Explainer
Why WinCC flexible shows only Tahoma in a panel project
Short answer
A WinCC flexible panel project offers only the fonts its panel firmware can render, and the default language family is why Tahoma is the one face you see. The language-and-font editor exposes two additional language families that change character coverage; fonts installed on the engineering PC never reach the panel. Boxes or blanks mean missing glyphs, so switch the family rather than the size.
On this page
A WinCC flexible panel project shows a short font list because the panel, not the engineering computer, draws every character: the fonts belong to the panel's firmware, grouped into language families, and the default family is why Tahoma is the one face you see. The language-and-font editor of a panel project exposes two additional language families, and the family you select decides both which fonts appear and which characters they can render. A font installed on the engineering PC never reaches the panel. Boxes or blanks on the display mean missing glyphs, and no change of size or emphasis supplies them; the fix is the language family, chosen before transfer.
Why the list stops at the default family #
The editor runs on your computer, but the runtime panel renders the screens after transfer, so the two machines hold separate font resources. A panel project lists only the faces its configured target can draw, and those faces belong to language families stored in the firmware. A new panel project opens on the default family, and its standard face is Tahoma, so the single style you found is the intended default, not a broken installation. The two additional families in the language-and-font editor are the only other sets the project offers; open that editor and read the family labels and their help text before changing anything. Record the panel model and the WinCC flexible version of the project as well, because the contents of each family are a property of that target and software combination, not of whichever PC runs the editor.
Families are character coverage, not decoration #
A font face is the visual design of a character set; a glyph is the drawn shape of one character. The distinction matters because wanting a different look and wanting readable characters from another writing system are different requirements. A language family groups fonts by the scripts they can render, so selecting a family changes coverage first and appearance second: a face that covers Latin text can hold no glyphs at all for the Chinese characters of a translated screen. Changing point size or emphasis changes how existing glyphs are drawn, never which glyphs exist. When the panel meets a character its font cannot draw, it prints a box or leaves a blank in that position. Font substitution, meaning rendering with a different face when the requested one is unavailable, can keep such text readable, but it changes width, line breaks and alignment, so the check that counts is the rendered screen on the actual panel, not the preview in the editor.
What the engineering PC can and cannot add #
For Asian project languages the documented prerequisite sits on the engineering computer: open Regional and Language Options in the Windows Control Panel, go to the Languages tab and enable the supplemental language support so the script files are installed; only then does the editor handle the characters you type. In the project itself you add the language in the project tree under Project > Language Settings > Project Languages, selecting for example Chinese (People's Republic of China), and you then pick the family whose fonts cover it. What the PC cannot do is extend the panel's font set: no documented method adds an own font to a WinCC flexible panel, so the families in the firmware are the entire selection. The engineering computer prepares the text; the panel's firmware draws it.
Choosing the family for English and Chinese project text #
Take a project that must run in two languages: English and Chinese (People's Republic of China), the language the manufacturer's Asian-font procedure selects for its own walkthrough.
The inputs:
- Language families the language-and-font editor of a panel project offers: 1 default plus 2 additional, the count that editor shows for a WinCC flexible panel project.
- Project languages in this case: 2, English and Chinese (People's Republic of China).
- Coverage requirement: every character of every project language must render, so 2 of 2 languages.
The rule, in words: a font draws only the glyphs it contains, so the selected family must cover all project languages; the default family covers the Latin text and none of the Chinese characters.
The arithmetic:
- Families to inspect = 1 + 2 = 3.
- Coverage with the default family = 1 of 2 languages = 1/2 = 50 percent, below the required 2 of 2 = 100 percent; the family that carries the Chinese glyphs reaches 2 of 2 = 100 percent.
Result: the default family fails this project; the family with Chinese coverage passes.
Decision: as soon as one translated screen contains characters outside the default family's coverage, switch the family before doing any formatting work; while all project text is Latin, keep the default family and its faces.
Applying the change without breaking the screens #
Save a separate copy of the project first, so the previous font assignments and screen geometry can be compared or restored. Install the Windows script files, add the project language under Project > Language Settings > Project Languages, then select the covering family in the language-and-font editor. A different face occupies a different width at the same point size, so after the switch re-check the width, wrapping and alignment of a heading, a button label, a value display and a longer text field; that is where substitution shows up. Compile, clear any language or font warnings, and transfer through the normal workflow. When the edits do not appear on the panel at all, the fault is the rebuild and transfer rather than the font, and why WinCC flexible edits do not show in runtime walks through those checks. On the panel, display the application's letters, digits, punctuation, symbols and translated text in every enabled language; each character must appear as its intended glyph, with no boxes and no blanks.
When the fault is not the panel project #
Neighbouring faults get blamed on the font list. If the engineering tool itself warns that an installed font is missing, the problem is the Windows font installation of the engineering computer, not the panel's families, and why your HMI software reports a missing installed font covers that repair. If the transferred project shows the wrong words rather than wrong shapes, the language assignment of the texts is at fault, not the glyphs. If the requirement is one specific new face that no family on your panel contains, the target has to change, not the project: a WinCC flexible PC runtime or a Unified panel with its documented own-font download both widen the choice. Decide which of these problems you actually have before opening a font dialog again.
Questions asked
Can I add a new face to a WinCC flexible panel by copying a font file onto it?
No documented method transfers an own font to a WinCC flexible panel, so a copied file is not a deployment and nothing on the panel loads it. Only the Unified generation documents downloading your own font: take the file from the Windows Fonts folder, read its details under Properties first, and download it to the Unified runtime. On a flexible panel, choose among the language families the editor offers.
Does WinCC flexible PC Runtime show the same single-font list?
No. PC Runtime draws its text with the fonts installed on the Windows computer that runs it, so its font dialog lists the faces of that installation instead of a firmware set. That is also why the same project can look different on the two targets, and why substitution checks belong on the runtime PC as much as on a panel.
How do I use one font for every language in a TIA Portal panel project?
The TIA Portal generation has a global switch that WinCC flexible lacks. Open the settings dialog, go to the Visualization section, General page, and enable 'Use same font for all languages'. Without it, each project language can carry its own font, which helps when one language needs wider glyph coverage.
The panel still shows my old font after I transferred the project. Why?
The panel renders only what the transferred project contains, so a change still unsaved in the editor changes nothing on the device. Recompile and transfer again. If the transfer succeeded and the old face remains, the object is formatted individually instead of following the project font assignment, so open its text format settings and point it back at the project font.