IMDTouchKnowledge BaseShop main store

How-to

Backing up a KTP600 Basic Mono PN with ProSave over Ethernet

HMI and touchscreens Published 5 min read

Short answer

The KTP600 Basic Mono PN has no memory card slot, so its only backup route is a SIMATIC ProSave image pulled over the panel's PROFINET interface from a service PC on the same subnet, with the panel switched to transfer mode. The result is a recovery image, not the editable TIA Portal project, so store the engineering archive separately.

On this page
  1. The backup you get and the one you do not
  2. Prepare the PC and confirm the panel identity
  3. Put the service PC on the panel's subnet
  4. Switch the panel to transfer mode
  5. Run the backup in ProSave
  6. Verify, label and store the image
  7. The decision
  8. Questions asked

The KTP600 Basic Mono PN has no slot for a memory card, so there is no card-based backup or card transfer for it. The one documented route is a SIMATIC ProSave backup pulled over the panel's PROFINET interface from a service PC on the same subnet, with the panel switched to transfer mode. The file you get is a recovery image of the panel, not the editable TIA Portal project, so the engineering archive has to be stored separately. The steps below cover the whole job: identity, subnet, transfer mode, the backup run and the acceptance check.

The backup you get and the one you do not #

ProSave reads the panel's data through its service functions and writes an image file to the PC. Restoring that image returns the panel to the state it was in when you captured it, application included. It does not contain editable screens, tags and connections as engineering source, and it cannot be opened in TIA Portal to change anything. Keep two artifacts for this machine: the ProSave image for panel recovery, and the compiled project archive from TIA Portal for every future change. Checking that the archive side is really captured is covered in verifying HMI project data is inside your platform backup.

Because there is no card slot, the route in transferring an HMI project with a USB drive or SD card does not apply here either; every transfer to and from this panel runs over its PROFINET connection.

Prepare the PC and confirm the panel identity #

  • Get ProSave from Siemens; it installs with TIA Portal and can also be started as its own program. The panel type must appear in ProSave's device selection list; if it does not, update ProSave from a newer TIA Portal release before going further.
  • Read the nameplate on the back of the panel and record the full designation and the order number (MLFB). Mono and Color variants, and PN and DP variants, are different devices in the selection list, and picking a look-alike is the most common way a backup or restore goes wrong.
  • Open the panel's control panel and record its configured IP address and subnet mask. You will enter that address in ProSave, so write it down rather than working from memory.

Put the service PC on the panel's subnet #

The service PC needs an address the panel can answer on the same network. The subnet mask decides which addresses an interface treats as local, so the two must share a subnet. Note that a working HMI-to-PLC connection proves nothing about the service PC's path: the PC may use a different adapter, sit on another subnet, or be filtered by its own firewall.

Worked example. Suppose the panel's control panel shows 192.168.1.10 with mask 255.255.255.0, and you give the service PC 192.168.1.50 with the same mask. Check it with the mask: 192.168.1.10 AND 255.255.255.0 gives 192.168.1.0, and 192.168.1.50 AND 255.255.255.0 also gives 192.168.1.0. Both hosts sit on the 192.168.1.0 network, so a direct cable or the local switch works and no router is involved. Before opening ProSave, ping the panel address from the PC; if the ping fails, fix the physical link, the adapter selection or the PC firewall first, one change at a time.

Switch the panel to transfer mode #

On the panel, open the transfer settings in its control panel and enable transfer over the Ethernet interface; the panel then boots into transfer mode at the next restart. Do not trust a screenshot from another HMI family for the exact menus: Comfort panels, for example, reach the same state through Settings > Transfer in their Center dialog, as described in backing up a TP 1500 Comfort panel to a PC, and the Basic panels differ from that.

While the panel is in transfer mode its operator screens are unavailable, even though the PLC program keeps executing. Schedule the job for a window in which the machine does not depend on panel visibility or operator input, and plan the restart back to runtime as part of the same job.

Run the backup in ProSave #

  1. Start ProSave on the service PC.
  2. In the device selection, choose exactly the panel type recorded from the nameplate.
  3. Select Ethernet as the connection type and enter the panel's IP address.
  4. Click the Backup button; the "SIMATIC ProSave [ Backup ]" dialog opens.
  5. In the "Save as" field, enter a filename that names the machine and the capture date, for example line3_ktp600_2025-06-12.psb.
  6. Click Start and keep panel power and the network cable undisturbed until the run ends.
  7. Wait for ProSave's explicit completion message before touching anything.

Verify, label and store the image #

A file appearing in the destination folder is not proof of anything; the acceptance criterion is ProSave reporting successful completion for the selected device. Keep with the file: the full designation, the order number, the panel's IP settings, the capture date and the ProSave version used, so a future restore or replacement has everything it needs without the original panel.

Store a protected second copy under your site's backup policy. Do not test-restore onto the running production panel just to check the file: a restore writes panel data and replaces the installed application. Use an approved compatible spare, and follow the same tool's restore procedure covered in restoring a KTP400 Basic .psb backup with ProSave. ProSave is also the tool for OS updates and for keeping panel image files, the same workflow described for an older mono panel's image file location and OS update via ProSave.

The decision #

  • The panel has no memory card slot: a ProSave backup over the PROFINET connection is the only route, and transfer mode with a ping-verified service PC is what makes it work.
  • You need to change screens, tags or connections: get the TIA Portal project archive; the ProSave image will never give you editable source.
  • The panel is being replaced: restore the image only to the same device designation, or reload the project from the archive onto the new panel and re-enter the IP settings you recorded.

Questions asked

Does the ProSave image contain my recipes and alarm logs?

The image captures what the backup dialog offers for the selected device; anything the dialog does not list is not in it. If a category such as recipe data matters for your process, confirm it is included in the scope you select, or export it through its own documented function before the panel leaves service. Note the chosen scope alongside the file so a future restore is not a guess.

ProSave finds the panel but the backup fails to start. What do I check first?

Confirm the panel was actually restarted into transfer mode after you enabled transfers, not just left running with the setting changed. Then ping the panel address from the service PC, and confirm ProSave holds the exact device type and the panel address you recorded. Change one setting per attempt and note the diagnostic ProSave reports, so each retry tests a specific cause.

Can I restore this image onto a replacement panel of a different type?

No. Restore the image only to a panel with the same designation as the one it came from; a same-size Color or DP variant is a different device and must not receive it. Write the full designation and order number into the file record at backup time so the matching spare can be ordered and verified years later. For a different device type, load the project from the TIA Portal archive instead.

Can I take the backup while the panel keeps running its screens?

Not on this panel. Transfers must be enabled in its settings and the panel restarted into transfer mode before ProSave can connect, and in that state the operator screens are unavailable. The PLC program keeps running throughout, so pick a window where the machine does not depend on panel visibility or control, and plan the restart back to runtime as part of the same job.

Keep reading

  • How-to

    Connecting a LOGO! 0BA8 to an MT8050iE HMI over Ethernet

    Yes, a LOGO! 0BA8 connects to a Weintek MT8050iE over Ethernet using the Siemens LOGO! (Ethernet) driver in EasyBuilder Pro, with both devices on the same subnet and a server-side Ethernet connection defined in the LOGO! project; prove the link with one read tag, then add writes only after that read follows a value you change in the controller.

    HMI and touchscreens

  • Explainer

    Why a KTP600 Basic DP needs a PC Adapter USB A2 for transfer

    A KTP600 Basic Color DP has no Ethernet port, so its project cannot be loaded through the S7-1200's Ethernet connection: the CM 1243-5 is a DP master for process data, not an engineering gateway. The documented path is a PC Adapter USB A2 (6GK1 571-0BA00-0XA0) on the panel's PROFIBUS socket, with transfer channel, baud rate and station addresses matched. The USB/PPI Multi-Master Cable is a different adapter for the S7-200 world.

    HMI and touchscreens

  • How-to

    Exchanging HMI memory data with a custom PC application

    Yes. The panel is the master and the PC program is the endpoint it polls: set the HMI project to Memory Link, then implement that command set, addressing and framing so every read and write the screen sends gets a valid answer. The exact model's communication manual supplies the frame format and memory areas; nothing else should be guessed.

    HMI and touchscreens