Why a WinCC Professional IO field is not transparent in runtime

HMI and touchscreens Published 6 min read By IMDTouch engineering team

Short answer

Clear Use WinCC classic design runtime under Runtime settings > Screens > General, set the IO field's transparency in Style/Design > Settings to 0, then run Compile > Software (rebuild all) and restart the simulation. If the background still appears on a V13 SP1 PC station after a rebuild and an IM folder cleanup, a repair and reinstall of TIA fixed the reported case.

On this page
  1. What the symptom is and what it is not
  2. Turn off the classic runtime design
  3. Set the transparency value on the IO field
  4. Rebuild all and restart the simulation
  5. Clean the IM folder when the generated data is stale
  6. Rule out the communication warning
  7. Escalation order and the decision
  8. Questions asked

An IO field that is transparent in the TIA Portal editor and colored in WinCC Professional runtime is being repainted by the runtime design layer, not by your screen. Clear Use WinCC classic design runtime under Runtime settings > Screens > General, set the IO field's transparency in Style/Design > Settings to 0, run Compile > Software (rebuild all) and start a fresh simulation. On the reported V13 SP1 Update 7 PC station those changes were not enough: after a full rebuild and an IM folder cleanup had also failed, a repair and reinstall of the TIA installation was the step that fixed it. A field that is grey and carries a yellow warning rectangle is a different fault — that is the missing-communication state, and no appearance setting touches it.

What the symptom is and what it is not #

The defining symptom is an object rendering mismatch: the IO field shows the screen behind it in the editor, and the same object carries a solid background color once the simulation runs. It is not a visibility problem, not a missing process value and not a communication indication. Sort the cases before you change anything:

  • Transparent in the editor, colored only in runtime: the classic design switch, the transparency value, the rebuild and, if needed, the installation repair described below.
  • Grey field with a yellow warning rectangle: no live PLC connection or bad tag quality — fix communication first.
  • Field invisible rather than colored: an output-mode or visibility configuration question, a different symptom from a painted background.
  • Every project on the station renders the same mismatch: suspect the generated data or the installation, not one screen.

The reported case behind this article used an IO field configured as Output on a PC station; changing a field's function between Output and Input/Output is not part of this fix, so confirm the function and leave it as the application requires. Two neighboring faults live at the image level, not at the object level: imported graphics losing their transparent background at import and images turning white in this same runtime. Neither one is an IO field property.

Turn off the classic runtime design #

The runtime-wide design option sits under the HMI device in the project tree: select the PC station, open Runtime settings, the Screens group, the General page, and clear Use WinCC classic design runtime. The editor only stores object properties; runtime renders the generated screens through its installed visualization components under the design rules you selected. A runtime-wide rule can therefore override an object-level appearance, and this checkbox changes exactly that behavior — with it active, runtime repaints objects in the older design and puts a solid background back over your transparent IO field.

Runtime reading the project in its own way is a recurring pattern in this toolchain; the same editor-versus-runtime gap is why bitmap icons can look worse in runtime than in simulation.

Set the transparency value on the IO field #

Open the IO field's properties and go to Style/Design > Settings. Set the transparency value to 0; the percentage only takes effect when the field carries a visible, solid background, so a field whose background is transparent renders transparent with the value at 0. While you are in the properties, check for an animation or dynamic entry that can write the background color while runtime runs — such an entry repaints the field on top of everything you set here.

Transparent handling is object-specific elsewhere too: on other HMI lines, transparent backgrounds on dynamic text objects are their own configuration topic.

Why the 99% workaround reads as transparent #

If the screen must pass before the design switch is cleared, the reported diagnosis offers a stopgap: set the transparency percentage to 99% and set the field's background color to the light grey of the object beneath it. The arithmetic is the proof: at that setting the rendered field ends up within 100 - 99 = 1 percentage point of the grey underneath, and because the field's own background color is that same light grey, nothing in the picture separates field from background. It is a matched paint job, not transparency — it breaks the moment someone changes the color under the field, so treat it as a temporary measure only.

Rebuild all and restart the simulation #

Runtime reads generated data, not the editor's live project, so an appearance edit is invisible to a simulation still running from older data. Run Compile > Software (rebuild all), stop the existing simulation, and start a new one so it loads the regenerated data. Reach for rebuild all whenever the simulation behaves unexpectedly after an edit; it is the standard first response and it costs minutes. The same rebuild-or-nothing rule bites across WinCC generations — WinCC Flexible edits that never show in runtime are the classic case.

Clean the IM folder when the generated data is stale #

If the mismatch survives a full rebuild, treat the generated data itself as stale. Siemens Industry Support document 109778709 documents the cleanup: back up your project first, delete the folder labeled IM from the project, and then recreate it by running Compile > Software (rebuild all). The folder holds generated intermediate data rather than the editable project, but the documented procedure still begins with a backup, so make that backup before you delete anything.

Rule out the communication warning #

Run every transparency test with a live PLC connection. An IO field without live process data greys out and shows a yellow warning rectangle; that state reports invalid or unavailable tag values, and it will survive every appearance setting you change. If your screenshots show grey plus the yellow rectangle, restore communication or correct the tag connection first, then judge the background.

To separate the object from the station, place a new output-only IO field with the same transparent settings on a simple screen and run it. If both the old and the new object pick up a background, the fault is in the generated data or the installation, not in the object's configuration.

Escalation order and the decision #

Work the steps in this order and retest after each one, so the result tells you which layer failed:

  1. Clear Use WinCC classic design runtime, set the IO field transparency to 0, run Compile > Software (rebuild all), and start a fresh simulation.
  2. Still colored: back up the project, delete the IM folder, rebuild all, and retest.
  3. Still colored: move to the latest update level approved for the installed V13 environment as a comparison — SP1 Update 8 reproduced no transparency problem, although updating alone did not repair the reported installation.
  4. Still colored: repair or reinstall TIA Portal with its runtime components, regenerate the PC station, and retest. On the reported V13 SP1 Update 7 station this was the step that fixed it.

The decision, case by case. An IO field transparent in the editor and colored in runtime is a runtime design and generation problem: work the four steps in order and expect the reinstall to close the cases the earlier steps miss, as it did on the reported station. A grey field with a yellow rectangle is a communication problem: restore the live connection, because no appearance setting applies. A field that turns transparent after a rebuild but reverts in a simulation left running is stale generated data: restart the simulation after every rebuild. And when every project on the station renders the same mismatch after a verified rebuild, treat the installation as the fault, not the screen.

Questions asked

Does the same IO field transparency behavior exist in WinCC Advanced?

WinCC Advanced is a different runtime, and its IO field behavior has a different gate: an IO field there can only be made invisible through the output-only configuration chosen in the engineering setting, not through a runtime switch. The classic design option and the rebuild sequence described here belong to Runtime Professional on a PC station, so do not carry the same fix over to an Advanced panel.

Why is my IO field grey with a yellow rectangle instead of transparent?

That grey fill with the yellow warning rectangle is the invalid-data state: the field has no live connection to the PLC, so the process value is bad quality. It is a communication symptom, not an appearance one. The rectangle clears by itself once the connection and tag quality return, and no screen setting causes it or cures it.

Will moving from V13 SP1 Update 7 to Update 8 fix it?

Update 8 is a useful comparison level, because on it the transparency of an IO field reproduced no problem at all. Updating alone, though, was not the action that repaired the reported installation; the reinstall was. Treat the update as a test level when it is approved for the installed V13 environment, and keep the design switch, transparency value, rebuild and IM folder cleanup in the sequence regardless.

How many display formats does an IO field have in Runtime Professional?

Four. The Runtime Professional manual lists four display formats for entering and showing values in an IO field. Format is a property of how the value is presented, separate from the background style, so changing it neither causes the runtime background nor cures it. Keep format settings and appearance troubleshooting apart when you document the fix.

Keep reading

  • Troubleshooting

    WinCC Runtime time input shows AM/PM when Windows is 24-hour

    The picker on a DateTime I/O field takes its format from the language active in WinCC Runtime, not from the taskbar clock: English (United States) gives AM/PM entry, English (United Kingdom) gives 24-hour. Enable a 24-hour language and make it the start language, set that language's Short time to HH:mm and Long time to HH:mm:ss in Windows, or remove tt from the picker's custom pattern. Then rebuild, download and test 14:07:45.

    HMI and touchscreens

  • Troubleshooting

    Why a Parameter Set Drop-Down Needs a Double Tap on Touch

    The Parameter Set Control's Value drop-down opens on touch only when two contacts land as a recognized double-click, and a mistimed pair can block the cell for the mouse until the screen reloads. Pace the second tap about 300 ms after the first on the same spot, keep press-and-hold off, compare kiosk with windowed mode, and only then suspect the tablet's touch driver.

    HMI and touchscreens

  • Troubleshooting

    Why the PDATA.FWX configuration file could not be loaded

    The message means the panel could not read the runtime configuration file its project generated, so it shut the application down. Save a backup, delete the generated PDATA file from the project, compile again, and prove the project starts clean on the PC runtime before redownloading. If the panel still fails, delete its stale copy from the flash storage folder the message names and download again.

    HMI and touchscreens

Why an HMI touch foil is not a field-replaceable part