HMI and touchscreens Published 5 min read

Short answer

Greyed Router IP and Control & Data TCP Port fields in Vijeo Designer Basic 1.1 mean the download-through-a-router function is not exposed for that edition and target pair — the GXU 3512 keeps downloading on the local network. Confirm the edition first: the demo cannot connect to a device at all, and the trial modes run 21 days or 42 days from install.

On this page
  1. What the deactivated fields tell you
  2. Rule out the demo and trial editions first
  3. Working the case: Basic 1.1 to a GXU 3512 on a 30-day-old installation
  4. Keep the local download as the controlled path
  5. What a real remote path would take
  6. Decisions for each outcome
  7. Questions asked

Deactivated Router IP and Control & Data TCP Port fields in Vijeo Designer Basic 1.1 are not a VPN setting you are missing. On a station whose GXU 3512 still accepts a download on the local network, they mean the router-translated download function is not exposed for that edition and target pair, and no routing change on your side switches it on. The working path is the local download you already have. The one thing to verify first is the installation itself: the demo edition cannot connect to a device at all, and that case — not the pair — is fixed in software, not in the network.

What the deactivated fields tell you #

The Router IP and the Control & Data TCP Port numbers carry the address translation for a download that passes through a router. Vijeo Designer Basic 1.1 draws them deactivated when that function is not offered for the selected target, here the GXU 3512. The state is a capability statement, not a permissions problem or a half-configured tunnel.

  • A local download that completes proves the project, the driver, the target address and the physical path.
  • Router IP and Control & Data TCP Port deactivated means router-translated download is not exposed for this edition and target pair.
  • Both observations together leave nothing to fix in the VPN: the function is absent, not misconfigured.

This family of engineering tools keeps network fields read-only wherever a function is unsupported; a vendor FAQ answers no to changing the panel's own IP from the tool for the same reason. Greyed controls flagging a configuration-level cause rather than a fault is a pattern across platforms — why grayed buttons in Studio 5000 mean no target is selected, not a PLC logic fault.

Rule out the demo and trial editions first #

The vendor splits the free installations by capability, and that split decides where your fault lives. The demo edition does not allow a connection to a device, so it cannot complete any download. The trial modes give full functionality on a clock: Schneider Electric's installation FAQ documents one limited to 21 days and one limited to 42 days from the install date. Read the edition in the About/licensing information of the installed software before you touch anything else.

The fast discriminator is the local download. If it completes, your installation can connect to the GXU 3512 and the demo theory is dead; the deactivated router fields then point at the edition and target pair. On this station, Basic 1.1 is the software paired with the GXU 3512 — the pairing question is exactly which HMI software works with which HMI panel hardware.

Working the case: Basic 1.1 to a GXU 3512 on a 30-day-old installation #

Inputs.

  • Software: Vijeo Designer Basic 1.1, the installed edition on the station.
  • Target: GXU 3512 operator panel.
  • Symptom: Router IP and Control & Data TCP Port fields drawn deactivated.
  • Working result: download to the panel completes on the local network.
  • Documented limits: the demo edition cannot connect to a device; trial modes expire at 21 days, or 42 days from the install date.
  • Example input, illustrative rather than from the station: the copy was installed 30 days before this check.

Rule in words. Compare the time since install against the documented trial windows, then let the local download discriminate: a demo, or a trial past its window, cannot complete a device download.

Arithmetic. 30 days elapsed − 21-day window = 9 days past the shorter trial mode. 42-day window − 30 days elapsed = 12 days remaining under the longer one. Under the first mode the trial would already be expired; under the second it still runs.

Result. Either way, the installation completes the local download to the GXU 3512 — behavior a demo cannot produce. The software has its device connection; the deactivated router fields are the capability of the Basic 1.1 and GXU 3512 pair.

Decision. The local download is the trip point. While it succeeds, commission on the local network and treat remote download as unavailable for this pair; the day it fails too, the investigation moves to the installation and its licence, not to the network.

Keep the local download as the controlled path #

  1. Read the edition in the About/licensing information and record it next to the target model.
  2. Put the engineering PC on the panel's network and run the download exactly as before.
  3. Confirm the tool reports completion and that the GXU 3512 starts the intended application.
  4. Leave that route written down as the recovery path, and run any remote experiment after it, never instead of it.

Do not substitute guessed TCP port numbers or router addresses for the deactivated fields; an undocumented value that appears to work is not a supported configuration.

What a real remote path would take #

The router fields serve the case where the download crosses an address-translating router. A VPN that routes the panel's subnet to the engineering PC removes that case: the ordinary local-style download applies, and downloading a Vijeo Designer project to a remote HMI over VPN covers that configuration for supported targets. If router-translated download is a hard requirement, get it in writing from local Schneider Electric support for the exact Basic version and the GXU 3512; in a pair that exposes the function, the fields are editable and take the documented Router IP and Control & Data TCP Port values.

Never forward public internet ports straight to the panel as a substitute — that puts an unauthenticated transfer service on the open internet.

Decisions for each outcome #

What you observe What it is Decision
Router IP and Control & Data TCP Port deactivated, local download completes Router-translated download not exposed for Basic 1.1 with the GXU 3512 Commission on the local network; confirm vendor support before any router configuration
Local download fails too Installation or target communication fault Fix edition, licence and communication first; a VPN cannot correct it
Fields editable after moving to a documented pair Function exposed Enter the documented Router IP and Control & Data TCP Port values and test the transfer

In every row the local download remains the recovery path — keep it working before anything else is attempted.

Questions asked

Why are the Router IP and Control & Data TCP Port fields greyed out in Vijeo Designer Basic?

Because the download-through-a-router function is not exposed for the selected target and edition. The fields are drawn deactivated when that combination does not offer the function, so no network setting on your side will switch them on. They become editable only in a software and target pair that documents router-translated downloads.

How can I tell whether my installation is the demo edition?

Read the edition string in the About or licensing information of the installed software. The functional check is faster: the demo edition cannot connect to a device at all, so any download that completes rules it out. Trial modes run 21 days, or 42 days from the install date, and an installation older than that which still downloads locally is a full edition.

Can I enable the deactivated fields by editing project files or configuration values?

No. Whether the router fields are editable is decided by the edition and target pair, not by a setting you can flip, and undocumented edits are not a supported configuration. The supported routes are a software and target combination that documents router-translated download, or a VPN that routes the panel's subnet so the ordinary local-style download applies.

Does the greyed-out state affect local downloads to the GXU 3512?

No. The router fields belong to the address-translated remote path only; the local download never reads them. That is why a station can download reliably on the local network while the Router IP and Control & Data TCP Port fields stay deactivated — the two paths are independent.

What exactly should I ask Schneider Electric support?

Ask whether remote application download is supported for Vijeo Designer Basic 1.1 with the GXU 3512 target, and if not, which software and target combination documents the Router IP and Control & Data TCP Port fields for your panel family. Getting that answer in writing settles whether the deactivated fields are by design before any router or VPN work starts.

Keep reading

  • Troubleshooting

    Why a PanelView 5310 reverts to the old project after reboot

    Nothing usually reverts. A completed View Designer download replaces the application a PanelView 5310 runs, and the download dialog has no startup-project selector. In the reported case the terminal is almost certainly running the new build while a copied screen still displays the old Revision A text label: prove source, destination, and download completion, then verify one marker across a single controlled restart.

    HMI and touchscreens

  • Troubleshooting

    Why Vijeo Designer direct IO variables show faded

    Faded, dotted %I and %Q values on a link where %M and %MW still read mean the v6.2 file upgrade broke the variable records' equipment and address linkage, not the communication path. Re-link and retype one I/O tag against the M221 equipment, fix the rest through the exported variable list, and rebuild the equipment entry only if the retyped tag still fades.

    HMI and touchscreens

  • Checklist

    Checking HMI engineering software before a panel replacement

    Vijeo Designer's current line is 6.2, ending at service pack SP12 (version 6.2.12, 26 January 2024). Newer HMI panels are engineered only in Operator Terminal Expert and cannot be added to Vijeo Designer by updating it. Before ordering a replacement, record your installed version, match the target designation exactly, and let the replacement's documentation decide between a drop-in and a migration.