How-to
Adding operator screens in WinCC flexible 2007 for an MP270
Short answer
Open the integrated STEP 7 V5.4 project in WinCC flexible 2007 and confirm the MP270 is the configured target, then add the screen in the screen list and bind every dynamic object to a tag that rides the same PLC connection your working tags use. Wire navigation in and out, compile clean, transfer, and prove the screen on live values before it runs the machine.

On this page
- What are the steps to add screens in WinCC flexible 2007 for the MP270?
- How do I open the MP270 project from STEP 7 V5.4 in WinCC flexible 2007?
- How do I add a new screen in WinCC flexible 2007?
- How do I bind the new screen objects to PLC tags?
- How do I make the new screen reachable from the existing screens?
- How do I compile and transfer the project to the MP270?
- How do I test the new screens before they run the machine?
- Why does my new screen compile but show no live values?
- Questions asked
You already know the trick from ProTool: a screen only earns its place when every value on it has a path back to the PLC. WinCC flexible 2007 works the same way, and your project is already set up for it — the same STEP 7 V5.4 project that carries the ProTool configuration also carries a WinCC flexible station for the MP270. Open that station and work there rather than in ProTool, add the screen in the screen list, bind every dynamic object to a tag that rides the connection your working tags already use, wire navigation in and out, compile, transfer. Three checks decide whether a new screen actually runs: the configured target is the MP270, the tags resolve to real controller addresses, and the screen is reachable and escapable. The sections below take those checks in the order you meet them.
What are the steps to add screens in WinCC flexible 2007 for the MP270? #
Ten steps, in this order: open the integrated HMI station, confirm the MP270 target, create the screen, add static labels, create or select tags on the working connection, bind the objects, wire navigation both ways, compile clean, simulate, transfer and prove live values. Each step has its own section below; this list is the shortest path from an open project to a screen an operator can use.
- Open the integrated STEP 7 V5.4 project and start the HMI station it contains in WinCC flexible 2007.
- Confirm the project tree names the MP270 as the configured device.
- Create a new screen in the screen list of the project view and give it a unique, descriptive name.
- Lay out the static text first: screen title, field labels, engineering units.
- Create or select the HMI tags; give each PLC value the same connection the working tags use, with address and data type taken from the controller program.
- Add the dynamic objects — output fields, status indicators, input fields — and bind each one to its tag.
- Add a control on an existing reachable screen that opens the new screen, and a return control on the new screen itself.
- Compile the complete project and clear every reported error.
- Test in simulation for layout, navigation, formatting and internal-tag behavior.
- Transfer to the MP270 and prove live values and permitted writes on the bench.
Steps 1 and 2 are where first attempts in WinCC flexible usually go wrong, so the next section begins there. If you want a guided warm-up first, the vendor documentation includes a getting-started guide for first-time WinCC flexible users; walking its example project once makes the rest of this procedure mechanical.
How do I open the MP270 project from STEP 7 V5.4 in WinCC flexible 2007? #
Start WinCC flexible 2007 from the integrated STEP 7 V5.4 project — open the project and launch the HMI station it contains — and check one thing before you draw anything: the project tree must name the MP270 as the configured device.
Integration coordinates the controller and HMI configuration, but it does not create screens, assign tags or validate navigation for you. A screen can compile cleanly while showing nothing but static values, because its objects reference internal tags, incomplete addresses or the wrong connection.
If the tree shows any device other than the MP270, stop: screen dimensions, supported objects and runtime behavior all follow the configured target, and screens drawn for another panel are rework at best. And because the same STEP 7 project is integrated to both tools, do this whole job in the WinCC flexible station — an edit session split between ProTool and WinCC flexible is how a finished screen never reaches the panel.
How do I add a new screen in WinCC flexible 2007? #
Create the screen in the screen list of the project view and give it a name that says what the operator does there — for example Charge_line_2_status — then open one existing production screen and copy its structure before you draw anything new.
The production screen is the house style: its object set, its tag conventions and its navigation events are what this panel's operators already know, and its tags sit on the addressing pattern the controller program expects. Reuse that structure and the new screen feels familiar on the first touch.
Add only the objects the operator's task on that screen requires. Static text needs no tag; every output field, status indicator and input field does, and the binding rules are the next section. If one of the new screens has to show an analog trend curve, treat that as its own job — the MP270 analog trend curve setup in ProTool and WinCC flexible has steps a plain screen does not.
How do I bind the new screen objects to PLC tags? #
Every dynamic object needs a tag, and every PLC-backed tag needs three things to match: the connection your working tags already use, the controller address taken from the PLC program or its symbol table, and the data type of that controller variable.
Check the tag source first: a process value must use the configured PLC connection, not an internal tag — an internal tag compiles, displays and never touches the controller. Check the address and data type next, because a mismatch shows up as wrong scaling, rejected operator input or a value that appears frozen. Decide the write intent while you are there: indicators read, and an operator entry field needs a writable destination plus whatever access level the process design requires at that station.
Two failures have their own fixes: if the controller program changed and the tag lists stop resolving, that is symbol synchronization, covered by Why STEP 7 symbols are missing in WinCC Flexible tag lists; if the editor rejects a bit-level address as invalid, work through Fixing invalid bit address errors when adding HMI tags.
How do I make the new screen reachable from the existing screens? #
Put a screen-change control on a screen the operator can already reach, aiming it at the new screen by name, and put a return control on the new screen itself — a screen with no way in never shows, and one with no way out traps the operator.
Use the navigation pattern a working screen already has: open it, see what its screen-change control calls, copy that control onto the parent of your new screen and swap the target. That keeps the operator's habits intact and avoids inventing a second navigation scheme on one panel. Check visibility while you are there — a control covered by another object, or visible only under a condition nobody remembers, is a control nobody can press.
If the change should come from the controller instead of an operator tap, the PLC can request the screen itself; How to Change WinCC Flexible Screens From the PLC shows that mechanism.
How do I compile and transfer the project to the MP270? #
Compile the complete HMI project first and do not transfer until the compiler reports no errors — unresolved tags, missing references and configuration errors all stop here — then send the compiled project to the MP270 over the transfer route your existing project updates already use.
Fix compiler output in this order: unresolved tags first, broken references next, configuration errors last — each class of error hides the ones behind it, and the compiler only reports what it can see. When the compiler is clean, transfer, and confirm the panel is ready to receive it the way your last successful update went in.
How do I test the new screens before they run the machine? #
Simulate first, then prove it live: simulation on the engineering PC checks layout, navigation, formatting and internal-tag behavior, and only a live check — a PLC test value changing on the panel, a controlled write landing in the controller — proves the signal path.
Put three observations on the bench before the screen earns operator trust:
- Reachability: the control on the parent screen opens the new screen, and the return control restores the screen it is defined to restore.
- Live indication: change a permitted PLC test value by the normal engineering method and watch the MP270 follow it in the same engineering format.
- Operator write: where writing is intended and authorized, enter a controlled test value and confirm the PLC variable receives it.
Run the write test against a bench panel or a value the process can spare — a test write to a live machine is a machine command, not a screen test. Simulation follows the simulator configuration, so it proves layout, navigation and formatting but cannot prove the physical path between panel and controller. When the screens pass, keep a record with the Project > Print project documentation... command so the as-built screens exist on paper as well as on the panel.
Why does my new screen compile but show no live values? #
In practice the object is bound to an internal tag or the wrong connection, so the screen is a valid edit that never touches the controller — put a working tag's connection, address and data type beside the new tag, and whatever differs is the fault.
Work the layers from the object inward:
- Object to tag: no tag bound, or an internal tag bound — the field shows a fixed value and ignores the process.
- Tag to connection: the tag rides a different connection than the working tags, or carries a wrong address or data type — the field freezes or scales wrong.
- Connection to controller: every screen on the panel stops updating, including the old ones — the fault is the link, not your screen.
The decision falls out cleanly: if only the new tags fail, correct the tag definitions and leave the graphics alone; if nothing on the panel updates, diagnose the panel-to-controller connection before touching screen or tags. A correction on the engineering PC does nothing at the machine until it is compiled and transferred again.
Questions asked
Can an MP270 share its live values with another system while the screens run?
Yes. The Multi Panels of the 270 series can optionally act as OPC XML DA servers, so a separate PC application can read panel tags over that interface while the MP270 keeps running its own screens. Configure it as a separate function of the panel; it does not replace the PLC connection that feeds your screens.
Will WinCC flexible 2007 open a project saved in a newer WinCC flexible version?
No. A project saved by a newer editor carries data the 2007 editor cannot read, so it will not open properly. Keep the project in the version that matches your panel work, and only move a project forward when you are ready to stay on the newer editor for that machine.
I work in ProTool every day — how different is WinCC flexible?
The thinking transfers directly: a screen holds objects, each object reads or writes a tag, and each tag points at a controller address through a connection. What differs is the editor layout — WinCC flexible organizes screens, tags and connections in one project view, and you compile and transfer from that same view before anything reaches the panel.
How long can I keep adding screens to an MP270 before the panel becomes the limit?
The workflow in this article does not age: as long as the MP270 boots, transfers reliably and responds to touch, new screens behave like the old ones. When the touch drifts, the backlight dims or a transfer keeps failing, the panel is the problem — replace it with a current industrial touchscreen panel and migrate the project rather than stacking repairs.