Why WinCC Flexible 2008 Cannot Pan an Oversized HMI Screen
Short answer
WinCC flexible 2008 SP5 has no runtime panning and no automatic zooming, so a screen configured larger than the display runs cut off with no way to reach the rest. The project resolution is hardcoded by the configured device in Device Settings, so the fix is to change the device to one matching the display with Fit Screens and Screen Items to new Device enabled, or to split the content across screens.
On this page
- Why there is no panning or zooming at runtime
- Where the resolution actually comes from
- Converting the project to a matching device
- Worked example: a 1920 × 1080 project on a 1280 × 1024 monitor
- Splitting the content instead of rescaling
- What newer software does differently
- The decision, case by case
- Questions asked
WinCC flexible 2008 SP5 cannot pan a screen that is larger than the display, and it cannot zoom one to fit: there is no runtime screen-movement function, and Screen Windows cannot be used to build automatically zoomed views. A screen configured larger than the display runs with everything beyond the display edge cut off and unreachable. The reason is structural. The project resolution is hardcoded by the configured device in the project's Device Settings — it is not a display property chosen at runtime. The fix is to make the project match the display: enable Fit Screens and Screen Items to new Device, change the configured device to one whose resolution matches, and verify every converted screen — or split the content across several screens sized to the device.
Why there is no panning or zooming at runtime #
The runtime draws each screen at exactly the project resolution on the configured device. Content that falls outside the display area is not scrolled, wrapped or shrunk — it is cut off, and a pushbutton placed there cannot be pressed. There is no setting that adds up, down, left and right movement to a screen, so the directional navigation an oversized design would need does not exist, and Screen Windows offer no automatic zoom either.
That leaves one design rule: lay every screen out so that it fits the configured device area completely. Nothing an operator must reach lives outside it.
On a computer target, check one thing before blaming the project: Windows itself should be set to the monitor's native resolution in the display settings, so the mismatch you are solving is the project's and not a video-scaling artifact.
Where the resolution actually comes from #
Device Settings is where the project resolution is defined, and it is bound to the configured device. Pick a panel and the project takes that panel's native resolution; pick a different panel and the resolution changes with it. The resolution cell is not an independent field. In an existing project the device type can be changed, but the resolution cell stays locked, because a panel offers exactly one native resolution and there is no other value the cell can hold.
A PC target behaves differently: WinCC flexible offers PC-based runtime as a device, and its Device Settings accept a resolution choice, so a project aimed at a computer can be set to the monitor's actual resolution. Running a WinCC flexible 2008 project in PC runtime covers how the PC target itself is set up.
The decision: treat the resolution cell as read-only. To get a different resolution, change the device — on a panel the panel defines it, on a PC you select it.
Converting the project to a matching device #
The fit option must be on before the device changes, because it governs how screens adapt at the moment of change:
- Open Device Settings and note the configured device and its resolution.
- In the WinCC flexible global settings, enable Fit Screens and Screen Items to new Device, the option that rescales screens and their objects when the device or resolution changes.
- Change the configured device to one whose resolution matches the display — a panel with that native resolution, or the PC target set to the monitor's resolution.
- Open every screen afterwards and check each object. Positions and sizes have been rescaled, so confirm that labels still fit their buttons, that indicators sit where the operator expects, and that nothing landed outside the new area.
Conversion is a rescale, not a redesign, and it is not self-verifying: the per-screen inspection in step 4 is what proves the result, particularly for text that must stay legible at the new size.
Worked example: a 1920 × 1080 project on a 1280 × 1024 monitor #
The numbers are an example. A project was configured for a device with 1920 × 1080 px screens, but the computer it runs on shows 1280 × 1024 px.
Missing width: 1920 - 1280 = 640 px, and 640 / 1920 is about 0.33, so one third of the screen width hangs off the display. Missing height: 1080 - 1024 = 56 px. Everything in the right-hand 640 px strip and the bottom 56 px strip is unreachable, and with no panning there is no way to reach it.
Converting to a 1280 × 1024 px device with the fit option on rescales by a factor of 1280 / 1920, about 0.67, horizontally and 1024 / 1080, about 0.95, vertically. A 120 px wide pushbutton then lands at about 120 × 0.67 = 80 px wide. Those factors give the ratio; what each object and font actually does in the conversion is exactly what the per-screen inspection confirms.
Decision: after conversion, no screen may depend on anything outside the configured area.
Splitting the content instead of rescaling #
When the device is fixed and the content is genuinely larger than any resolution available for it, split the screen. Two or more screens at the device resolution, each holding one zone of the machine, replace the single oversized one. Operators move between them with ordinary screen-change buttons; if the changeover should follow the machine state instead of an operator's touch, the PLC can drive it, as changing WinCC flexible screens from the PLC describes.
A split is usually an improvement rather than a compromise. Fewer screens, each built around one task, are easier to read at a glance — the approach in designing HMI screens for clear operator decisions works screen by screen and suits a fixed-resolution target well.
What newer software does differently #
This limit belongs to the WinCC flexible generation. In TIA Portal, screens are resized when the device changes: panel projects get a screen-resize setting for device replacement, and an RT Unified PC runtime can adapt a screen's configured size to the display with a command on the screen itself. The exact commands are in the first FAQ answer below. On current software the same mismatch is a settings adjustment rather than a rebuild.
Moving the project to different hardware altogether is a migration rather than a rescale. When the target moves from a computer to a panel, migrating a WinCC PC runtime project to a Comfort panel walks through one such PC-to-panel move.
The decision, case by case #
- Screen larger than the display: WinCC flexible 2008 SP5 offers no pan and no zoom, so do not build for them; plan the project around the configured device resolution.
- Resolution does not match the display: enable Fit Screens and Screen Items to new Device, then change the configured device — or the PC target's resolution — to match.
- Resolution cell locked: that is how a panel behaves; the value follows the panel model, so select a device whose native resolution is the one you need.
- Content larger than any available resolution: split it across screens at the device resolution and navigate between them.
Questions asked
How does TIA Portal handle a screen that does not match the display?
In TIA Portal the tools exist. For an RT Unified PC runtime, select the screen in the project navigation, right-click it and choose Resize to display; the configured screen size is then adapted to the display. For panel projects, the adjustment lives in the menu under Tools > Settings > Visualization > Resize screen, which resizes the screens to the new device. Neither command exists in WinCC flexible 2008, where the device change with the fit option is the only equivalent.
Why can I change the device type but not the resolution cell?
The resolution cell mirrors the selected device rather than being a free field. A panel device brings exactly one native resolution, so once that device is configured there is no other value the cell could take and it stays locked; the device type itself can still be changed. To reach a different resolution, select a different device whose native resolution matches the display, or move the project to a PC target, where the resolution is chosen in Device Settings.
What resolution should I design new WinCC flexible screens for?
Design at the native resolution of the target display and keep every object inside that area. As an example sizing, a monitor that shows 1024 × 768 px gets screens laid out at 1024 × 768 px; a design that would not fit is split across additional screens before any object is placed. Confirm the configured device in Device Settings reports exactly that resolution, then lay out against it.
Does a service pack such as SP5 add panning or zooming to WinCC flexible 2008?
No. Service packs within the WinCC flexible 2008 generation, SP5 included, keep the same screen model: resolution hardcoded by the configured device, no runtime pan controls and no automatic zooming through Screen Windows. The resize commands in TIA Portal are design-time conversions of the configured screen size, not pan or zoom at runtime, so a later generation does not add the missing screen movement either.