Why a PanelView 600 runs an hour ahead after daylight saving

HMI and touchscreens Published 5 min read

Short answer

A one-hour offset after the seasonal change points to the terminal's daylight-saving setting. Enter Parameter mode from the lit lower-left block during power-up, enable daylight saving under System Settings > Date and Time, correct the clock once, and check the L32E processor clock separately.

On this page
  1. Read the offset before touching the clock
  2. Which clock you are actually looking at
  3. Enter Parameter mode and enable daylight saving
  4. Example: correcting a one-hour offset at the spring change
  5. Verify after the change
  6. Fixes to avoid
  7. Questions asked

A PanelView 600 that reads one hour ahead after the daylight-saving change almost always has its daylight-saving option disabled or its clock set to the wrong base time. The fix is a terminal setting, not application logic: power-cycle the terminal, touch the lit block in the lower-left corner during startup to enter Parameter mode, open System Settings > Date and Time, enable daylight saving, and set the date and time once against a trusted local clock. The L32E processor keeps its own clock and needs a separate check. Work through the checks below in order.

Read the offset before touching the clock #

Compare the PanelView display with a trusted local clock, such as a phone set to network time, and confirm both are on the same local time zone. A difference of exactly one hour after a seasonal transition points first at the daylight-saving configuration; anything else (minutes off, wrong date, a wrong year) points at the base time setting instead. Record the displayed time and the trusted time before you change anything, so you can tell whether the terminal applied no seasonal adjustment, a duplicate one, or simply carries a stale base time.

What you observe First check
One hour ahead right after the spring change Daylight-saving option under System Settings > Date and Time
One hour behind right after the autumn change Same option; the terminal has not dropped its seasonal hour
PanelView and L32E disagree Each device's clock separately; they are not synchronized by one setting
Minutes or the date are wrong The base date and time, not the daylight-saving option

Do not start with repeated power cycles or application changes. The power cycle is only the door into Parameter mode; it does not correct the time by itself.

Which clock you are actually looking at #

The time on the PanelView screen can come from two places: the terminal's own clock, shown by a time display object in the application, or a controller value the L32E supplies. Before changing anything, open the application in the engineering tool and identify which one the display reads. If it reads a controller tag, correcting the PanelView clock will not move that number, and the processor clock needs its own correction. Driving the terminal clock from the controller instead is covered in setting PanelView 600 time and date from the SLC clock, and a daily resynchronization scheme is covered in setting HMI clock time from PC and PLC daily.

If you instead want the processor itself to know the season, daylight saving time logic that provides a seasonal PLC bit is the pattern to follow on the controller side.

Enter Parameter mode and enable daylight saving #

Plan the access for a maintenance window: the power cycle interrupts the operator interface while the terminal restarts.

  1. Power-cycle the PanelView 600.
  2. During power-up, watch the lower-left corner of the screen for a lit block.
  3. Touch the lit block while it is visible to enter Parameter mode. The window is brief; if you miss it, power-cycle again and watch the corner rather than hunting through the running application.
  4. Open System Settings, then Date and Time.
  5. Enable the daylight-saving option.
  6. Review the displayed date, time and time-zone information against your site's local settings.
  7. If the clock is still offset, set it once to the correct current local date and time.
  8. Exit the parameter screen and let the terminal complete startup.

Enabling the option is what makes the next seasonal change automatic. The PanelView 600 must be powered on when the transition occurs for the adjustment to apply; a terminal that is switched off over the weekend of the change can come up with a stale offset, which is another reason to compare it against a trusted clock after every transition.

Example: correcting a one-hour offset at the spring change #

Inputs:

  • PanelView display: 09:30, read from the terminal after the spring change (the reader's reported condition)
  • Trusted local clock: 08:30, same time zone (network time on a phone)
  • Seasonal adjustment: 1 h = 3600 s (the standard daylight-saving shift)

Rule: the displayed offset is the terminal time minus the trusted time. If it equals the seasonal shift, the terminal has missed the transition, so enable the option and subtract the offset once.

Arithmetic:

Offset = 09:30 − 08:30 = 1 h = 3600 s

Corrected terminal time = 09:30 − 1 h = 08:30

Result: the offset matches the 3600 s seasonal shift exactly, which confirms the daylight-saving configuration as the cause rather than clock drift.

Decision: with daylight saving enabled and the clock set to 08:30, the terminal matches the trusted clock and the next transition is automatic, provided the terminal is powered on when it occurs. If the offset had been anything other than a whole hour (say 20 minutes), the daylight-saving option would not be the cause, and the base time setting would be the item to correct instead.

Verify after the change #

  • Compare the PanelView display with the trusted local clock on the same time-zone basis; both the hour and the date must match, since a wrong hour near midnight usually means a wrong date too.
  • Confirm the operator application starts normally after Parameter mode.
  • If the application shows controller time, read the L32E clock through its programming software and correct it there if it is off; the two devices now agree only because each was set, not because one drives the other.
  • At the next seasonal transition, repeat the comparison. If the terminal is off again, check first whether it was powered on across the transition, then re-inspect the option.

Fixes to avoid #

  • Do not hand-adjust the clock every six months. It hides the disabled option and leaves the next transition to fail the same way.
  • Do not toggle the daylight-saving option repeatedly. Enable it once, then correct the base time once; repeated toggling can add or remove the seasonal hour unpredictably.
  • Do not assume the PanelView and the L32E share a clock. They are separate devices with separate time sources.
  • Do not blame the application before checking terminal parameters. The Date and Time setting is a terminal parameter, not a screen object property.
  • Do not power-cycle more than the access requires. One cycle gets you into Parameter mode; further cycles fix nothing.

If the terminal still shows a wrong time after the option is enabled and the base time is set correctly, record the model, firmware revision and the observed times, and take it to the manufacturer's support channel rather than continuing to change settings.

Questions asked

Does enabling daylight saving on the PanelView also fix the L32E processor clock?

No. The terminal and the processor keep separate clocks. Enabling daylight saving only affects the PanelView's own time. If the application displays controller time or timestamps from the L32E, that clock must be corrected on the processor and given its own seasonal handling.

Can I enter Parameter mode without power-cycling the PanelView?

The documented access path is the lit block in the lower-left corner during power-up, so plan a power cycle in a maintenance window. Power-cycling alone does not fix the time; the setting must be changed once you are in Parameter mode.

Why is my PanelView one hour behind instead of ahead after the change?

The same check applies in reverse: the terminal has not removed or not added its seasonal hour, or its configured base time is wrong. Enable daylight saving, then set the date and time once against a trusted local clock. Do not toggle the option repeatedly hoping it lands correctly.

What if the display is right but a trend or alarm timestamp is still an hour off?

That value likely comes from the controller or was written before the correction. Identify which device supplies the timestamp, correct that device's clock, and accept that records already written keep their old times. New entries will carry the corrected time.

Keep reading

  • Troubleshooting

    Why PanelView 600 Plus Alarms Stay Blank and Configure Mode Crawls

    Blank alarms mean the alarm Trigger Type, whole-word trigger address and message value do not match the PLC bits — with Trigger Type on bit and the trigger on the whole word, the message value is the bit number plus 1. The close-to-five-minute Configure Mode exit is tag errors elsewhere in the application; deleting loaded runtime applications was tried and changed nothing. Re-map the alarms, clear every reported tag error, and both symptoms clear.

    HMI and touchscreens

  • Explainer

    What an HMI Is and How a Touch Panel Runs One

    An HMI is the hardware or software through which an operator watches and commands a controller. It is not written in a general-purpose language: you configure screens in a vendor engineering editor, compile the project into a runtime, and the touch panel computer runs that runtime while exchanging variables with the control logic over a driver you verify first.

    HMI and touchscreens

  • Troubleshooting

    Why the Vision Text Area Touch Keyboard Stops After 7.8.0

    On Ignition 7.8.0 the Vision Text Area fails its touchscreen permission check, so the on-screen keyboard never opens for it while every other touch component keeps working. The fix shipped in 7.7.7 and reached the 7.8 line by 7.8.2. Until the Gateway is upgraded, a one-line mousePressed script calling system.gui.showTouchscreenKeyboard restores input.

    HMI and touchscreens