IMDTouchKnowledge BaseShop main store

Troubleshooting

Why Weintek MPI tags stay blank with a flashing comm LED

HMI and touchscreens Published 7 min read By IMDTouch engineering team

Short answer

The LED shows polling, not data. The verified fix on an MT8070iE to a VIPA CPU was COM1 in RS485/2/4W mode — RX− pin 1 to CPU pin 8, RX+ pin 2 to CPU pin 3, pin 5 to pin 5 — with the HMI and the CPU port both set to 19.2K, and the failed setup was COM3 at 187.5K.

On this page
  1. Why do MPI tags stay blank while the HMI comm LED flashes?
  2. Which port and cable wiring actually worked with the VIPA CPU?
  3. Do I need an MPI-to-RS485 converter for this connection?
  4. What baud rate and frame format do both ends need?
  5. Why did 187.5K fail when the panel datasheet lists it?
  6. How do I prove the MPI link is passing real data?
  7. What if the tags are still blank after the change?
  8. Questions asked

Blank MPI tags with a flashing communication LED mean the panel is polling a link that returns nothing usable. On an MT8070iE wired to a VIPA CPU, the verified fix was to leave COM3, put the link on COM1 in RS485/2/4W mode, and run both ends at 19.2K: RX− pin 1 to CPU pin 8, RX+ pin 2 to CPU pin 3, ground pin 5 to CPU pin 5, keeping 8 data bits, even parity and 1 stop bit. The failed setup — COM3 at 187.5K — kept the LED blinking without one read or write updating, while the same project ran over Ethernet, which isolates the fault to the serial link.

Why do MPI tags stay blank while the HMI comm LED flashes? #

The LED only shows that the port is active under its current settings, not that valid replies are arriving; on this link the panel blinked on COM3 at 187.5K, no read or write value updated, and the "PLC no response" alarm stayed silent until the cable was unplugged.

Two observations from the failing installation show why the LED proves nothing. Changing the COM parameters stopped the blinking, so the LED follows the port configuration rather than the data. And the alarm appeared only on a physical disconnect, so its silence while connected was never evidence of good traffic. Because the very same project worked over Ethernet, the tag addresses and CPU data were fine; what remained at fault was the serial path — port, wiring and line settings. An Ethernet-side failure between a VIPA CPU and a PC runtime is a different fault, and why WinCC flexible 2008 PC Runtime will not reach a VIPA PLC covers that one.

Which port and cable wiring actually worked with the VIPA CPU? #

The working link used COM1 in RS485/2/4W mode with a direct 9-pin cable: RX− on pin 1 to CPU pin 8 (D−), RX+ on pin 2 to CPU pin 3 (D+), and ground on pin 5 to CPU pin 5, with no converter anywhere in the line.

The failed cable had followed the COM3 RS-485 drawing, data− on pin 6 and data+ on pin 9 at the panel, into the same CPU pins. The CPU side never changed — pin 3 is data+, pin 8 is data− and pin 5 is the reference ground, the 9-pin MPI assignment the S7-300 CPU manual documents — so only the panel end of the cable was rebuilt. Weintek publishes per-model pin tables as part of its PLC connection guide; use the COM1 column for RS485/2/4W, not the COM3 column you may have wired first.

Item Failed setup Working setup
HMI port COM3, RS-485 2-wire COM1, RS485/2/4W
HMI data− pin 6 pin 1 (RX−)
HMI data+ pin 9 pin 2 (RX+)
CPU side pin 8 D−, pin 3 D+, pin 5 GND pin 8 D−, pin 3 D+, pin 5 GND
Rate 187.5K 19.2K at both ends
Frame 8 data bits, even parity, 1 stop bit 8 data bits, even parity, 1 stop bit
Converter none none

Check the finished cable pin to pin with a meter, panel power off, before blaming software. This is the reported result for an MT-series panel driving a VIPA 312C over MPI — field-verified for that pairing, not a blanket statement about every Weintek model's MPI behavior.

Do I need an MPI-to-RS485 converter for this connection? #

No: MPI is an RS485 (EIA-485) interface at the electrical level, Weintek's connection guide shows a straight 9-pin cable for this driver, and the working installation was a direct cable between the panel's COM1 and the CPU's MPI socket.

The converter habit comes from the PC side. A programming laptop has no RS485 MPI socket, so it needs an adapter to talk to the CPU; an HMI with an RS485 port that supports MPI already speaks the right electrical language. A converter added to a link like this only adds connectors, power and one more thing to misconfigure.

What baud rate and frame format do both ends need? #

Set the HMI to 19.2K and the CPU's MPI port to the same rate, keeping 8 data bits, even parity and 1 stop bit at both ends; the failing setup ran at 187.5K and never exchanged usable data, and a rate mismatch produces exactly this blank screen.

In EasyBuilder Pro the settings live in the PLC driver's communication parameters — port COM1 with the rate and format above — followed by a project transfer to the panel. On the CPU side only the rate is yours to set, as a parameter of the MPI interface in the hardware configuration; MPI fixes the frame on that port, so there is no parity or stop-bit setting to chase inside the CPU.

The frame format still matters at the panel end, because a mismatched parity or stop-bit setting corrupts characters the same way it does in any serial exchange — what parity and stop bits change in a Modbus read shows that mechanism on another protocol.

The lower rate has a measurable cost, and the arithmetic is simple. MPI frames carry 11 bits per character: 1 start bit, 8 data bits, 1 even-parity bit, 1 stop bit. At 19,200 bit/s the line moves 19,200 ÷ 11 ≈ 1,745 characters per second, against 187,500 ÷ 11 ≈ 17,045 at the old rate — 187,500 ÷ 19,200 ≈ 9.8 times the throughput. A screen polling a few dozen tags will not feel the difference; a dense screen with cyclic exchanges will update visibly slower, so budget the polling before you blame the panel.

Why did 187.5K fail when the panel datasheet lists it? #

The MT8070iE datasheet documents MPI at 187.5K on COM1 and COM3 RS-485 2-wire, with one port in use at a time — a statement of what the port can do, not a promise about a given CPU's port; with this VIPA CPU, usable data flowed only at the lower rate.

Two things changed between the failed and working setups, the panel port and the rate, so the evidence establishes the working pair rather than which single change would have sufficed alone. Commission on the pair as documented here. If you want to isolate the variables, do it on the bench with the cable fixed, change one setting at a time, and restore the verified pair after each test.

Accept the link only when a value you know is changing updates on the screen and a controlled write lands at the address you aimed at; in the failing state neither happened, so neither the LED nor the alarm's silence counted as evidence.

Run the acceptance in this order:

  • Read a value you know is moving — a counter you increment from the programming tool, or the CPU's clock byte if one is enabled — and watch it change on screen.
  • Perform one controlled write to a spare address that drives nothing, and confirm the value lands where you aimed.
  • Unplug the cable and confirm "PLC no response" appears; that proves the alarm path works, so its silence while connected was meaningless.

Do the write on an isolated bench against a spare, non-connected address — never against an output on a running machine. The same wire-then-verify discipline resolved an RS422 link that also showed activity with no data; the FX3GE RS422 to HMI wiring fix for no response walks through that case.

What if the tags are still blank after the change? #

Re-open the PLC driver in EasyBuilder Pro, confirm it is the CPU300 MPI entry, transfer the project again, and confirm the CPU actually received its new port rate — a similar blank-tags state on this panel family was cleared by reselecting the driver and downloading once more.

Then work down the list:

  • Match the driver entry to the port you wired: the PLC list carries a CPU 300 Ethernet entry beside the MPI one.
  • Confirm the hardware configuration carrying the CPU's new rate was downloaded; a rate set on the laptop and never loaded leaves the CPU at its previous speed.
  • Keep the MPI driver on one COM port only.
  • Re-check the cable pin to pin against the table above, panel power off.
  • After any driver change, transfer the project, then repeat the changing-value read and the controlled write.

Whatever you try, return to the verified baseline — COM1 in RS485/2/4W mode with both ends at the matching rate — before the next test.

Questions asked

Which PLC driver entry do I select in the Weintek software for this MPI link?

Choose CPU300 MPI, the entry made for the serial MPI port. The PLC list also carries a separate CPU 300 Ethernet entry for the TCP port, and the two are not interchangeable: the entry must match the port you actually wired. Picking the Ethernet entry while the cable sits on COM1 leaves the serial link unused and the tags blank.

Where do I change the MPI port speed on the CPU, and what happens if I never download it?

The rate is a parameter of the CPU's MPI interface inside its hardware configuration; change it there, then download that configuration to the CPU. If you set the rate and skip the download, the CPU keeps its previous speed and the screen stays blank no matter what the panel does. Afterwards, point your programming PC's connection at the new rate too, or the next online session will not reach the CPU.

My screens are busy, so do I have to live with the slower link?

On this link, yes: keep the verified pair and cut the load instead. Poll fewer tags, drop cyclic exchanges nobody watches, and split dense screens across pages. If throughput still hurts, change the topology rather than the rate: a CPU with an Ethernet port and the matching CPU 300 Ethernet driver gives you the fast path, and the MPI link stays for programming or as a backup.

Will the same cable and settings work on a Siemens S7-300 CPU?

Yes. The MPI socket on S7-300 CPUs uses the same 9-pin assignment, with pin 3 as data plus, pin 8 as data minus and pin 5 as ground, so the cable does not change, and the CPU 300 driver family covers both brands. Set the port rate identically and accept the link the same way: a changing read value on screen and one controlled write, never the LED.

Keep reading

  • Troubleshooting

    FX3GE RS422 to HMI wiring fix for no response

    Wire HMI COM1 receive to the FX3GE transmit pair, the HMI transmit pair to the PLC receive pair with matching polarity, and land signal ground on PLC pin 5. The failed map had the transmit pair reversed and ground on pin 3; the crossed, polarity-matched map with ground on pin 5 restored communication.

    HMI and touchscreens

  • Troubleshooting

    Why a Weintek HMI Will Not Connect to a Mitsubishi FX PLC

    A Weintek HMI that reports no connection to a Mitsubishi FX over an SC09-style cable almost always has a physical-layer problem: the FX port is RS-422, the cable pinout at both ends must match the documented assignments, and the HMI's USB port is not a PLC serial port. Verify driver, port, settings and wiring in that order.

    HMI and touchscreens

  • Troubleshooting

    Fixing HMI PLC Communication Timeout Over Serial

    A serial HMI-to-PLC timeout means the panel sent a request and no valid reply arrived before its timer expired — not that the link is slow. Match the baud rate and parity in the PLC port setup and the HMI driver settings first, then verify the cable pinout, the selected ports and the ground bond. At 9600 baud a full poll cycle takes about 28 ms of wire time, so a failing one-second timeout points to settings or wiring, never the timer.

    HMI and touchscreens

Why a new HMI editor screen stays blank or black