Troubleshooting
Why WinCC Unified PC Runtime shows a red topology line
Short answer
WinCC Unified PC Runtime communicates over IP only and does not take part in LLDP topology discovery, so a red line and an IRT port diagnostic describe an unvalidated drawing, not a broken HMI connection. Delete the PC Runtime port interconnection, keep the IP network, and verify the Runtime PC path separately.

On this page
- Why does the topology show red on the Runtime PC when the HMI works?
- Why does TIA Portal report "IRT not possible at this port"?
- How do I remove the port interconnection correctly?
- Why does Runtime work with the simulator but not the hardware PLC?
- Which addresses and routes must the Runtime PC check?
- Why does secure communication or certificate trust block Runtime on real hardware?
- What about alarm 1637 on the S-200 servo drive?
- What is the decision for each symptom?
- Questions asked
A red line on the WinCC Unified PC Runtime in TIA Portal's topology view means the drawn port interconnection cannot be validated, not that Runtime tag access has failed. WinCC Unified communicates over IP only and does not provide the LLDP neighbor behavior the topology editor expects, so the red line and diagnostics such as "IRT not possible at this port" describe an unvalidated drawing entry. The fix is to delete the PC Runtime port interconnection, keep both devices on the IP subnet in Network view, and then verify the Runtime PC's own path to the PLC separately.
Why does the topology show red on the Runtime PC when the HMI works? #
Because the topology editor checks physical port-to-port neighbor relationships for devices that answer LLDP discovery, and a WinCC Unified PC Runtime station answers none. PROFINET uses LLDP for topology diagnostics, and topology-capable devices send LLDP frames on their ports in the factory setting; the PC Runtime communicates solely over IP, so the editor can never confirm the drawn cable and flags the line red or disconnected. A Unified HMI panel on the same network operating perfectly is the proof: the PLC serves HMI data, and the red line describes only the missing LLDP partner, not a communication failure.
Why does TIA Portal report "IRT not possible at this port"? #
The diagnostic concerns a PROFINET port expectation that a PC Runtime station cannot meet, because isochronous real-time is a scheduled PROFINET class between devices that support it. An HMI tag connection from Unified Runtime needs no IRT relationship with the PC at all. When the project draws the PC station as a physical port partner of the S7-1200 G2's PROFINET interface, the downloaded topology cannot be matched and the port reports the mismatch together with messages such as "port cabling or configuration is inconsistent". Treat both messages as symptoms of the same wrong drawing entry, not as evidence of a broken link.
How do I remove the port interconnection correctly? #
Delete the physical port line to the PC Runtime station and keep the IP subnet assignment. Follow this order:
- Open Devices & Networks and switch to the topology view. Find the port line between the S7-1200 G2 PROFINET interface and the SIMATIC WinCC Unified PC station.
- Delete that port interconnection. Leave both devices assigned to the same IP subnet in Network view; that subnet entry is what the HMI connection uses.
- Check the real cabling against the remaining drawn lines. If a cable actually passes through a switch, draw the relationship to the switch or omit the physical entry instead of depicting a direct cable that does not exist.
- Compile the hardware configuration and download it to the PLC.
- After the download, confirm that the diagnostic buffer no longer reports the removed relationship, and verify Runtime tag access with an actual tag read.
Why does Runtime work with the simulator but not the hardware PLC? #
A simulator session stays inside the engineering computer, so it exercises none of the hardware path: the Runtime PC's adapter, the switch, the cable, or the CPU's own access settings. Passing the simulator therefore proves the project logic while leaving every physical-layer cause untested. When only the hardware connection fails, work through the PC network path, the configured HMI connection endpoint and the security settings in that order, because a failure in each layer produces the same symptom in the project. If PLC online access from TIA Portal also fails, the fault is in the network path; if online access succeeds but Runtime alone fails, move to the HMI connection and security configuration.
Which addresses and routes must the Runtime PC check? #
The Runtime PC must hold its address on the adapter that carries Runtime traffic and must route the PLC address through that same adapter. As an example, with the addresses this kind of installation uses:
| Device | Example address | Commissioning check |
|---|---|---|
| S7-1200 G2 PLC | 192.168.0.1 | Read the address and mask online from the hardware |
| Unified HMI panel | 192.168.0.2 | Confirm uniqueness on the subnet |
| Servo drive 1 | 192.168.0.3 | Confirm the downloaded address matches the device |
| Servo drive 2 | 192.168.0.4 | Confirm the downloaded address matches the device |
| Runtime PC | 192.168.0.5 | Confirm the address sits on the active adapter Runtime uses |
Then run the deciding tests:
- Identify the adapter holding the Runtime PC address and confirm its link is up.
- Ping the PLC address from that PC. A reply proves IP reachability but not an HMI session; still, no reply ends the search at layer 3.
- With more than one adapter present (a VPN or virtual adapter counts), confirm the route to the PLC address leaves through the intended adapter; disable unused adapters temporarily while commissioning.
- Remove unmanaged variables from the path: bypass an unconfigured VLAN, a filtering switch rule or a routed segment, so the baseline is a plain switched connection on one subnet.
A duplicate address anywhere in the plan produces intermittent address resolution even when link LEDs stay green, so read the actual address and mask from every device instead of trusting the offline project.
Why does secure communication or certificate trust block Runtime on real hardware? #
If the CPU restricts communication to protected PG/PC and HMI access, the Runtime station must present a configuration and certificates the CPU trusts, and certificate validation also depends on agreeing clocks. Compare the time and time zone of the PLC, the engineering station and the Runtime PC before touching certificates; a clock disagreement fails trust exactly like a missing certificate. In the certificate manager, identify the station by its computer name rather than by an IP address, because the name is what the certificate binds to. The PLC driver for the connection should be the one for the S7-1200/1500 family, and its endpoint must resolve to the PLC's actual address, not to a simulator endpoint or a stale interface assignment. A certificate or clock failure on a TLS-protected link to another device shows up the same way; the separate article on the S7-1500 MQTT TLS error 8089 and CPU clock versus certificate trust walks that diagnosis. Record whether PLC online access and Runtime tag access fail together or separately; the article on why WinCC Unified PC Runtime fails to open its PLC connection continues from that point.
What about alarm 1637 on the S-200 servo drive? #
Alarm 1637 reports that the safety configuration is not protected, and the documented remedy is to set the drive's user name and password. Leaving it unprotected because a Python program also talks to the PLC is not a safe trade: the alarm concerns the drive's safety configuration storage, not your communication, and protecting that configuration does not affect a Python connection to the PLC. Keep the drive's protection enabled and, if you need machine data in Python, read it from the PLC or an OPC UA server on the controller instead of weakening the drive. One safety note belongs here: never disable or bypass a drive safety function on a machine that will run.
What is the decision for each symptom? #
Delete the PC Runtime port interconnection and stop reading the red line as a connection failure: the HMI connection rides on the IP subnet and needs no topology entry. If the HMI panel works but the PC Runtime does not, the topology was never the problem; diagnose the Runtime PC's adapter, route, HMI connection endpoint and certificate/clock trust as separate checks, in that order. If the simulator works and hardware does not, the PC network path is untested, not broken by the project. And for alarm 1637, set the drive's protection credentials as documented and leave the safety configuration protected.
Questions asked
Can WinCC Unified PC Runtime work without a topology entry in TIA Portal?
Yes. The PC Runtime station joins the IP subnet in Network view like any other device, and its HMI tag connection runs over standard TCP/IP. PROFINET topology entries describe physical neighbor relationships for devices that answer LLDP discovery; a PC Runtime station does not, so the project compiles, downloads and communicates with the port interconnection removed.
Why does my Unified Runtime reach the simulator but not the hardware CPU?
A simulator session never leaves the engineering computer, so it bypasses the Ethernet adapter, the switch, the cable to the CPU and the CPU's own communication settings. When only the hardware connection fails, check the adapter that holds the Runtime PC address, the route to the PLC address, the HMI connection's controller endpoint, and the CPU's secure-communication and certificate settings, in that order.
Can I leave the S-200 servo safety configuration unprotected so Python can read it?
No. Removing that protection weakens the drive's safety configuration storage. Your Python program talks to the PLC, not to the drive's safety parameters, so protecting the configuration does not affect it.
Does the red topology line prove the HMI connection has failed?
No. The topology editor validates physical cabling between ports that support LLDP discovery. WinCC Unified communicates over IP only and answers no such discovery, so the line stays red while tag access works normally. Prove communication with an actual tag read or the PLC's online status, never with the color of a topology line.