving while the new one stays hidden confirms the stored data is stale and sends you to the reorganized save. A project that should be integrated but opens on its own has its own failure pattern, walked through in why a standalone HMI project will not open in your integrated editor.

Does the panel connection still point at the right PLC? #

Check the connection before you blame the symbol data: bring the panel back into HW Config, activate the connection in the WinCC Flexible project, and run Reconnect from the connection's right-click menu.

That is the vendor's documented sequence for PLC tag synchronization trouble with WinCC Flexible, and it is quick enough to run before anything heavier. Browse the DB again afterwards; these steps exist because connection-level staleness is a known cause of tags failing to synchronize. Keep the two failure classes apart while you work: a stale connection stops tag values at runtime, but it does not change which symbols the selection list offers. If the list still hides saved members after a clean reconnect, the remaining suspect is the stored project data, and only the reorganized save reaches it.

How do I force STEP 7 to rebuild its symbol data? #

Save the project with File > Save as and tick the With reorganization (slow) checkbox; save it under a new project name, open that copy in SIMATIC Manager, and the rebuilt symbol data appears in WinCC Flexible after you recompile the HMI.

Run it as a procedure, on the engineering PC:

  1. Save every pending PLC and HMI edit, so the copy carries the declarations and screens you need.
  2. Close the HMI editor and close the project in any other editor session.
  3. Choose File > Save as, tick With reorganization (slow), and save under a new project name; the run takes noticeably longer than a normal save, and that is the reorganization working.
  4. Open the new copy in SIMATIC Manager, then open the integrated WinCC Flexible station from inside that copy.
  5. Browse the missing DB members in the tag selection; they should now be offered under the intended connection.
  6. Assign one recovered symbol, check its connection, address and type, and compile the HMI configuration.
  7. Leave the original project folder untouched until the copy has been proven on the panel.

Transfer the recompiled runtime to the panel only during a planned stop: the transfer interrupts the operator screens while the machine may still be running.

If the button is needed before the copy is proven, assign the tag with a direct S7 address instead of a symbol; how to address S7 PLC outputs in a WinCC Flexible tag covers direct addressing in the tag table. Then run the reorganized save once. If the copy still hides the members, the fault is elsewhere: go back to the declaration, type-filter and connection checks rather than repeating the save.

What proves a recovered tag before I download to the panel? #

Treat the recovered list as unproven until one symbol has been assigned, compiled and reopened: check the tag's connection, address and data type against the saved DB declaration, then compile and close-reopen the project copy before any download.

Worked example, with an illustrative declaration: DB20 holds a member named Batch_Count at byte 20, bit 0. The recovered HMI tag must resolve to exactly that operand — DB number 20 from the block identity, byte 20 from the declaration offset, bit 0 from the declaration bit — which the tag's address field shows as DB20.DBX20.0. The proof is a bench write: write 1 to the tag from the HMI and watch DB20.DBX20.0 in the PLC's online status; that exact bit must flip, because a healthy but misrouted tag flips a different bit or nothing at all. Then close and reopen the project copy and confirm the assignment and the screen list persist.

Compile diagnostics must show no unresolved-reference or type errors for the changed tags before anything goes to the panel. Pulling a copy back from the panel is not a recovery path: why an uploaded HMI copy is not an editable project explains what an upload actually returns.

Why are the HMI screens not synchronized with the project either? #

Missing screens come from the same stale stored data, not from a communications fault: screens are engineering objects kept with the project, while tag values are exchanged only at runtime through the configured connection.

One stale store hides both, which is why your screen list and tag list drifted together. The division of work between the two tools — the PLC project owns blocks and symbols, the HMI station owns screens and tags, joined through the shared project — is mapped in how WinCC and STEP 7 work together in a PLC project. After the reorganized save, compare the copy's screen list with the panel; the missing screens should return with the symbols. If one list recovered and the other did not, suspect device selection or project identity rather than the stored data, and rework the identity checks above.

The decision, case by case: a member never saved — finish the edit and save in STEP 7. Wrong station or wrong project open — switch to the integrated one before anything else. A connection that no longer exchanges — reconnect in HW Config, activate the connection in WinCC Flexible, run Reconnect. Saved members still hidden after all three — one File > Save as with With reorganization (slow), recompile, then the bench proof above before any download.

Questions asked

Does a reorganized save change anything in the PLC program or on the running panel?

No. The reorganization rebuilds the project's internal storage on the engineering PC, and blocks, symbols, screens and connections are carried into the copy unchanged. The PLC keeps running its loaded program and the panel keeps its last transferred runtime until you deliberately download the recompiled configuration, so the save itself can be made while the machine is in production.

What warns me before project data goes stale enough to hide symbols?

Rising save and open times in SIMATIC Manager. The same reorganized save is the vendor's documented remedy for general SIMATIC Manager slowdown, so a mature project that opens slowly or browses symbols sluggishly is the early case of the fault that later hides new DB members from WinCC Flexible tag lists.

Should I rename the reorganized copy back to the original project name?

No. Keep working in the reorganized copy and retire the original once the panel is proven. The new name exists so both projects can sit side by side during testing; shuffling names back afterwards invites opening the wrong folder, and one current project folder per machine is what keeps every editor's tags and screens consistent.

Who needs to close the project before the reorganized save runs?

Everyone. Close your own HMI and STEP 7 editor sessions, and make sure no colleague has the same project open on another PC. The save copies the project's stored data, and a session left open can hold unsaved edits or locks that end up missing from the reorganized copy.

Keep reading

  • Troubleshooting

    Why SIMATIC HMI Station Is Missing in STEP 7 Insert Station

    The SIMATIC HMI Station entry under Insert > Station appears only when WinCC flexible is installed with its Integration in STEP 7 component while STEP 7 is already on the PC. Reinstall WinCC flexible with that option ticked and restart; STEP 7 V5.4 with WinCC flexible 2008 SP2 is a working pair, while STEP 7 V5.7 is not supported.

    HMI and touchscreens

  • Explainer

    How WinCC and STEP 7 Work Together in a PLC Project

    STEP 7 configures and programs the Siemens PLC; WinCC builds the operator screens that read and write selected PLC variables over a configured connection. The boundary between the tools is the tag: STEP 7 owns the variable, WinCC owns the display and command objects bound to it.

    HMI and touchscreens

  • Troubleshooting

    Why a Copied WinCC Picture Does Not Show Its Tag Squares

    The squares vanish for two compounding reasons: the copied picture references the Modbus tag by name only, and its Display mapping hides the square on FALSE — exactly what an unresolved or bad-quality tag evaluates to on the working server. Transfer the project with the copy tool, and set Display to Yes on the NO/False row if the square must stay visible in both states.

    HMI and touchscreens

Why two Vijeo Designer HMIs cannot share one user list