WinCC Unified HMIRuntime.FileSystem.Browse for file lists

HMI and touchscreens Published 6 min read By IMDTouch engineering team

Short answer

HMIRuntime.FileSystem.Browse() lists the entries of a WinCC Unified panel folder and IsDirectory() sorts folders from files; take the display name from the text after the last slash. Trigger any file write from a screen object: Task Scheduler tasks run as user scs, which has no write access to the industrial home folder, so scheduled CSV writes do nothing.

On this page
  1. What replaces the VBS FileSystem objects
  2. List a folder from a screen script
  3. Cut the display name from the full path
  4. Write files from a screen trigger, not the Task Scheduler
  5. Create the parent folder before the subfolder
  6. File selection stays inside the runtime
  7. The decision for each case
  8. Questions asked

WinCC Unified has no Visual Basic Script FileSystem objects, and with them the familiar folder listing disappears from JavaScript. The runtime object model fills the gap with the HMIRuntime.FileSystem branch: HMIRuntime.FileSystem.Browse() returns the path names of a folder's entries, and HMIRuntime.FileSystem.IsDirectory() tells you which of those entries are subfolders. Take each display name from the text after the last slash of the returned path. Before you write anything, keep the trigger rule in mind: file creation and writes work when a screen object fires the script, and they do nothing when the Task Scheduler fires it, because scheduler tasks run as user scs, which has no write access to the industrial home folder. This article gives the listing steps with code, the name extraction with the arithmetic shown, and the decision for each case.

What replaces the VBS FileSystem objects #

On Windows CE panels, VBS listed a folder through the Dir method of the FileSystem object; on Windows, through the Files collection of the Folder object. Neither object exists in JavaScript, so the WinCC Unified runtime object model was extended with HMIRuntime.FileSystem, and those methods are documented for Unified Comfort Panels and for Unified PC Runtime alike.

Browse() takes a folder path and returns the path names of its entries — files and subdirectories together. It enumerates a directory from script; it is not a file-selection dialog and it does not read file contents. IsDirectory() answers, for one returned path name, whether that entry is a directory. The method documentation notes exactly this pairing: the path names Browse returns are the inputs IsDirectory expects.

List a folder from a screen script #

  1. Attach the script to a screen object — a button event on an HMI screen — so the runtime executes it in screen context. The section below on writes explains why the Task Scheduler is excluded.
  2. Call Browse() on the exact folder the files live in, for example C:/Data/temp/ on a Windows-style host or the internal folder your project uses.
  3. Call IsDirectory() on every returned path and keep the result beside the path.
  4. While you develop, send the requested folder, each returned path and its classification to the Trace Tool; the trace shows the folder the runtime actually read.
  5. Fill the on-screen list from the classified entries and keep the full path in every row, because the next file operation needs the path, not the label.
// Illustrative pattern. Browse and IsDirectory are the documented
// HMIRuntime.FileSystem methods; the variable names are examples.
const folder = "/home/industrial/mydatadir";          // directory to list
const entries = HMIRuntime.FileSystem.Browse(folder); // entry path names
for (const entry of entries) {
  const isDir = HMIRuntime.FileSystem.IsDirectory(entry); // true: subfolder
  const name = entry.substring(entry.lastIndexOf("/") + 1); // display name
  // while testing, write folder, entry and isDir to the Trace Tool;
  // show name in the list and keep entry for the later file work
}

The loop is the illustrative shape, not a copy of the reference page. Take the exact signature and result handling for Browse from the RT Unified JavaScript object model documentation of your TIA Portal version, inspect the operation result rather than assuming success because the next statement ran, and continue dependent work only once the operation has completed.

Cut the display name from the full path #

Operators should read names, not paths. The display name is the final path component — everything right of the last slash:

const displayName = entryPath.substring(entryPath.lastIndexOf("/") + 1);

Worked example, using the entry path /home/industrial/mydatadir/mysubdir/log1.csv: the string is 44 characters long and its last slash sits at index 35, so substring(36) returns the remaining 44 − 36 = 8 characters, log1.csv. The same arithmetic on the directory entry /home/industrial/mydatadir/mysubdir — 35 characters, last slash at index 26 — gives substring(27) and the remaining 35 − 27 = 8 characters, mysubdir.

Two rules keep this safe. If a directory entry arrives with a trailing slash, remove that separator before extracting, while the operational value keeps the original path. And a display name is not a unique identifier — two folders can hold files with the same name — so every row stores its full path for the actual file work. The string operation changes presentation only; it neither validates the file nor grants access to it.

Write files from a screen trigger, not the Task Scheduler #

A listing proves visibility, not write permission. The verified sequence on a Unified Comfort Panel ran CreateDirectory for the subfolder, WriteFile for the CSV and AppendFile for later additions, all from a button on an HMI screen, and it created both the folder and the file. Triggered from the Task Scheduler instead, the same work does nothing: scheduler tasks execute as user scs, and scs has no write access to industrial's home folder (/home/industrial). The trigger is the difference, not the path syntax.

The rule follows: any script that creates folders or writes files on the panel is called from a screen object. Seeing the folder in the Toolbox FileBrowser proves only that the directory exists and is enumerable — it says nothing about whether the calling account may create a file there. A script that runs but skips its file work is a known failure shape on the PC line as well; the article on why a WinCC Runtime Advanced VBScript runs but does not copy a CSV documents the same pattern.

Create the parent folder before the subfolder #

One CreateDirectory call creates one level. A call for the two-level example path fails when the parent does not exist yet, the same way mkdir without the -p option fails on Linux. Create the parent first and the subfolder second; that two-step order is part of the verified Comfort Panel sequence. When the parent already exists, a single call for the subfolder is enough.

File selection stays inside the runtime #

An operator who should pick a file inside the visualization cannot use Windows File Explorer for it. Explorer is a standalone application: it can run alongside the browser, but it cannot be embedded in the web page that WinCC Unified Runtime serves, and no mechanism returns a selection from it to the runtime. The supported routes are a list screen you fill from Browse(), or the FileBrowser faceplate from the SIMATIC WinCC Unified Toolbox application example — a complete faceplate-based implementation, comparable in function to the OpenFileBrowser system function. A file that lives on the operator's browser PC stays out of reach either way; design a transfer step that copies it into storage the runtime can read before any listing or file method touches it.

The decision for each case #

Case Decision
List a folder's files and subfolders HMIRuntime.FileSystem.Browse() from a screen script, IsDirectory() on every returned path
Show names without paths Substring after the last slash; the row keeps the full path
Create a folder or write a CSV Screen-object trigger; parent folder created before the subfolder
Automate the write Not from the Task Scheduler: its scs tasks cannot write the industrial home folder; move the trigger into a screen event
Operator selects a file Toolbox FileBrowser faceplate or a Browse-built list screen, never Windows File Explorer
Unified Basic Panel Methods documented for Comfort Panels and PC Runtime; run a one-button create-and-write test on the Basic panel first and keep the USB stick path as the fallback

Verify each decision on the exact runtime target with your TIA Portal version before the pattern is copied across a project: the engineering tool version, the target model and the runtime build are separate checks.

Questions asked

Does the listing also work on a Unified Basic Panel?

The FileSystem methods are documented for Unified Comfort Panels and Unified PC Runtime. A reported Basic Panel case on TIA V19 Update 3 wrote to the USB stick path (X61) from a screen button but created nothing in the internal folder, even though the Toolbox FileBrowser showed that folder. Before building on a Basic Panel, run a one-button test that creates one folder and one file, and keep the USB stick as the fallback destination.

Does Browse list files on the operator's browser computer?

No. HMIRuntime.FileSystem addresses the storage of the runtime host, the panel or the PC Runtime machine. When the visualization runs in a web browser, the calls still execute on the runtime, so a file on the operator's PC is invisible to Browse and to the write methods. Such a file first needs a transfer into storage the runtime can read; only then can the script list and process it.

How do I tell an empty folder from a failed Browse call?

Inspect the operation result instead of trusting the absence of output. A completed call that returns no entries means the folder exists and is empty; a failed call means the path or access did not resolve. While developing, write the requested folder and every returned path to the Trace Tool, so the trace shows the folder the runtime actually read rather than the one you meant to ask for.

Keep reading

  • Troubleshooting

    Why WinCC Unified CSV access needs an existing directory

    On a WinCC Unified Comfort or Basic panel, the USB device in the X61 port mounts under /media/simatic/X61, and WriteFile and ReadFile require every folder in the target path to already exist — create it on the stick or with CreateDirectory before the first write. When the file contents prove correct but the expected read/write success message never appears, the transfer has succeeded and only the feedback path is faulty.

    HMI and touchscreens

  • Troubleshooting

    Why a WinCC Unified alarm row stays after it clears

    A Program_Alarm row that survives its condition has left the incoming state but still waits for acknowledgment, or the alarm control is showing a history or unfiltered list instead of active alarms. Read the SIG tag online, then the row's state and acknowledgment columns. Fix it by acknowledging the outgoing row or filtering the alarm control to the active alarm list, and change the alarm class's acknowledgment requirement only when the process allows it.

    HMI and touchscreens

  • Explainer

    Why clearing Zoom allow does not stop WinCC Unified panning

    In WinCC Unified PC Runtime V20, a screen that does not fit its screen window always stays pannable, and the Zoom - allow property controls only Unified's own zoom. Clearing it at design time or from the screen's load event leaves the geometry untouched, so a script-cropped window cannot hide privileged settings. Keep each restricted screen small enough to fit and load privileged settings only after the privilege check passes.

    HMI and touchscreens

How to Build a Drop-Down Product List in Crimson 3