Why WinCC Runtime V13 cannot run two instances on one PC

HMI and touchscreens Published 5 min read

Short answer

WinCC Runtime Professional V13 SP1 runs as a single instance on a PC, so you cannot start one Runtime per monitor. Two independently operated screens need the WebNavigator option: the server component runs with Runtime, each monitor gets its own client session in a browser or the WinCCViewerRT.exe viewer, and each session occupies one WebNavigator license at the server. If both seats share control, one Runtime with windows on both monitors does the job with no extra option.

On this page
  1. Why one Runtime per PC is the hard limit
  2. The WebNavigator architecture that fits two clients on one PC
  3. Licensing: where the licenses sit and how many you need
  4. What the client shows on screen
  5. The alternatives, and the decision for each
  6. Check it before startup
  7. Questions asked

WinCC Runtime Professional V13 SP1 runs as one instance per PC. There is no supported way to start a second, separately operated Runtime on the same machine, so one Runtime per monitor is not a configuration you can build. The supported path for two independent operator positions on the two monitors of one PC is the WebNavigator option: its server component runs with the Runtime, each monitor gets its own client session in a browser or in the WinCCViewerRT.exe viewer, and each session occupies one WebNavigator license on the server. If the two operators do not need independence, skip the option entirely — one Runtime can place its windows across both monitors. Below are the limit, the architecture, the license arithmetic for a dual-monitor station, and the decision for each case.

Why one Runtime per PC is the hard limit #

In the normal Runtime system without options, WinCC Runtime does not run multiple instances. Launching it a second time does not create a second operator station; the same single Runtime keeps running, and there is no setting that turns two instances on.

The installation side blocks the obvious workaround too. The parallel-installation notes in the TIA Portal documentation do not permit WinCC Professional versions side by side on one PC — WinCC Professional V21 next to an earlier WinCC Professional, engineering or runtime, is explicitly not permitted — so stacking two Runtime installations and starting one on each is not a path either.

Decision: two independently operated native Runtimes means two PCs, one Runtime installation each. On a single PC, native Runtime alone gives you one operator station.

The WebNavigator architecture that fits two clients on one PC #

The WebNavigator option splits the job into one server and any number of clients. The server component installs on the WinCC Runtime system. The client component installs on the computer that should operate the visualization — for a dual-monitor station hosted on one PC, that is the same machine. A session opens either in a web browser or in the dedicated WinCCViewerRT.exe viewer, and the documentation describes such a client as fully functional: your project screens with live operation, rather than the plain status pages built into controllers.

Two sessions then run side by side, one per monitor. Both can connect to the same project, and where more than one WebNavigator server exists in the plant, a session can point at a different server instead. If the runtime screens are also to be published to web clients elsewhere on the network, the prerequisites are covered in What Publishing HMI Runtime Screens to Web Clients Requires.

One operations note: independent sessions still write to one process, so two seats can command the same machine at the same time; agree in advance which position owns which actions.

Licensing: where the licenses sit and how many you need #

The licensing documentation for WinCC/WebNavigator and for the WebNavigator option under WinCC RT Professional states the model plainly: no license is required on the PC where the client runs, the licenses sit on the WebNavigator server, and each connected client session occupies one of them. The count follows sessions, not computers.

Worked example — one PC hosts WinCC Runtime Professional V13 SP1 with the WebNavigator server component, and both monitors hang off that PC:

  • Operator positions required: 2, one independently operated position per monitor.
  • Client sessions needed: 2 positions x 1 session each = 2 sessions.
  • WebNavigator licenses on the server: 2 sessions x 1 license each = 2 licenses.
  • Licenses on the client PC: 0, because the PC running the client carries no license by design.

Split the same two positions onto two separate client PCs and the arithmetic does not move: still 2 sessions, still 2 licenses on the server, 0 on the clients. The number of independent positions is what moves the license count; the number of computers does not.

What the client shows on screen #

The sources describe the WebNavigator client as fully functional — the project screens, available for operation. What they do not document is the rendering mechanism: whether the graphics are translated to HTML5, JavaScript and CSS or delivered another way is not stated for the versions in question, so treat any specific rendering claim as unverified. Expect your screens and their operation to carry over; do not expect a documented statement about how they are drawn. Settle the visual question the short way: start one session on the installed version and compare it against the panel look before an operator relies on it. That is a bench check, not a design step.

The alternatives, and the decision for each #

What the operators need Configuration that works License side
Two seats, shared control of one process One Runtime instance with its windows placed across both monitors No extra option
Two independently operated seats on one PC Runtime plus the WebNavigator server component; two client sessions, one per monitor 2 WebNavigator licenses on the server
Two independent native Runtimes Two PCs, one Runtime installation each Runtime licensed on each PC

Shared control is the cheap case: place the single Runtime's windows across both screens, and the placement mechanics are covered in How One HMI Runtime Places Windows on Two Monitors. If the underlying want is two different plant visualizations rather than two seats on one project, one server host can carry several HMI projects — the pattern is covered in How multiple HMI projects run on one server host.

The second session also needs a real screen at the machine. One PC can drive two touchscreens, and the display-side setup is covered in Running One HMI Interface on Multiple Touchscreens From One PC; if you are adding the second touch surface to a computer you already have, that is exactly the job for industrial touchscreen monitors.

Check it before startup #

Validate the built configuration, not the limitation: two sessions open, one sits on each assigned monitor, both operate the project, and a license is free for each session. Do not validate the design by launching the normal Runtime twice — that path is not supported, so a pass there proves nothing about two independent stations. Keep one known failure on the bench list: after the WebNavigator client is installed, the WinCCViewerRT.exe viewer can fail to start with error 1000, and the fix is covered in resolving WinCCViewerRT.exe error 1000 after a WebNavigator install.

Questions asked

What happens if I start WinCC Runtime a second time?

Nothing useful. In the normal Runtime system without options there is no second instance, so the same single Runtime keeps running and no second operator station appears. Installing a second copy alongside is blocked as well, because the TIA Portal installation notes do not permit parallel WinCC Professional installations on one PC. Split operator positions with WebNavigator client sessions or with a second PC carrying its own Runtime.

Does the client PC need its own WebNavigator license?

No. With server-end licensing, the licenses live on the WebNavigator server and the PC running the client carries none. A dual-monitor station driven from one client PC consumes two server-side licenses for its two sessions, and the same two positions split across two client PCs consume the same two, because the count follows the sessions rather than the computers.

Can the two monitor sessions be operated independently?

Yes, and that independence is the point of the arrangement. Each session is its own client of the runtime project, so each can be navigated and operated separately on its monitor. Both still write to the same project data, which means both seats command one process; agree in advance which position owns which actions so the operators do not fight each other.

Does the browser client look like the runtime on a panel?

Functionally yes: the documentation describes the WebNavigator client as fully functional, with the project screens available for operation. How those screens are rendered in the browser, translated to HTML5, JavaScript and CSS or delivered another way, is not stated in the sources for the versions in question, so confirm the exact look by starting one session on your installed version.

Keep reading

  • Troubleshooting

    What WinCC V11 needs to run a PC as an HMI

    WinCC V11 Professional in TIA Portal configures and downloads HMI projects; it does not make the PC a runtime station by itself. To run the PC as an HMI you install WinCC Runtime Advanced for panel-class projects or WinCC RT Professional for SCADA, each on its own runtime license. When the Advanced setup stops at the Sebu_winccv11 check, the image carries classic SIMATIC packages the V11 SP2 compatibility list does not clear, so clean the machine and reinstall.

    HMI and touchscreens

  • How-to

    Running a WinCC 7.0 project on another PC without a new build

    No. WinCC has no compile-to-EXE option: the destination PC needs WinCC Runtime of version 7.0 or higher, installed and licensed, and you transfer the project files to it. A newer WinCC opens and converts the project; an older release will not open it.

    HMI and touchscreens

  • How-to

    Simulate two HMI panels in WinCC Advanced V13 SP2

    TIA Portal V13 SP2 with WinCC Advanced starts only one simulated panel at a time. To run two, copy an HmiRTm.ini into the WinCCRT Adv folder, set OnlyOneInstance to false, point LoadConfigFile at each compiled .fwc file, and start HMIRTM.exe once per panel.

    HMI and touchscreens