Why WinCC TIA Portal REAL exponential display is runtime limited

HMI and touchscreens Published 7 min read By IMDTouch engineering team

Short answer

Exponential display of a Real value in WinCC TIA Portal belongs to the runtime family, not to the tag. Only WinCC RT Professional I/O fields provide a format pattern that renders an exponent; WinCC RT Advanced and panel I/O fields cannot, so a very small value otherwise needs twelve fixed-point decimal positions. The fallback is rescaling to a prefixed unit such as picoBar with the inverse scale on operator entry.

On this page
  1. A Real tag stores a number, the I/O field renders characters
  2. The runtime boundary that decides exponential display
  3. The format pattern that works on WinCC RT Professional
  4. The scaled-unit workaround for RT Advanced and panels
  5. Worked example: 1.0e-12 bar as 1.0 picoBar on an RT Advanced screen
  6. Keep the recipe on one storage convention
  7. The decision for each runtime
  8. Questions asked

Exponential display of a Real value in WinCC TIA Portal is decided by the runtime family, not by the tag, the recipe or the screen layout. Only the I/O fields of WinCC RT Professional provide a display format that renders an exponent, so they can show a value such as 1.0e-12 bar in a few characters. The I/O fields of WinCC RT Advanced and of the panels cannot render exponential format at all; on those targets the same value needs twelve fixed-point decimal positions unless you rescale it to a prefixed unit such as picoBar and apply the inverse scale on operator entry. Below are the boundary, the pattern that works on RT Professional, the scaling method that replaces the exponent everywhere else, and the decision for each runtime.

A Real tag stores a number, the I/O field renders characters #

A Real tag holds one number. In TIA Portal the Real data type is a 32-bit IEEE 754 single-precision value, so it carries about seven significant decimal digits regardless of what the screen shows. A recipe record stores or transfers that same number from one place to another. The I/O field and the Recipe View are converters: each turns the stored value into characters according to its own display-format capability.

That split is exactly the behavior you are seeing. TIA Portal accepts exponential text when you type a small value into a recipe, because the editor's only job is to store the number. The runtime object that later shows the value applies its own format rules, and if those rules are fixed-point only, every power of ten below one costs one decimal position. Raising the decimal-place count changes the characters, never the precision the Real carries; the extra positions show zeros, not new information.

The runtime boundary that decides exponential display #

The decisive setting is not on the tag, the recipe or the screen. It is which WinCC runtime family the screen runs on.

WinCC RT Professional: the I/O field has its own display-format property, and the TIA Portal documentation for that object lists four display formats for value input and output. The Decimal format accepts a pattern whose trailing exponent letter requests exponential rendering; the pattern is set up in the next section. On this runtime, an I/O field can show the exponent directly.

WinCC RT Advanced and the panels: the I/O field has no exponent pattern. Its format patterns render fixed-point decimal, so on these targets the exponential route does not exist at any TIA Portal setting.

The decision falls out immediately: expect exponential rendering from an I/O field only when the configured runtime is WinCC RT Professional. Format availability is decided per object and per runtime family, the same mechanism behind why a WinCC I/O field shows no Real or DINT format. If your target is RT Advanced or a panel, stop hunting through format settings and go to the scaled-unit method below.

The format pattern that works on WinCC RT Professional #

On an RT Professional I/O field bound to the Real tag:

  1. Open the field's display-format properties.
  2. Set the display format to Decimal.
  3. Set the format pattern to 99.99e. Each 9 reserves one digit position, two before the point and two after it, and the trailing e tells the field to render the result with a power-of-ten exponent.
  4. Size the digit positions to your value range so the mantissa does not round: widen them before the point for values above unity, after it for finer resolution.
  5. Run the screen and test values on both sides of unity and across the whole small-value range the machine actually produces.
  6. Test entry separately from display. A field that renders an exponent correctly can still reject a typed value because of the allowed range, the digit count or the decimal separator, so both directions need their own test.

An I/O field and a Recipe View can expose different format properties even when both reference the same tag, so confirm that the object you actually use, not its neighbor, renders the exponent.

The scaled-unit workaround for RT Advanced and panels #

On WinCC RT Advanced and on panels, typing exponent characters into a format pattern is not a commissioning path, because the field cannot render them. Represent the value in a prefixed unit and scale at the interface instead.

Pick the prefix from the magnitude you must show. Applied to the 1.0e-12 bar test value:

Displayed unit One displayed unit equals The test value renders as Fixed-point decimals needed
microBar 10^-6 bar 0.000001 microBar 6
nanoBar 10^-9 bar 0.001 nanoBar 3
picoBar 10^-12 bar 1.0 picoBar 1

Only picoBar brings that magnitude into a one-digit display; microBar still hides the first significant digit behind six zeros.

The conversion is two-directional. Let P be the prefix factor, the number of displayed units in one base unit, here 10^12. Multiply the base-unit value by P to display it; divide the operator's entry by P before it is sent to the tag. Apply both directions every time: scaling only the displayed output means an operator typing 1.0 puts one whole base unit on the tag, twelve orders of magnitude away from the intended value.

Multiply to display, divide to enter: it is the same presentation-versus-value split as when you scale a PLC integer into an HMI display value; only the factor differs.

Worked example: 1.0e-12 bar as 1.0 picoBar on an RT Advanced screen #

Inputs:

  • Process value: 1.0e-12 bar, the magnitude the whole question turns on and the value this article tracks throughout.
  • Display unit: picoBar. The SI prefix pico means one trillionth, so 1 picoBar equals 10^-12 bar.
  • Prefix factor: P = 10^12, because one bar contains 10^12 picoBar.
  • Target: a WinCC RT Advanced or panel I/O field, which renders fixed-point decimal only.

Rule in words: multiply the base-unit value by the prefix factor to display it, and divide the entered number by the same factor to recover the base-unit value for the tag.

Display arithmetic: (1.0 × 10^-12 bar) × (10^12 picoBar / bar) = 1.0 picoBar. The units cancel as bar × picoBar / bar = picoBar.

Entry arithmetic: 1.0 picoBar ÷ (10^12 picoBar / bar) = 1.0 × 10^-12 bar. The tag receives exactly the magnitude the process expects.

Result: the screen shows 1.0 beside a picoBar label while the tag keeps the base-unit value, and the fixed-point field needs a single decimal place.

Decision: on RT Advanced or a panel, scale by a prefix as soon as the first significant digit of your smallest value would sit deeper than the decimal positions you are willing to display, and choose the prefix that puts the shown number in a readable range, roughly 1 to 999. For this magnitude the table above shows that only picoBar clears that bar; microBar and nanoBar still leave leading zeros after the point.

Keep the recipe on one storage convention #

Recipe View formats independently of the I/O field, so set it up and test it on its own terms. The scale must then hold across every object that touches the value:

  • Choose one storage convention and keep it: either the recipe rows hold base-unit bar values and the prefix scale lives only at the screen objects, or the rows hold scaled values and the conversion moves to the process boundary.
  • Label every recipe row and column with the unit actually stored. A row of scaled numbers under a base-unit heading is a magnitude error no one catches by eye.
  • Give the operator the inverse scale on entry, in the Recipe View edit field and in any separate I/O field used for editing the same value.

Round-trip test: save a recipe holding the scaled value, close it, recall it, apply it to the process, and read the tag on the PLC side. Recipe View, unit label, edit field and process tag must all describe the same physical magnitude before and after the trip.

The decision for each runtime #

  • Screen runs on WinCC RT Professional: set the I/O field display format to Decimal with an exponent-bearing pattern such as the one above and display the Real directly. Test typed entry as well as shown output.
  • Screen runs on WinCC RT Advanced or on a panel: no exponent pattern exists at any setting. Rescale to a prefixed unit, multiply to display, divide to enter, and put the storage convention on the recipe documentation.
  • Either target: prove the full path with one known small value, covering entry, tag read, recipe save and recall, and transfer back, before operators use the screen.

Questions asked

Why does a fixed-point I/O field need twelve decimal positions for a pico-range value?

In fixed-point rendering the field draws one character position for every power of ten below one, so the first significant digit of a pico-range value sits twelve positions past the point and every position before it shows a zero. Exponential rendering moves the magnitude into the exponent, which is why a two-digit mantissa with e-12 shows the same number in a handful of characters.

What do the digit positions in the exponent format pattern mean?

Each 9 in the pattern reserves one digit position: in the RT Professional pattern given in the article, two nines sit before the point and two after it, and the trailing e tells the field to render the result in exponential form. Size the positions to your value range so the mantissa does not round. The exponent letter, not the digit count, is what switches rendering to exponential.

How do I verify exponential display before operators use the screen?

Enter a known small value through the operator object and read the tag on the PLC side, save and recall the recipe, then edit the recalled value and transfer it back. On WinCC RT Professional the I/O field should show an exponent-bearing string; on WinCC RT Advanced or a panel it should show the scaled decimal beside the prefixed unit label. Display and entry must round-trip to the same physical magnitude.

Which decimal separator does exponential entry use?

The separator configured on the target runtime, not the one on your engineering PC. On a comma locale the mantissa is typed with a comma; on a period locale it is typed with a period, and an entry that uses the other separator will not parse as intended. Check one known value on the target runtime before you document the entry procedure for operators.

Does raising the decimal-place count add precision to the value?

No. A Real is a 32-bit IEEE 754 single-precision value with roughly seven significant decimal digits; the extra fixed-point positions render zeros or rounding leftovers, not new information. If the application needs more than about seven meaningful digits, the data type is the constraint, not the format. Use LReal where the controller and the HMI tag both support the 64-bit type.

Keep reading

  • Troubleshooting

    Why a simulated HMI shows hash marks, not PLC values

    Hash marks mean the simulated panel runtime is not receiving any displayable value, so treat it as a communication problem before anything else. In the Windows Control Panel of the configuration PC, set S7ONLINE (STEP 7) to TCP/IP on the adapter that reaches the S7-1200, or to PLCSIM when the PLC is simulated too. Then confirm each tag's data type, widen any format pattern the value outgrows, and prove the route with a safe write.

    HMI and touchscreens

  • How-to

    Showing Thousand Separators in WinCC TIA Portal Output Fields

    Digit grouping in a WinCC output field is presentation only: set it in the field's format pattern in TIA Portal when the target supports one, otherwise in the target runtime's regional settings, and verify with a known value on the deployed panel or PC runtime. The PLC value stays unchanged.

    HMI and touchscreens

  • Troubleshooting

    Why a WinCC Professional IO field is not transparent in runtime

    Clear Use WinCC classic design runtime under Runtime settings > Screens > General, set the IO field's transparency in Style/Design > Settings to 0, then run Compile > Software (rebuild all) and restart the simulation. If the background still appears on a V13 SP1 PC station after a rebuild and an IM folder cleanup, a repair and reinstall of TIA fixed the reported case.

    HMI and touchscreens

Start a published WebIQ HMI project without Runtime Manager