IMDTouchKnowledge BaseShop main store

Explainer

Why WinCC to an S7-1500R/H needs no S7-REDCONNECT

HMI and touchscreens Published 7 min read

Short answer

WinCC connects to an S7-1500R/H redundant system through its system-wide system IP address, which the current Primary CPU always serves, so S7-REDCONNECT does not apply. If a communication-path failure on the X2 or X3 interface must not interrupt the HMI, use WinCC V7.5 script-based switching between the two CPU device IP addresses instead.

On this page
  1. Does WinCC need S7-REDCONNECT for an S7-1500R/H connection?
  2. What is the system IP address of an S7-1500R/H system?
  3. How do you set up the HMI connection to the system IP address?
  4. Why can the connection drop on X2 or X3 without a role change?
  5. How does WinCC V7.5 switch between the two CPU device IP addresses?
  6. How do you test controller failover and path failure separately?
  7. When do you use the system IP address and when script switching?
  8. Questions asked

On every S7-1500R/H project that runs WinCC SCADA the same question comes up: does the PC need S7-REDCONNECT, as it does with an S7-400H? It does not. WinCC connects to the redundant system through the system IP address, one address that belongs to the entire R/H system and is always served by the CPU that currently holds the Primary role. S7-REDCONNECT belongs to the S7-400H architecture, whose highly available S7 connections the S7-1500R/H system does not support. One gap remains: a communication-path failure on the X2 or X3 interface leaves the CPU Primary and the connection broken, and only for that case do you add script-based switching between the two CPU device IP addresses in WinCC V7.5.

Does WinCC need S7-REDCONNECT for an S7-1500R/H connection? #

No. WinCC connects to an S7-1500R/H redundant system through the system IP address, which the CPU currently holding the Primary role serves, and S7-REDCONNECT belongs to the S7-400H architecture because it is the PC-side counterpart of the highly available S7 connections that the S7-1500R/H system does not support.

An S7-1500R/H system runs two identical CPUs: one takes the Primary role and serves the plant, the other follows as Backup. The process I/O sits on the redundant I/O side of the architecture, covered in ET 200SP HA redundant I/O with S7-1500R/H. Two kinds of address identify the pair on the network: a device IP address belongs to one CPU, and the system IP address belongs to the redundant system as a whole. A WinCC connection aimed at the system IP address is always answered by the current Primary, so a role change needs no change in the WinCC configuration.

S7-REDCONNECT has no function in this architecture, because the R/H system does not offer the connection type it serves. The older redundant controllers use a different mechanism; see connecting an S7-400H to WinCC Professional with a Device Proxy. Keep two properties apart from here on: controller redundancy and communication-path redundancy are separate, and both CPUs can be perfectly healthy while the HMI's route to the serving CPU is broken.

What is the system IP address of an S7-1500R/H system? #

The system IP address is one extra address configured on the R/H CPUs in addition to their device IP addresses, and it identifies the whole redundant system on the network instead of one individual CPU.

The R/H CPUs support it on all interfaces. You configure it for the interface the HMI network uses, and SIMATIC HMI devices and WinCC Runtime applications build their HMI connection to that address. Because the CPU that currently holds the Primary role serves every such connection, the Runtime configuration stays independent of which CPU is Primary.

Example address plan, illustrative only: CPU 1 gets the device IP address 192.168.10.11, CPU 2 gets the device IP address 192.168.10.12, and the redundant system gets the system IP address 192.168.10.10, all with subnet mask 255.255.255.0. Check that all three fall into one subnet: 192.168.10.10 AND 255.255.255.0 = 192.168.10.0, 192.168.10.11 AND 255.255.255.0 = 192.168.10.0, 192.168.10.12 AND 255.255.255.0 = 192.168.10.0. The three network parts match, so the HMI needs no route between its own subnet and the controllers. Keep the system address distinct from both device addresses: a duplicated address, a system IP address outside the HMI subnet, or a missing route produces an apparent redundancy fault before any failover ever happens. Record the interface, both device addresses and the system address before you configure Runtime.

How do you set up the HMI connection to the system IP address? #

You point the partner address of the HMI connection at the system IP address; in a TIA Portal project you create that connection in connection mode or by dragging a tag from the redundant system into an HMI screen, and STEP 7 sets it up automatically.

In the devices and networks editor, the Connections icon on the toolbar activates connection mode, and from there you draw the HMI connection between the HMI device and the redundant system. Dragging a tag from the redundant system into an HMI screen or into the HMI tag table does the same job. In a WinCC V7.5 project, open the connection configuration, create the S7 connection to the redundant system and enter the system IP address as the partner node address. The check is the same in both tools: the connection configuration shows the shared system address, not the device address of either CPU.

Why can the connection drop on X2 or X3 without a role change? #

X2 and X3 are not implemented as switches, so no fully redundant communication path leads to them, and a cut cable between the Primary CPU and its adjacent switch port breaks the HMI connection while that CPU keeps the Primary role.

A link-down on its own port gives the CPU no reason to hand the Primary role to its partner: the CPU, its program and its I/O are all healthy. The system IP address keeps following the serving CPU, and the HMI's path to that CPU is gone. This is a path failure, not a controller failure, and the redundancy reacts to controller failures. The same logic applies to the HMI's own uplink or to a shared switch segment: switching destination addresses recovers nothing when both destinations depend on the same failed segment. Trace the real network before you commit to an availability concept: identify each CPU-to-switch cable, the HMI's own attachment and every shared uplink.

How does WinCC V7.5 switch between the two CPU device IP addresses? #

WinCC V7.5 can change the IP address used by one connection through scripting, a method the WinCC System Manual documents under software redundancy for S7-1500R/H, and the switch runs between the two CPU device IP addresses.

Use this method when the X2 or X3 exposure is unacceptable for your plant. Implement the address change exactly as the manual and the application example describe it, and use only the timing and diagnostic interfaces documented for your installed version. Specify three things before you write the logic: the conditions that trigger a switch, the recovery policy once the original CPU is reachable again, and the indication the operator sees. Base a successful switch on restored connection status and good tag quality, never on one bad sample; unstable switching can stop either connection attempt from ever completing, and the operator then has no data at all.

How do you test controller failover and path failure separately? #

You run two separate tests in an approved commissioning window: first provoke a Primary to Backup role change and watch the HMI reconnect through the system IP address, then cut the Primary CPU's X2 or X3 cable and watch the connection drop while the roles stay unchanged.

Test one covers the controller failure. Force the role swap with the procedure the vendor documents for testing, and read two things at once: the CPU roles in the controller diagnostics and the connection status in WinCC. Expected result: the roles swap, the connection drops and re-establishes on its own, and the tags return to good quality with no change to the connection configuration.

Test two covers the path failure. Pull or sever the cable between the Primary CPU and its adjacent switch port on X2 or X3. Expected result: the CPU stays Primary, the connection reports a fault and tag quality goes bad. Then confirm that the second CPU is still reachable over its own path, because that reachability is the precondition for script switching to cover this case. Run both tests only on an idle or simulated process, or in a window the process owner has approved; while the connection is down, the operator station is blind to the plant.

When do you use the system IP address and when script switching? #

Use the system IP address alone when CPU failure coverage is enough and the HMI path runs over the fully redundant network arrangement; add the documented script switching between both device IP addresses when a single X2 or X3 cable failure must not interrupt operator visibility.

Failure to cover Mechanism What you configure
CPU failure only HMI connection to the system IP address The system IP address as the partner address, no switching logic
CPU failure plus an X2 or X3 cable failure Script switching in WinCC V7.5 Both device IP addresses as destinations, with documented and tested switching logic
Highly available S7 connections S7-REDCONNECT Not applicable, the S7-1500R/H system does not support this connection type

The default decision on an S7-1500R/H project is the system IP address: no switching logic, nothing that can oscillate, and every controller role change covered. Add script switching only when the HMI network attaches over X2 or X3 and a single cable must not cost operator visibility, and prove that switch on the bench with a changing process value before the plant relies on it.

Questions asked

Where is the WinCC V7.5 switching method documented in detail?

The application example with contribution ID 101908495, WinCC communication with S7-1500, S7-1200 and ET 200SP, covers the method in chapter 7, next to the software redundancy description in the WinCC System Manual. Download both through Siemens' official documentation channels and implement the procedure exactly as published instead of guessing at script interfaces for your installed version.

Can you pin the HMI connection to one fixed CPU?

Yes. The connection configuration in TIA Portal contains the check box "Use the system IP address for switched communication". Clear it and the HMI connection changes over permanently to the device IP address of the CPU you selected, so it stops following role changes. Keep it selected for a redundant connection, and clear it only when you deliberately want to observe one fixed CPU, for example during diagnostics.

How do you create the system IP connection for WinCC Unified?

Open the Network view, select the "Connections" tab and choose HMI Connection, then draw the connection between the Unified panel and the redundant system's system IP address. The mechanism matches WinCC Runtime on a PC: the current Primary CPU answers, and the panel needs no switching logic of its own to survive a controller failover.

Does an address that answers a ping prove the HMI connection is healthy?

No. A ping proves only that a network path to the address exists; it says nothing about the S7 connection or about tag acquisition. Judge the connection by its reported status and tag quality, and read a controller value that is changing: a screen can keep showing its last received value after communication stops, so a steady display is no evidence of a live connection.

Keep reading

  • Troubleshooting

    Comfort panel redundant H system connection over Ethernet

    A TP1900 Comfort panel cannot be configured in WinCC flexible, so the redundant connection to a 412-H station is engineered in the WinCC environment of TIA Portal: the panel talks to the active CPU over Ethernet, and a PROFINET media redundancy ring in client role protects the cable path. Accept the result with two separate tests: a controlled CPU changeover and a single-cable removal.

    HMI and touchscreens

  • Troubleshooting

    Fix WinCC Professional runtime not connecting to the S7-1500

    WinCC Professional Runtime can start, load screens and raise no error while the HMI connection leaves through the wrong PC network adapter, because the access point selects the interface automatically. Disable that automatic option, assign the access point to the PLC-facing adapter in Set PG/PC interface, re-download the runtime and restart.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC Runtime Advanced shows no data through a CP343-1 Lean

    STEP 7 goes online through the CP343-1 Lean, but WinCC Runtime Advanced opens with no tag update and no error banner, because the S7 connection was given the CP's slot number. The CP cannot service an HMI read; the CPU-side endpoint lives in the CPU. Enter the CP's IP address with rack 0 and slot 2 — the CPU 316-2 DP's slot in a standard S7-300 central rack — and no FC5 or FC6 call is needed in the PLC program.

    HMI and touchscreens

Why a Twido needs no Comm macro or EXCHANGE for an HMI button