Why WinCC flexible 2008 fonts look oversized on another PC

HMI and touchscreens Published 5 min read

Short answer

Oversized text and shifted buttons in WinCC flexible 2008 on one computer come from the Windows letter-size (display scaling) setting, not the project. A PC set to 125% draws every text and control 1.25 times larger than the PC the project came from. Set Windows letter size to 100% and reopen the project.

On this page
  1. What the scaling setting changes
  2. Isolate the cause
  3. Setting the Windows letter size back to 100%
  4. Worked example: a 1920 x 1080 screen with 125% letter size
  5. Confirm the fix and close out
  6. Questions asked

If a WinCC flexible 2008 project shows oversized text and shifted buttons on one computer while it looked correct on the computer it came from, check the Windows letter-size setting before anything else. Both machines can use the same screen resolution and the same project resolution, and the text still renders 1.25 times larger on a computer whose Windows letter size is set to 125% instead of 100%. In the case behind this article, that single setting explained everything: the project texts, the displaced buttons, and the WinCC flexible editor's own clipped labels, which were cut off just below the Tab order group. A new empty project showed the same fault, which ruled out a corrupted project file.

What the scaling setting changes #

WinCC flexible 2008 is a classic Windows desktop application. It sizes its text and lays out its controls using the Windows letter-size (display scaling) setting, not the pixel resolution of the monitor. When that setting is 125%, Windows reports a larger logical font and the application draws 1.25 logical pixels for every physical one. Anything computed in logical units — text height, button captions, fixed-height editor labels — grows by that factor, and controls anchored in logical coordinates land in different physical positions. The project file itself is untouched, which is why the same file looks fine on the correctly configured machine.

Because the fault is in the workstation, it also affects the editor chrome, not just runtime screens. The clipped text under Tab order in the editor is the giveaway: a project problem would leave the editor intact.

Isolate the cause #

Work through these checks in order:

  • Compare screen resolutions on both computers. Matching resolutions do not rule out a scaling difference, so treat this check as eliminating only one variable.
  • Open a new, empty project on the affected computer. If the editor's own labels are also clipped or oversized, the fault is the machine, not the project.
  • Toggle the fit to screen option in the settings menu, with and without the checkbox. If nothing changes, the option is not involved; in the reported case it made no difference either way.
  • Read the Windows letter-size setting on the affected computer. Anything above 100% — 125% and 150% are the common values — reproduces the fault.

If every step points at the machine and the letter size is above 100%, you have your answer.

Setting the Windows letter size back to 100% #

Open the Windows display settings on the affected computer — on the Windows 8 and 10 generations used with WinCC flexible 2008 this is the Display page under PC settings or Control Panel, where the letter-size or scaling option is set. Select 100%, apply it, and sign out and back in if Windows asks so every running application picks up the change. Then reopen WinCC flexible 2008, load the copied project, and compare it side by side with the original computer. Screens drawn by the same runtime behave the same way, and the vendor documents this exact cause for fonts and objects shown shifted on a PC Runtime system or operator panel.

Worked example: a 1920 x 1080 screen with 125% letter size #

Inputs: both computers run a 1920 x 1080 desktop with the project configured for the same resolution; the affected computer's Windows letter size is 125%, the original computer's is 100% (these are the settings from the case behind this article).

The rule: a classic Windows application draws text and fixed-size controls in logical pixels, and the physical size is the logical size multiplied by the scaling percentage.

The arithmetic, for a text field the project defines at a logical height of 16 px (an example value, not a project value from the case):

  • At 100%: 16 px × 1.00 = 16 px on screen.
  • At 125%: 16 px × 1.25 = 20 px on screen.
  • Overflow: 20 px − 16 px = 4 px, a 25% increase.

A label box sized for 16 px of text now receives 20 px, so the text either spills into the control below it or, where the control has a fixed height, the top of the glyphs is clipped — exactly the clipped text under the editor's Tab order group. The same factor moves controls: a button anchored at a logical 800 px lands at 800 × 1.25 = 1000 physical px on the 125% machine, 200 px to the right of where the project placed it.

The decision: when the letter size is 125% and the symptoms scale by that same 1.25 factor, set Windows letter size to 100%. Do not move project objects to compensate — the geometry is correct, and moving it would break the layout on every correctly configured machine and on the panel.

Confirm the fix and close out #

Verify three things on the corrected computer: project text is the same size as on the original machine, buttons sit where they were placed, and no editor label is clipped. Check both the copied project and a new empty project so you know the machine, not one file, was at fault. Leave the project geometry untouched.

If text is still oversized after the letter size is at 100%, the evidence for this case does not name a second cause, but one machine-specific suspect remains worth checking: the graphics driver. An outdated driver has been reported to affect how scaled fonts render, and updating it changed the on-screen size in at least one documented case. Compare the remaining machine-level display settings against the working computer rather than editing the project. The same class of problem — oversized HMI text with a workstation-level cause — is worked through for another platform on the page about troubleshooting oversized HMI fonts on Emerson PAC ME systems.

For related WinCC flexible 2008 display behavior, the article on why WinCC Flexible 2008 cannot pan an oversized HMI screen covers what happens when the project resolution exceeds the target screen, which is a different mechanism from the scaling setting described here.

Questions asked

Why are WinCC flexible 2008 fonts larger on one computer but not another?

The two computers render at different Windows letter-size settings. A machine set to 125% draws text and controls 1.25 times larger than a machine at 100%, even with the same screen resolution and the same project file. Set the affected computer to 100% in the Windows display settings, sign out and back in if Windows asks, then reopen the project and compare.

Does the fit to screen option in WinCC flexible fix shifted buttons?

No. Fit to screen only scales the editor's project view on your monitor; it does not change how the runtime draws text relative to Windows scaling. In the case behind this article the shifted buttons and clipped editor text stayed the same with fit to screen on and off, and only returned to normal once Windows letter size was set back to 100%.

How do I verify the scaling fix before touching the project?

Open an existing project and a newly created empty project on the affected computer, and check three things: project text matches the size on the original computer, buttons sit where they were placed, and editor labels such as the text under the Tab order group are no longer clipped. If all three render correctly at 100% scaling, the workstation setting was the cause and the project needs no edits.

Keep reading

  • Troubleshooting

    Why a Comfort Panel seems to scale fonts set in TIA Portal

    A Comfort Panel applies no scaling to the fonts a TIA Portal project sets, and it offers no scale setting to change. The size difference is authored in: Windows display scaling at 125% on the engineering PC enlarges the editor's text metrics, and a hypervisor display option can add a second factor. Set Windows Scale to 100%, sign out and back in, disable the VM scaling option, recompile completely and download.

    HMI and touchscreens

  • Troubleshooting

    Why the 840D sl HMI package will not install on Windows 7 x64

    The SINUMERIK HMI configuration package for WinCC flexible 2008 fails on Windows 7 x64 because setup's operating-system check finds a 64-bit host and the package's documented engineering environment is 32-bit Windows XP. Compatibility mode and administrator rights cannot pass that gate. The supported fix is a licensed 32-bit XP station, usually a virtual machine, with base WinCC flexible 2008 installed first.

    HMI and touchscreens

  • Explainer

    Why WinCC Flexible 2008 Cannot Pan an Oversized HMI Screen

    WinCC flexible 2008 SP5 has no runtime panning and no automatic zooming, so a screen configured larger than the display runs cut off with no way to reach the rest. The project resolution is hardcoded by the configured device in Device Settings, so the fix is to change the device to one matching the display with Fit Screens and Screen Items to new Device enabled, or to split the content across screens.

    HMI and touchscreens