Explainer

Why WinCC Flexible 3D pipes scale instead of stretching

HMI and touchscreens Published 6 min read By IMDTouch engineering team

Short answer

Library 3D pipes in WinCC flexible 2005 are single WMF graphics: dragging a handle scales the whole symbol, and no rotate command exists for them. To lengthen an angled run, overlap two or more copies end to end, or export the artwork, rework it outside the tool and import it as a JPG. Read the Hotfix 7 readme before assuming the hotfix changes either limit.

On this page
  1. Why the pipe scales as one object
  2. The rotate command never applied to these symbols
  3. Lengthening a 30-degree run by overlapping two library pipes
  4. The export, edit and import route
  5. What Hotfix 7 decides
  6. Accepting the finished graphic on the panel
  7. Questions asked

When you drag a handle of a 3D pipe from the WinCC flexible 2005 factory symbol library, the whole symbol grows: longer, fatter, and with its drawn angle visually distorted. That happens because the pipe is a single WMF graphic, not a parameterized object with a length property. The editor offers no length-only control and no rotate command for it. The two working answers on a 2005 SP1 installation are to overlap several copies of the pipe until the run reaches the required length, or to export the artwork, rework it outside the tool and import it back as a JPG. Before assuming Hotfix 7 changes anything, read its readme, because the readme is the only place the corrected issues are listed.

Why the pipe scales as one object #

The library stores each 3D pipe as one WMF file: a single vector drawing with one bounding box. When you pull a corner handle, the editor scales that bounding box, and everything inside it scales with it. Length, apparent diameter, the shading that makes the pipe look three-dimensional, and the angle of the run all change together. There is no anchor point separating the straight section from the end fittings, so a length-only stretch is not possible on this object. The reported case, an angled pipe that "blots in size" as its length is increased, is exactly this whole-box scaling. Whether every factory pipe behaves identically was never confirmed, but any pipe delivered as one WMF drawing will, because the behavior belongs to the file format and the editor, not to one symbol.

The rotate command never applied to these symbols #

The missing rotate feature is not an omission specific to your installation. The current WinCC documentation describes rotation of suitable objects only in steps of 90 degrees around the object's center, clockwise or counterclockwise, and states plainly that not all objects can be rotated. Arbitrary-angle rotation was never a capability of library graphic objects, so the slant you see in the library pipe is baked into the artwork by whoever drew it, not set by a property you can edit. The same limit still surprises users on newer releases; see why WinCC library symbols rotate only in 90 degree steps for how that restriction shows up today. For a 2005 project, accept the angle the artwork carries and work with composition instead.

Lengthening a 30-degree run by overlapping two library pipes #

This is the fastest workaround when the library angle already suits your process graphic.

Inputs, and where each comes from:

  • Pipe angle: about 30 degrees, the angle of the library symbol as selected (from the reported case).
  • Number of copies: two, the minimum this method needs (from the practical answer to that case, which says to put two or more pipes in a row and overlap them).
  • Overlap: one quarter of a symbol length. This is an example value; in practice you nudge the second copy by eye until the joint disappears.
  • Target: the run length the combined symbols produce, measured in symbol lengths.

The rule in words: a chain of overlapped identical copies covers the number of copies minus the total overlap, counted in symbol lengths. Because every copy is the original artwork, the angle and the apparent diameter stay exactly as the library drew them.

The arithmetic:

2 copies × 1 symbol length − 0.25 symbol length of overlap = 1.75 symbol lengths

Result: a continuous run 1.75 times the length of one library pipe, at the same 30-degree angle and the same diameter, with no scaling distortion.

The decision: for a run up to about two symbol lengths, overlapping copies is the right fix and takes a minute per joint. Above that length, or when a joint is still visible at the panel's actual screen size, stop adding copies and switch to the export, edit and import route below.

Alignment is the only real effort here. Place the copies on the same line, zoom in, and overlap the ends until the shading of the first copy's end disappears into the second copy's start. A joint that looks clean at editor zoom can still show on the panel, so the acceptance check at the end matters.

The export, edit and import route #

When you need a custom length, a custom angle, or a joint-free run that overlapping cannot deliver, take the artwork outside the tool:

  1. Export a library graphic that looks close to what you need.
  2. Rework it in external image editing software: extend the straight section, keep the 3D shading consistent, and draw the new angle if the run must turn.
  3. Import the finished picture into the screen as a JPG.

Two properties of this route shape how you use it. First, the imported JPG is flattened: the pipe is one bitmap with no separately adjustable components, so keep both the exported source and the reworked file, because any later change means returning to the artwork. Second, judge sharpness at the final on-screen size, not at editor zoom; a screen-resolution panel shows a JPG differently from the engineering PC.

What Hotfix 7 decides #

For WinCC flexible 2005 SP1 the corrective update in question is Hotfix 7, and its readme file, Readme_WinCC_flexible_2005_SP1_HF7.doc, lists every issue the hotfix corrects. That gives you a clean decision rule: if the readme does not name rotation or scaling of WMF library graphics, the hotfix does not change that behavior, and the workarounds above remain the fix. Install the hotfix for the corrections it does document, but do not expect it to add a rotate command that the object model never had.

If the readme leaves the graphics question genuinely unresolved after reading, raise the point through Siemens' official support channel for the product rather than guessing, and keep building the screen with the overlap or JPG method so the project does not wait on the answer.

One installation consequence belongs here: after applying Hotfix 7, the images on the panel must be updated to the new version the hotfix delivers. Do that update before you download and evaluate the process graphic, so you are judging the screen against the images it will actually run on.

Accepting the finished graphic on the panel #

The editor view is not the deliverable; the panel display is. Check the assembled or imported pipe at the intended screen size, on the panel, and confirm four things: the angle of the run matches the neighboring pipes, the apparent diameter is consistent from one end to the other, no overlapping joint is visible, and the panel runs the updated images if Hotfix 7 was installed. If all four hold, the 3D process graphic is done regardless of which route built it. If the joint shows or the diameter wanders, the overlap failed and the export-and-import route is the remaining answer for that run.

Questions asked

Will Hotfix 7 for WinCC flexible 2005 SP1 let me rotate library pipes?

The readme file Readme_WinCC_flexible_2005_SP1_HF7.doc lists every issue the hotfix corrects. If rotation or scaling of WMF library graphics is not on that list, the hotfix does not change that behavior, and overlapping copies or importing a JPG remains the fix. Install the hotfix for the corrections it documents, not for this.

What must change on the panel after installing Hotfix 7?

The panel images must be updated to the new version the hotfix delivers. A project compiled with the updated engineering tool against old panel images is a mismatch, so download the updated images to the panel before judging how the pipe graphic looks.

Why does dragging the pipe corner scale it in both directions?

The pipe is stored as one WMF vector drawing inside one bounding box. The editor scales that box, so length, diameter and the drawn angle all change together. There is no anchor that separates the straight section from the end fittings, which is why a length-only stretch is impossible.

Should I keep the source artwork after importing a reworked pipe as a JPG?

Yes. The imported JPG is a flattened image with no separately adjustable components. Keep the exported source and the edited file so a later change of length or angle means editing the artwork again instead of rebuilding the whole process screen.

Keep reading

  • Troubleshooting

    TP177B color PN/DP OS update fails: version set and image fix

    The transfer is refused because the project, the engineering version and the panel image are not a compatible set. Install Hotfix 7 for WinCC flexible 2005 SP1, which supplies the TP177B image and downgrades the panel to it, or keep the panel's newer version with at least WinCC flexible 2008 SP1; then convert the project from TP177B mono to TP177B color PN/DP and transfer over MPI.

    HMI and touchscreens

  • How-to

    Connecting a WinCC flexible 2005 Tag to STEP 7 PLCSIM

    The order you used is correct: STEP 7 5.3 first, WinCC flexible 2005 second, and SP3 for STEP 7 5.3 last, so no reinstall is needed. Define MD 4 as an external tag on the connection to the simulated controller, marker memory, byte offset 4, 4-byte integer, then force a value in PLCSIM and confirm the HMI follows it.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC Flexible 2008 SP5 runtime closes without a message

    A runtime that opens and closes without a message 10 to 20 seconds after launch is a startup-path termination, not a license fault. Record the exact Windows 10 build with winver, install the Update (Hotfix) for WinCC flexible 2008 Service Pack 5 delivered at the end of Update 2, and correct the Project ID area pointer in the connections editor. The msjet40 archive failure is a symptom branch; rebuilt MDB files hold about a day, then the exit returns.