WinCC flexible 2008 Runtime on other brands of panel PC
Short answer
Yes on Windows XP Professional SP2 or SP3: any PC that meets the delivery release requirements can host WinCC flexible 2008 Runtime, regardless of brand. On Windows XP Embedded, treat B&R, AAEON and other brands as unconfirmed — an embedded image carries brand-specific components and drivers, and a normal boot proves nothing.
On this page
Yes, with a split that decides everything. On Windows XP Professional with Service Pack 2 or 3, the vendor's own guidance allows any PC that complies with the WinCC flexible 2008 Runtime requirements, so a B&R, an AAEON or any other brand of panel PC qualifies on its specifications alone. On Windows XP Embedded, the situation reverses: the delivery release names approved systems for the embedded operating systems, and an embedded image is assembled from brand-specific components and drivers, so an other-brand panel PC that boots to a normal desktop has proven nothing. This article walks both branches — reading the Windows edition correctly, checking the requirements with real numbers, deciding the embedded case by documented approval instead of a successful boot, and bench-testing the exact machine before it becomes the operator station.
Read the Windows edition before comparing anything #
Windows XP Professional and Windows XP Embedded are not two flavors of the same compatibility answer; they are two different tests. Professional is the general-purpose desktop operating system. Embedded is a componentized build: an integrator assembles the image for one specific device from the drivers and components that device needs, which is why the functionality in an embedded image is largely brand-specific.
Read the edition from the system properties of the running image before any comparison. A unit that reports Windows XP Embedded goes down the embedded branch even when the report also shows a service pack. The year in the label dates the embedded release the image was built from; it is not a compatibility approval, and it says nothing about which components the integrator put in.
The branch decision:
- Windows XP Professional at SP2 or SP3 — a requirements check against the delivery release; the brand of the panel PC is not a factor.
- Windows XP Embedded, 2002 or 2009 label — an approval check on the exact system and image; a normal boot is not evidence.
The XP Professional branch: the requirements document decides #
For this branch the vendor guidance is explicit: with the runtime on Windows XP Professional SP2 or SP3, any PC complying with the requirements can be used — no approved-systems list and no brand restriction. The deciding document is the delivery release for WinCC flexible 2008 (Siemens Industry Support document ID 29735640), which lists the runtime system requirements. Compare the candidate against the minimums and size it to the recommended values.
The document names a Pentium M class processor for Windows XP and recommends 1 GB of memory for the runtime role and 1.5 GB for the engineering role.
Worked example, with illustrative inputs against those documented requirements: a used third-party panel PC reports Windows XP Professional SP3, a Pentium M processor and 512 MB of installed RAM. The processor line passes — Pentium M is the class the document names for Windows XP. The memory line fails: the runtime recommendation is 1 GB, which is 1024 MB, so the unit is 1024 - 512 = 512 MB short, and successful booting does not change that arithmetic. Add memory to reach 1024 MB and the unit becomes a legitimate candidate; until then it does not comply, whatever its brand.
One requirement sits outside the hardware table: match the runtime service pack to the project. The release note for Service Pack 3 requires SP3 on engineering systems as well as runtime systems, with all HMI devices upgraded together — a project engineered in SP3 is meant to run on an SP3 runtime, not on a base-version runtime on the panel PC.
The XP Embedded branch: approval attaches to the system, not the boot #
For the embedded operating systems, the delivery release changes shape: it names approved systems instead of publishing a generic PC specification. That structure exists because an embedded image is assembled per device, so the same runtime meets a different set of drivers and components on each brand's hardware. A B&R or AAEON unit can boot Windows to a normal desktop and still lack a video driver the runtime's rendering path expects, a touch controller driver, or an operating system component the runtime installation requires — the gaps surface during operation or after a restart, not at power-on.
The vendor publishes a dedicated installation procedure for the embedded case (Siemens Industry Support document ID 40237764). Its first steps are a restart of the system and work in the Windows command console, because the image has to be prepared before the runtime goes on; the procedure presumes the image already contains the components the runtime needs.
The decision here: if the exact system model is one of the approved systems for the release in use, proceed to the bench test. If it is any other brand's embedded unit, the combination is unconfirmed — either verify the exact image on the exact machine per the documented procedure, or change the operating system branch. The same discipline applies to any software hosted on embedded hardware, and it is laid out in Windows Embedded panel PC software compatibility checks.
Prove the exact machine on the bench #
Whichever branch the panel PC is on, the final evidence comes from the machine, not the paper comparison:
- Clear any requirements shortfall first — a unit below a recommended value is not a test candidate yet.
- Install the runtime with its service pack matched to the engineering station that produced the project, upgrading all HMI devices together when Service Pack 3 is in play.
- Start the real project against a test controller on an isolated bench; a touch or write fault during testing must never be able to move a live output.
- Exercise every screen, touch input and communication driver the application uses — displayed values must update and every operator action must register.
- Power-cycle the panel PC and repeat. The OS and the runtime must return to the same working state; a driver that vanishes after restart is the classic embedded-image failure and ends the evaluation.
On XP Professional, after the requirements pass, this test is short. On XP Embedded, it is the verification no document can give you.
The decision, and the exits when the answer is no #
- Windows XP Professional at SP2 or SP3, requirements met — run the Runtime; the brand neither qualifies nor disqualifies the machine.
- Windows XP Embedded on an approved system — run it.
- Windows XP Embedded on another brand — do not deploy it unverified; validate the image per the documented procedure or change the operating system branch.
When the machine in front of you is an other-brand embedded unit, forcing a 2002 or 2009 image to comply is rarely the best use of the effort, because two documented exits exist. Service Pack 5 for WinCC flexible 2008 documents Windows 7, 32 and 64 bit, for the runtime system as well as the engineering system, so a compliant Windows 7 PC hosting the SP5 runtime is the supported way off Windows XP; the license side of that platform is covered in WinCC flexible 2008 lifecycle and the Runtime Advanced license. The steps for moving a 2008 project into PC runtime are in Running a WinCC Flexible 2008 Project in PC Runtime. And when the old panel cannot be validated, the hardware class for that job is an industrial panel PC running the runtime on a supported operating system.
Questions asked
Can a B&R or AAEON panel PC host WinCC flexible 2008 Runtime at all?
On Windows XP Professional, yes: the vendor allows any PC that complies with the delivery release requirements, so the brand is not a factor. The same three checks — edition, requirements, service pack — decide every brand. On Windows XP Embedded, no other brand is documented: the approved-systems list covers the vendor's own systems, so an embedded unit of another make stays unverified until the exact image passes a bench test on that machine.
Why is a booting XP Embedded image not proof?
An embedded image is assembled for one device, so another brand's hardware can boot Windows normally while missing a display or touch driver the runtime needs, or an operating system component the installation requires. Those gaps appear during operation or after a restart, not at startup. Back up the working image before any installation attempt on an embedded unit, so the panel can be returned to its previous state.
What should a third-party XP Professional panel PC meet?
A Pentium M class processor for Windows XP and 1 GB of memory for the runtime role, with 1.5 GB recommended for the engineering role. Check the memory line first: it is the one old panel PCs most often miss. Match the runtime service pack to the project as well, because the service pack must be present on engineering and runtime systems alike.
Is there a documented installation path for XP Embedded?
Yes. The vendor publishes a dedicated procedure, document ID 40237764, whose first steps are a restart of the system and work in the Windows command console, because the image must be prepared before the runtime is installed. It presumes the image already contains the components the runtime needs, so run it only on the exact unit being evaluated.