Why WinCC DataMonitor Viewer RT reports unknown user or bad password

HMI and touchscreens Published 5 min read By IMDTouch engineering team

Short answer

When WinCC DataMonitor Viewer RT reports an unknown WinCC user or bad password, the credentials are usually fine. In a documented V7.2 case the cause was a missing start picture in the WinCC user's Web Options. Set the correct Basic Process Control web start picture, the MainControl.asp default page and the right group memberships.

On this page
  1. Why does Viewer RT reject a user whose password is correct?
  2. How do I set the web start picture in WinCC User Administrator?
  3. Which start picture does a Basic Process Control web client need?
  4. Why are the picture-selection buttons missing on the client?
  5. Which Windows and WinCC accounts and groups does DataMonitor need?
  6. Does a 64-bit Windows system cause this error?
  7. Questions asked

Viewer RT's "unknown WinCC user or bad password" error usually means the WinCC user has no start picture assigned under Web Options, not that the credentials are wrong. In a documented DataMonitor V7.2 case, the remote PC reached the web page, the username and password were correct and the Web Monitor box was checked; assigning the start picture cleared the error on the next connection. Work through the checks below in order before you touch any password.

Why does Viewer RT reject a user whose password is correct? #

The message reports a failed login because Viewer RT cannot start a runtime session, and a user with no web start picture produces the same failure as a rejected password. Reaching the DataMonitor web page in the browser only proves network and web-server access; it proves nothing about the runtime session Viewer RT tries to open after login.

Check in this order:

  1. Start picture assigned in the WinCC user's Web Options.
  2. Correct start picture type when the project uses Basic Process Control.
  3. Default web page set to MainControl.asp and the process-control plug-ins installed on the client.
  4. Matching Windows and WinCC usernames and passwords.
  5. Group memberships trimmed to what the DataMonitor functions need.

Only after all five pass should you treat the message as a real credential problem.

How do I set the web start picture in WinCC User Administrator? #

Open WinCC User Administrator, select the WinCC user the remote client logs in with, confirm Web Monitor access is selected, then open that user's Web Options and assign a start picture. This one setting was the confirmed fix in the reported case: without it, the web client has no picture to load, and the login path reports the failure as a user or password problem.

Reconnect from Viewer RT after saving. If the runtime window opens and the error is gone, stop here; the remaining checks apply only when navigation or windows are still missing.

Which start picture does a Basic Process Control web client need? #

The runtime and the web client need different start pictures: the runtime uses the file @screen.pdl, while the web client uses @screen.pd_. Do not pick a plant picture directly, even though it looks like a reasonable choice. The framework picture is what supplies the screen toolbar and navigation; starting straight on a plant picture bypasses it.

In the documented case the user had selected a plant picture and lost the framework controls. Switching the web start picture to the web framework picture restored them. Publishing every plant picture does not recreate that framework by itself.

Why are the picture-selection buttons missing on the client? #

Missing selection buttons almost always mean the client started outside the Basic Process Control framework or its plug-ins are not installed. Three fixes cover the reported symptoms:

  • Set the viewer's Default Web-Page to MainControl.asp. With that page active, hovering the mouse at the left edge of the browser window opens the menu bar, where the download area shows whether the WinCC Basic Process Control and WinCC Advanced Process Control plug-ins are installed; install them there if not. These plug-ins are normally offered on the client's first connection, so an incomplete first install leaves navigation unavailable even after reinstalling the DataMonitor client software.
  • Confirm the web start picture is the framework picture, not a plant picture.
  • Publish the project functions that change pictures. Global Action scripts do not execute on the web client, so any picture switching that depends on them needs a published alternative such as picture tree management.

If screen names still do not appear on the buttons after all three, recheck that the functions were published on the server, because a client reinstall cannot supply functions the server never published.

Which Windows and WinCC accounts and groups does DataMonitor need? #

Create the Windows user and the WinCC user with the same username and the same password, and keep them synchronized; a mismatch between the two identities produces login failures that look identical to a wrong password. Then add Windows group memberships for the specific DataMonitor functions in use, for example SIMATIC Report Administrators for reporting functions, as the DataMonitor documentation describes.

Do not put the remote-access user in SIMATIC HMI VIEWER. That membership reduces the user's rights relative to the other groups, so a user in HMI VIEWER plus Report Administrators ends up with less effective access than the administrators group alone. Grant only the groups each function requires.

Does a 64-bit Windows system cause this error? #

No known problems tie this error to a 64-bit operating system, and the reported case ran on 64-bit Windows 7 with DataMonitor V7.2 installed per the manual. The client had reinstalled the client software without effect, which is the expected result here: the failure lives in server-side user configuration, not in the client installation.

If you have worked through the start picture, the default web page, the plug-ins and the accounts above and Viewer RT still refuses the login, then verify the password by logging the same WinCC user in at the server itself. At that point a genuinely wrong or expired password is the remaining explanation.

When the DataMonitor session finally opens the runtime window, remember that published screen access still depends on the project's own rights setup; the related article on why runtime passwords do not restrict offline HMI screen edits (article:hmi-runtime-passwords-offline-screen-edits) covers that boundary. For remote read-only access without full Viewer RT sessions, a read-only web client mirror of an HMI screen is a lighter alternative.

Questions asked

Why does WinCC Viewer RT say unknown user or bad password when the password is correct?

The message is misleading: a missing start picture in the WinCC user's Web Options produces the same symptom as rejected credentials. In the documented case, assigning the start picture in WinCC User Administrator and reconnecting let Viewer RT open the runtime window without any password change.

Which start picture should a WinCC Basic Process Control web client use?

Basic Runtime starts on the picture ending in .pdl, while the web client must start on the web variant ending in .pd_. Selecting a plant picture directly skips the Basic Process Control framework, so the client shows only the plant picture with no screen navigation.

Why are the picture-selection buttons missing on the web client?

Set the default web page to MainControl.asp, confirm the Basic Process Control web start picture, and check in the browser's download area that the WinCC Basic Process Control and Advanced Process Control plug-ins installed. Also publish the project functions that change pictures, because Global Action scripts do not run on the web client.

Can I remove the SIMATIC HMI VIEWER group from the remote-access user?

Yes, remove it. That membership reduces the user's effective rights compared with the other groups, so keep only the Windows groups the DataMonitor functions in use actually require, such as the reporting administrators group.

Keep reading

  • Troubleshooting

    Why a PLCnext HMI redirects HTTP to HTTPS and what to change

    The redirect is in the controller's nginx web-server configuration, not in the HMI project: nginx answers every HTTP request with a jump to HTTPS before the eHMI page is delivered, and an HTTP-only browser cannot follow. Edit the active nginx configuration so the HTTP branch serves or routes the HMI, keep the HTTPS branch intact, validate and reload, then verify from the customer's browser.

    HMI and touchscreens

  • Troubleshooting

    Why an HMI VNC Session Shows a Black Screen but Input Works

    When a VNC session to an HMI authenticates, stays black, and clicks at known button positions still actuate the physical panel, the remote-control path is healthy and only the framebuffer-update path is failing. Compare the local screen, confirm authentication, run one observed input test, then take the display-delivery branch: check the access route and client, and get the panel firmware or engineering-software revision that restores screen delivery. Leave tags, drivers and cabling alone.

    HMI and touchscreens

  • How-to

    Where to enter Sm@rtServer credentials in WinCC Runtime Advanced

    Enter the remote user and password in Windows Control Panel under WinCC Runtime Advanced Internet, on the Remote tab, behind Change Settings in the Server tab of the dialog that opens. The Sm@rtServer checkbox in the project's runtime settings only enables the server. Record the listening port shown there and use it with the PC's address in Sm@rtClient.

    HMI and touchscreens

Configuring WinCC Unified user administration and function rights