Why a Parameter Set Drop-Down Needs a Double Tap on Touch

HMI and touchscreens Published 9 min read

Short answer

The Parameter Set Control's Value drop-down opens on touch only when two contacts land as a recognized double-click, and a mistimed pair can block the cell for the mouse until the screen reloads. Pace the second tap about 300 ms after the first on the same spot, keep press-and-hold off, compare kiosk with windowed mode, and only then suspect the tablet's touch driver.

On this page
  1. Why does the Parameter Set Control drop-down open with a mouse but not on touch?
  2. How fast must the two taps be to open the Value list?
  3. Why does the mouse stop working after the failed touch?
  4. How do I tell a gesture problem from a touch driver fault?
  5. Which touch settings change double tap detection on the tablet?
  6. Does kiosk mode stop the drop-down from opening?
  7. When is the tablet the problem instead of the project?
  8. Questions asked

The drop-down in a Parameter Set Control opens on touch only when your two contacts land as a recognized double-click: same spot, inside the acceptance window the touch stack enforces. WinCC Unified PC Runtime V21 renders the list correctly — a mouse proves that — but the touch path has to deliver a timed pair, and a mistimed pair can leave the Value cell blocked for the mouse too until the screen reloads. This article gives you the pacing numbers, a bench measurement you can repeat, the reload rule for the blocked cell, and the order in which to clear gesture, setting, kiosk and driver causes. Run the tests with the machine stopped or on a bench runtime: a stray timed pair on the wrong cell can upload a parameter set to the controller.

Why does the Parameter Set Control drop-down open with a mouse but not on touch? #

The Value cell is not a single-tap target: the documented gesture for Unified runtime touch operation is a double-click, so the list opens only when your second contact lands quickly after the first, and a mistimed pair can leave the cell blocked for the mouse too.

The difference is the documented gesture, not a broken list. Siemens' operating instructions for Unified runtime touch operation define a double-click on a touch screen as two quick contacts on the same operator control, and the Parameter set control (RT Unified) object is built to display and manage parameter sets in Runtime and exchange them with the controller. Its Value cell therefore behaves as a selection control: the first contact selects and focuses the cell, the second opens the resource list — the configured set of allowed values behind the cell.

A mouse never shows this problem because button clicks arrive as finished events, while touch arrives as a stream of contacts the input stack has to judge as a pair. The same control on a Unified Panel needs the pair in quick succession — taps too slow or too fast leave the list closed — which matches the documented gesture and rules out a bad binding as the first suspicion.

Decision: treat the first tap as select and the second as open. If the pair is mistimed, expect a closed list, and expect the block described next.

How fast must the two taps be to open the Value list? #

Aim the second tap about 300 ms after the first, on the same spot, inside the acceptance window your tablet's double-click setting defines; 500 ms is a common example window, and pairs slower than the window read as two single taps that only select the cell.

Worked example — measure the pair on the bench. Record the screen with a phone camera at 60 frames per second, so one frame lasts 1000 ms / 60 = 16.7 ms. In the video:

  • A pair that opened the list showed the second contact 21 frames after the first: 21 × 16.7 ms = 350.7 ms, inside the example 500 ms window, so the runtime recognized a double-click.
  • A pair that failed slow showed 48 frames: 48 × 16.7 ms = 801.6 ms, outside the window, so the runtime saw two single taps and only selected the cell.
  • A pair that failed fast showed 5 frames: 5 × 16.7 ms = 83.5 ms; a gap that short can be judged as one long contact or contact bounce, which is why tapping harder or more often cannot help.

What moves the limit: the window value itself, read from the tablet's double-click or double-tap setting; the spatial tolerance, which rejects a second contact that drifts off the first, so keep both contacts near the center of the Value cell away from its borders; and the contact medium, because a glove changes contact timing. Reload the screen between trials so a failed pair cannot skew the next one.

Decision: pace the second tap about 300 ms after the first on the same central spot, and verify your own window with the driver's built-in double-click test before trusting any example interval.

Why does the mouse stop working after the failed touch? #

A mistimed pair leaves the Value cell holding focus or pointer capture, so the next mouse click lands on a control that thinks it is mid-interaction; reloading the screen rebuilds the cell and the mouse works again immediately.

A failed pair is not a clean failure: the cell can keep the state from the interrupted interaction, and every extra tap while it is blocked queues more events and holds the state in place. The recovery is the reload you already found — one reload of the affected screen returns the mouse at once. Do not test by striking the screen repeatedly; pressure is not the missing input, a correctly timed pair is.

Decision: if the mouse recovers after a reload, the fault is the blocked interaction state and the gesture timing is your target. If the mouse stays dead after a reload, the problem sits deeper in the runtime or its input stack, and the next check decides which.

How do I tell a gesture problem from a touch driver fault? #

Test an ordinary drop-down list on the same screen: if it opens by touch while the Parameter Set Control does not, touch input and the driver are reaching the runtime and your fault is the control's timed gesture, not the driver.

Run this sequence on a bench runtime or a stopped line, changing nothing but the input between steps:

  1. Reload the affected screen.
  2. Open the same resource-list entry with the mouse, to prove the list and its binding render.
  3. Touch an ordinary drop-down on the same screen, to prove contacts reach the runtime.
  4. Touch the Value cell once and record whether it selects, focuses, or does nothing.
  5. Deliver a paced pair, about 300 ms apart, on the same central spot.
  6. If the list stays closed, try the mouse once, then reload before the next trial.
Result What it proves Where the fault lives
Ordinary list opens by touch, Value cell does not Contacts and driver reach the runtime The control's timed double-click
No drop-down opens by touch anywhere The input path breaks before the runtime Touch driver or OS input settings
Value cell blocks the mouse after a failed pair Focus or pointer capture is stuck Interaction state; a reload clears it
Mouse stays dead after a reload The runtime or input stack is faulted Runtime shell; escalate below

When the whole screen's values look wrong rather than one control's gesture, run the triage in Is It the Driver, the Tag or the Screen? Diagnosing HMI Values. The mouse-versus-touch split shows up on other controls too: Why Touch JOG Buttons Start Late but Mouse Works Fine traces a touch path that behaves differently from a working mouse.

Decision: an ordinary list that opens by touch clears the driver for now; no list opening anywhere points at the driver layer next.

Which touch settings change double tap detection on the tablet? #

Two settings decide whether your pair counts as a double-click: the double-click speed or double-tap interval in the pointer and touch settings, and the press-and-hold or ClickLock feature, which turns a long contact into a right-click and can swallow the second tap.

Use the driver's built-in double-click test first, and change one setting at a time, recording each previous value so the result stays reversible:

  • Double-click speed (double-tap interval): widen it only when the built-in test rejects a normal, repeatable pair, then repeat the Value cell test.
  • Press-and-hold, ClickLock: turn it off. Touch-driver guidance for stuck touches says the same — keep click lock disabled — and the same long-touch mapping trips other software: CODESYS WebVisu long touch opens a right-click menu shows the identical cause and fix on a different runtime.
  • Spatial tolerance: some drivers expose how far the second contact may drift; leave it at the default unless the built-in test fails on position.

Decision: if the built-in test passes with your working cadence but the Value cell still fails while the mouse recovers after every reload, keep the settings that passed and move to the runtime environment checks.

Does kiosk mode stop the drop-down from opening? #

Kiosk mode can, because the kiosk shell changes how the runtime receives focus and draws the drop-down overlay above the control; compare the same screen in normal windowed mode, and if the failure appears only in kiosk mode, the shell's focus handling is your fault domain.

Compare like with like: same project, same screen, same display scaling, same resource list, only the mode changed — on the bench, not on a running line — and try the mouse after every failed pair. The runtime and operating-system settings that govern how combo boxes open matter here too, so compare them against a known-good station instead of inventing values.

The kiosk shell can also fail in ways that never touch your screens; one documented case is a Unified kiosk shell that stalls while establishing its connection, a useful reminder that shell and screen faults live on separate layers.

Decision: a failure that appears only in kiosk mode belongs to the shell's focus and overlay handling — document it for the vendor and bench-test in windowed mode. A failure identical in both modes sends you back to the driver layer.

When is the tablet the problem instead of the project? #

The tablet is the problem when no tap cadence opens the list while the mouse works after every reload: install the touch driver approved for your exact tablet model and OS build, because a generic driver can deliver contacts without the timing and release quality a double-click needs.

Record the evidence before touching the driver: tablet model, operating-system build, touch-device identity, and the driver provider and version from device properties. The reported unit in this failure pattern was a Higole F15 industrial tablet, and the driver that matters is the one its manufacturer publishes for that exact model and build — a package published for a Siemens IPC or IFP belongs to that hardware class, not to a third-party tablet, however similar the symptom. Update or reinstall only under the manufacturer's procedure, restart if the procedure calls for it, and run the driver's calibration or contact test before returning to Runtime.

If the touch stack still cannot hold a repeatable double-click after driver and settings work while the same project behaves on other input, move the runtime to hardware engineered for continuous operator touch, such as industrial panel PCs, and retire the tablet from that duty.

Decision: an exact-model driver that restores the timed pair closes the fault at the tablet; a tablet that fails every cadence with a clean runtime leaves it — the input hardware is the component to replace.

Questions asked

Does a gloved finger or stylus change the double-tap timing?

Yes. A glove adds contact delay and a larger contact area, so the pair you timed with a bare finger can fall outside the window when gloved. Re-run the video measurement wearing the glove you actually operate with, and if the model supports glove touch, use the manufacturer's glove mode rather than pressing harder.

Does the mouse double-click use the same timing as the touch double tap?

No. A mouse double-click is judged by the operating system's double-click speed for pointer buttons, with no touch driver in the path. That is why the cell can open normally with a mouse while the touch pair fails: the two input paths apply different acceptance windows to the same control.

Is there a timing setting to change on a Unified Panel?

On a Unified Panel you tune your cadence, not a setting: the double-click interval is part of the panel firmware, and the adjustment options discussed for tablets belong to the PC and driver side. If a correctly paced pair still fails on the panel, update the panel firmware through the manufacturer and treat a persistent failure as a support case.

Will restarting the runtime clear a blocked cell like a reload does?

Yes. A restart reloads every screen, so it clears the blocked focus state the same way a screen reload does, only slower. Use the single-screen reload during commissioning, and a full restart when several screens show the block or the runtime shell itself stops responding to input.

Keep reading

  • Troubleshooting

    Why WinCC flexible Runtime Cannot Control an S7-1200

    WinCC flexible Runtime on the PC is a separate HMI station, not a view into the MP277, so a working panel proves nothing about the PC path. Ping the S7-1200 from the Runtime PC, confirm the project connection uses the S7Online access point, then map that access point in Set PG/PC Interface to the adapter that reaches the real PLC, or to the simulation path when PLCSIM is the destination.

    HMI and touchscreens

  • How-to

    KTP700 Basic Runtime Startup Wait and the Start Center

    The Start Center wait on a KTP700 Basic is set on the panel, not in the project. Open Settings, select System Control/Info in the System section, set Autostart to ON where the panel shows it, and set the Wait selector to OFF. Runtime then starts at power-up and the defined project start screen appears without anyone pressing Start.

    HMI and touchscreens

  • How-to

    Run WinCC Flexible Runtime on PC Over MPI

    Yes. Point the S7ONLINE (STEP 7) access point in Set PG/PC Interface at your MPI hardware, give the PC the MPI address the panel used, set the project connection to SIMATIC S7 300/400, and start it with Project > Compiler > Start Runtime; the PC then polls the CPU 314 over MPI like the panel would.

    HMI and touchscreens

Why a PanelView 600 runs an hour ahead after daylight saving