Troubleshooting
Why Vijeo Design'air Plus cannot connect when ping succeeds
Short answer
A ping from the PC proves only ICMP reachability from that PC, not that the tablet has a path or that the panel's app service is reachable. Confirm in order: the project running on the HMISTU 5T contains the enabled function, the tablet is on a subnet with a route to the panel's current address, and the app's documented service is permitted.
On this page
- Why does ping succeed while the app cannot connect?
- What must be true on the panel before the app can connect?
- How do I know the running project includes the activated function?
- Why does the tablet fail when the ping came from the PC?
- Which IP address goes into the app?
- What can block the app's traffic while ping passes?
- What do I fix first when ping works but the app does not?
- Questions asked
Your ping proves exactly one fact: the PC reached the panel's IP address with ICMP echo traffic. It says nothing about the tablet's path, about the project the HMISTU 5T is actually running, or about whether the panel's remote-access service may accept a session. It was also run from the PC, not from the tablet, so the tablet's reachability is unproven. Work the fault in evidence order: confirm the project running on the panel contains the enabled function, confirm the tablet sits on a subnet with a route to the panel's current address, then confirm the app's documented service is permitted. Failures of this shape are almost always one of those three.
Why does ping succeed while the app cannot connect? #
Because they are two different tests: ping exchanges ICMP echo messages, and ICMP, specified in RFC 792, carries control messages only — no application data, no session state. The app must find the panel's service listening, open its session, and keep that session alive.
An echo test sends one request and waits for one reply. Success means a layer-3 path existed, for ICMP, between those two endpoints, at that moment. Everything else the app needs is untested: a listening service on the panel, a permitted session, and the same path from the tablet. Devices in between — access points, routers, firewalls, endpoint filters — handle ICMP and the app's service independently, so one can pass while the other is dropped without any message. The same gap is why engineers elsewhere chase a TIA Portal HMI connection failure when ping succeeds. Use the port and protocol documented for your app release and target; a port you guessed that happens to answer proves nothing about the app's service.
What must be true on the panel before the app can connect? #
Three conditions, all panel-side: the exact panel must be a documented target for your app release, the application actually running on the panel must have the remote-access function enabled, and the panel's communication settings must match what that app release documents.
- Panel identity. A name like "HMISTU 5T" is shorthand. Read the full catalog reference from the panel label or the project's hardware configuration and check it against Schneider Electric's compatibility documentation for your app release. Vijeo Designer addresses the Harmony and Magelis HMI ranges, and app support is per panel and firmware.
- App and project. The app release must be one your panel serves, and the application downloaded to the panel — not the one open in Vijeo Designer — must contain the enabled function.
- Network target. The address entered in the app must be the panel's current address at the time of the attempt.
One distinction worth making early: the tablet app and the browser are two different remote-access routes. The browser route is the WebGate server, enabled in Vijeo Designer under Project Settings → WebGate, with its own client covered in where to find the Vijeo Web Gate client 6.3 installer. Schneider Electric also publishes a quick setup guide for Vijeo Design'Air; run the panel through it once the identity is confirmed.
How do I know the running project includes the activated function? #
You verify the deployed application, not the workspace: enabling the function in Vijeo Designer edits the project on your engineering PC, while the panel keeps executing whatever was last downloaded to it. The setting reaches the panel only inside a downloaded project.
You activated the function with Vijeo Designer, which is a project property for the target panel. Until a build containing that property is transferred and starts, the panel's service is unchanged — so verify the HMI project version running on the panel before trusting any panel-side setting. If the panel is not on your bench, downloading a Vijeo Designer project to a remote HMI over the existing route is the transfer step. Decision: if the running version does not match the workspace build that has the function enabled, download that build, let it start, and retest from the tablet before touching the network.
Why does the tablet fail when the ping came from the PC? #
Because the ping and the app ran on different devices: the PC's echo proves the PC has a path, and the tablet's Wi-Fi icon proves association with an access point, not membership of the panel's subnet. Test reachability from the tablet before touching the panel.
- On the tablet, open the Wi-Fi network details and read the connected SSID, the assigned IP address and the subnet mask.
- On the panel, read the current IP address and mask from its network settings.
- Compare the two networks, not the two signal icons.
Worked example (illustrative addresses). The tablet shows address 192.168.10.45 with mask 255.255.255.0. The panel shows 192.168.1.30 with mask 255.255.255.0. Tablet network: 192.168.10.45 AND 255.255.255.0 = 192.168.10.0. Panel network: 192.168.1.30 AND 255.255.255.0 = 192.168.1.0. The networks differ (192.168.10.0 ≠ 192.168.1.0), while the PC that pinged successfully sits on 192.168.1.0/24 — exactly why its ping worked and the tablet's session cannot start. Decision: join the tablet to the SSID that serves the panel's subnet, or have a route added for the app's service; no app setting connects across that mismatch.
Two wireless traps produce the same symptom even with matching subnets: a guest SSID that bridges nowhere, and client isolation, which lets a station reach infrastructure while blocking station-to-station traffic. The address side of Wi-Fi fails for PCs too — the sequence behind why a PC fails to reach an HMI when Wi-Fi owns its address is the tablet's check as well: read the assigned address, not the icon. Where the segment is uncertain, have the administrator confirm the SSID-to-VLAN mapping and the isolation setting.
Which IP address goes into the app? #
The panel's current address, read from the panel's own network settings at the moment of the attempt — not the address configured inside the project, and not one that worked last year. A panel that obtains its address by DHCP can hold a different address than any record on your desk.
Stale targets come from three places: the panel's DHCP lease renewed onto a different address, the panel was swapped or reset to defaults, or the address in the app was typed once and never revisited. One mistyped octet points the session at a different device or at nothing at all. Read the address on the panel, enter exactly that in the app, and retest. Decision: once the session works, set the panel to a static address outside the DHCP scope — a moving panel address will break the app again on the next lease.
What can block the app's traffic while ping passes? #
Any device on the path that treats the two differently: wireless controllers running client isolation, routers or firewalls whose rules permit echo but filter the service's port, and VLAN boundaries with no rule for the app at all. Ping survives every one of those while the session cannot start.
The fastest discriminator is a second client on the same wireless segment, running the same app or the documented client:
- The second client connects, the tablet does not — the fault is tablet-side: app release, typed address, SSID membership.
- Neither client connects, both ping — the fault is panel-side or path-side: deployed project, service configuration, or an access rule.
When you ask for a rule, ask for the narrow one: permit the documented service between the tablet's subnet and the panel address, and do not expose the panel to a guest or untrusted network to make a test pass.
What do I fix first when ping works but the app does not? #
Change one thing at a time, in this order — deployed project, tablet subnet, current address, service permission — because each check either fixes the fault or removes a whole branch of causes. The mapping below turns each finding into its single fix.
- Finding: the panel is not running the build with the function enabled. Fix: download that build, confirm it starts, retest from the tablet.
- Finding: the tablet sits on a different subnet. Fix: move it to the production SSID, or have routing added for the app's service only.
- Finding: client isolation is on. Fix: the wireless administrator disables station-to-station blocking for the industrial SSID.
- Finding: the app targets a stale or mistyped address. Fix: enter the panel's current address, then make the panel static.
- Finding: ICMP is permitted, the service is filtered. Fix: permit the documented service from the tablet's subnet to the panel, nothing wider.
- Finding: a second client connects, the tablet does not. Fix: correct the tablet's app release, address entry, or SSID membership.
A working result is an app session showing that panel's screens with live data updating — an echo reply was never that.
Questions asked
Does the free Vijeo Design'Air edition connect differently than Plus?
No. The panel-side requirements are identical, and Schneider Electric's support note for the free edition's repeated 'Connection failed' message troubleshoots it with connection checks of the same kind used here: the deployed project, the panel's current address, and the network path. The editions differ in features and licensing, not in how the session reaches the panel.
Which panels can this app reach?
Vijeo Designer builds applications for the Harmony and Magelis HMI ranges, and the app is the companion client for those panels. Whether your specific unit serves the app session depends on documented support for your app release and the panel's firmware. Read the full catalog reference from the label, since a name like 'HMISTU 5T' is shorthand, and check it against the compatibility documentation.
Can the tablet connect from outside the plant network?
Only across a real route to the panel's address, normally a VPN terminated on the plant network. Once routing exists, the same order of checks applies: the running project, the tablet-side addressing of that route, the panel's current address, and permission for the documented service between them. The app cannot reach a private address across the internet on its own.
The app connected once, then stopped updating. Is that the same fault?
Usually the same family. A session that opens and then freezes points at the path or the service dropping mid-session: Wi-Fi roaming between access points, a panel restart after a project download, or the service restarting. Reconnect to the panel's current address; if it freezes again, note the exact time it dropped and check the wireless segment and the panel's restart behavior first.