Selection guide
Choosing a Legacy HMI Replacement for a Machine Fleet
Short answer
Qualify one pilot machine before touching the other 19. Record the CJ controller and its connection, inventory every function the old application performs, confirm the candidate's documented CJ driver over FINS Ethernet or serial, then pass a read test, one controlled write test and a full function baseline before fleet rollout.
On this page
- What do you record about the existing fleet before shortlisting anything?
- Which connection does a CJ fleet standardize on?
- Which candidates earn a place on the shortlist?
- Will the replacement fit the existing panel opening?
- What must the pilot machine prove before the fleet commits?
- Example: how long does the rollout take once the pilot passes?
- When does a candidate get dropped?
- Questions asked
The gate is a driver sheet, not an Ethernet port: a replacement qualifies only when its documentation names a native CJ driver over FINS Ethernet or serial — FINS/UDP or FINS/TCP on port 9600 by default — reaching the W, H and D memory areas the old screens use, addressed by network, node and unit. For a fleet of roughly 20 legacy panels on Omron CJ controllers, you prove that gate on one pilot machine — a CJ2M with its ETN21 Ethernet option unit, for example — before touching the other 19. The pilot must reproduce every function the old application performs — displays, alarms, recipes, access levels and command behavior — passing a read test, exactly one controlled write and a full baseline run, not merely display live values. Record each machine's CPU, communications hardware and operator functions first, shortlist only panels whose driver sheets name that exact hardware, then order for the fleet.
What do you record about the existing fleet before shortlisting anything? #
Record the controller identity, the exact connection and every operator function the old application performs before any vendor name goes on the shortlist; that inventory selects the pilot machine, and the rest of the fleet inherits the pilot's results only after the full gate passes.
Start with a per-machine record read from the running equipment, not the drawings: the exact CPU identification — a CJ2M, for example, with its option cards — and the communications hardware the old panel actually uses, which is either the Ethernet option unit (an ETN21, for example) or the serial port and its configured mode. Group the fleet by that record. Machines with the same CPU and connection inherit each other's test results, and every different combination repeats them.
Preserve the old application before anything is unplugged: the NS project, the PLC project and the communications settings, with the files verified against the running machine; reading an old HMI program before panel replacement walks through that recovery. Then write the function baseline from the running system, not from memory: every screen an operator actually opens, every command that writes to the controller, alarm behavior including acknowledgement, recipes, trends, access levels, languages and any maintenance screens in use. Mark each item read-only or write — the write items decide the controlled-write test later. Choose the pilot from the most common CPU-and-connection combination, so one qualification covers the largest share of the fleet.
Which connection does a CJ fleet standardize on? #
Standardize on Ethernet with the vendor's documented FINS driver, and accept serial only where a machine has no Ethernet path; FINS runs over UDP or TCP on port 9600 by default and addresses the controller by network, node and unit, so the driver setup must document all three.
FINS is Omron's request-and-response protocol across its CS, CJ and CP controller families. Over Ethernet it rides UDP — FINS/UDP — or TCP, with the port set identically at the panel and the controller, and the connection names the network, node and unit addresses of both ends. That is what a claim of Omron support has to mean on a datasheet: a driver entry for CJ over FINS Ethernet, not an Ethernet connector.
Check two more driver properties before a pilot order. First, memory coverage: the driver must reach the work, holding and data memory areas the baseline uses — W, H and D — or part of the old screens will not map at all. Second, transport type: some drivers reach Omron controllers through EtherNet/IP rather than FINS, and CIP-based access depends on 'CIP multiservice' support in the controller — present on the NJ series but not on every CJ — which is why two Ethernet panels can behave differently on one CPU.
Serial stays acceptable for a machine with no Ethernet path, and it succeeds or fails on the whole link: electrical interface, cable pinout, port mode, station number and baud all match the driver sheet or nothing comes online. Connecting an HMI to a controller over a serial COM port covers that setup. When a CJ serial link still refuses to come online, fixing an Omron CJ1M serial connection that will not go online lists the usual causes in order. The fleet decision: FINS Ethernet where the hardware has it, a proven serial link where it does not, and never a transport the driver sheet does not name.
Which candidates earn a place on the shortlist? #
Put a candidate on the shortlist only when its published driver list names the installed CJ hardware and its engineering tool covers every baseline function; a name mentioned in field reports, including the NA5 and Red Lion routes, is a starting point to verify, never a qualification.
Every name below arrived as a field recommendation for this exact job, which makes each one a hypothesis; the driver sheet and the pilot are what turn it into a result.
| Candidate route | Why it is on the list | What the driver sheet must show before a pilot order |
|---|---|---|
| Omron NA5 | Same manufacturer as the CJ controllers; named in field reports for CJ connectivity | A CJ driver for the installed CPU and Ethernet unit, the documented path for the old NS project, and the engineering tool with its licensing |
| Red Lion panels, configured in Crimson | Named in field reports for Omron PLC connections with native drivers | A Crimson driver entry that names CJ explicitly, with the FINS Ethernet or serial transport and the memory areas the baseline uses |
| Pro-face / QuickPanel mention | A family-name pairing that circulates for Omron connectivity | The mention resolved to one manufacturer, family and model, then that model's own driver sheet |
| Maple Systems | Field reports describe working installations on Omron C-series controllers | A driver entry for CJ specifically — C-series operation is not CJ evidence |
The engineering tool is a separate check from the driver: the tool that builds the new application has to produce every baseline function — recipes, alarm history, access levels, multi-language text where used — and its support for the chosen panel gets confirmed before anything is ordered, exactly as in checking HMI engineering software before a panel replacement. A PC-based HMI runtime on an industrial computer is a parallel route through the same gate — a documented CJ driver and a licensed runtime matched to the host — but it changes the maintenance model, so treat it as a fleet-wide decision rather than a per-machine fix.
Will the replacement fit the existing panel opening? #
Measure the old panel's cut-out, the depth behind the door and the cable approach, then compare them with the candidate's published mounting drawing before the pilot order; a panel that qualifies electrically but misses the opening by 10 mm becomes a door or fascia change.
Record, per machine: opening width and height, panel thickness, clear depth behind the door to the first obstruction, the connector approach on the candidate's rear face, and the supply arrangement at the old panel. A swap that must land in the existing opening is dimension-matched first — compare the old and new mounting drawings against a panel cut-out reference before anything is ordered. The check is pass or fail. A candidate with an unresolved envelope mismatch leaves the list, because an adapter plate or a door change becomes a per-machine job that scales with every conversion week. A machine in a washdown or outdoor location adds one requirement: the candidate's rating documentation must cover that location as installed, which is a datasheet check, not an assumption.
What must the pilot machine prove before the fleet commits? #
The pilot passes only after a read test on live values, exactly one controlled write to a non-hazardous test address, and a full run of every baseline function that matches the old panel's behavior on two consecutive trials; anything less is not a qualification.
Build the pilot application from the baseline list, and expect that build to be a rebuild or a documented import rather than a file copy; the options and their traps are covered in importing legacy HMI screens when migrating to a new panel.
Run the read test first, with the controller online. Pick a discrete state and a numeric value the PLC program makes meaningful, then compare the panel display against the controller's own monitor of the same address, checking each mapping item: memory area and address, data width and signedness, decimal and scaling position, word order on 32-bit values, and bit selection within a word. When a displayed value disagrees, the fault is the driver, the tag or the binding, and diagnosing that split is its own short procedure.
Then authorize exactly one controlled write, to a non-hazardous test address nothing in the running process depends on — keep the machine in a state where an unexpected output cannot move anything while that write is live. Verify the destination, the value and the persistence directly in the PLC. Exercise command behavior next: momentary and maintained buttons, what happens at a screen change, and what happens when communications drop — a command must not stay active because the panel stopped talking, and stale data must be visibly distinct from live data.
Finish with the baseline itself: alarms including acknowledgement, recipe load and save, access levels, trends — every item on the list, run from power-up. Pass means two consecutive clean runs. Freeze the pilot project as the fleet template and record the driver version, panel firmware and connection settings that passed.
Example: how long does the rollout take once the pilot passes? #
With a three-week pilot and a two-machine-per-week conversion rate after it, a 20-machine fleet finishes in 13 weeks: the pilot occupies weeks 1 to 3, and the remaining 19 machines need 19 divided by 2, rounded up to 10 more weeks.
The arithmetic: 20 machines − 1 pilot = 19 conversions; 19 ÷ 2 per week = 9.5, rounded up to 10 conversion weeks; 3 pilot weeks + 10 conversion weeks = 13 weeks from kickoff to the last machine.
Each assumption moves that answer. The conversion rate assumes one trained pair, a planned downtime window per machine and a single baseline-run sign-off; a failed post-swap run holds that machine's slot until it is resolved; and every additional connection variant adds its own repeat of the read and write gates before its machines convert. Per machine the conversion is mechanical by then: load the frozen template, apply the machine-specific addressing from the inventory, run the baseline once, sign the sheet. Order pilot-verified spares before the conversion weeks start, so a dead panel during rollout is a swap from the shelf, not a new selection.
When does a candidate get dropped? #
Drop a candidate the moment its documentation cannot name the installed CPU and Ethernet unit combination, because a driver written for one CJ generation is not a driver for every CJ; dropping costs only a shortlist line, while a wrong pilot order costs a season of rollout time.
Drop a route when any of these is true:
- The driver sheet names the controller family but not the installed CPU and Ethernet unit combination.
- The engineering tool cannot produce a baseline function — no recipe equivalent, no alarm history, no access levels.
- The CJ evidence offered is behavior on C-series or NJ controllers.
- A machine without an Ethernet path cannot get documented serial settings for the CJ port.
- No connection example exists for the exact CPU, transport and memory areas the baseline uses.
Run that list before the pilot order, with the same discipline as verifying an obsolete HMI replacement before ordering. The decision rule for the fleet: no documented driver for the installed hardware, no pilot; no clean pilot, no fleet order. The purchase goes to the panel that cleared the pilot with zero unresolved baseline items and a frozen template. A second source can exist, but it repeats the same gate on its own hardware before a single machine receives its panel.
Questions asked
Should every machine in the fleet get the same panel model?
One model keeps spares, screens and operator training identical, so the shortlist should favor a panel whose driver covers every CPU and connection variant found in the inventory. If a machine turns out to need a second model, it repeats the full pilot gate on its own; pilot results never transfer between different hardware.
Does replacing the panels commit us to replacing the controllers too?
No. The selection is made against the controllers you have: the replacement's driver must serve the installed CPUs as they are, and the pilot proves exactly that. A later controller upgrade is a separate project with its own driver and baseline checks; folding the two into one rollout doubles what the pilot must prove.
How long do pilot results stay valid for machines converted later?
They hold for any machine whose CPU model, communications hardware and firmware match the pilot. Before each conversion, compare the machine's identification against the pilot record; if the CPU, the Ethernet unit or the serial port setup differs, that machine repeats the read test, the controlled write and the baseline run before it counts as converted.
What happens to the retired panels and the old programming setup?
Keep one retired panel and the old engineering laptop as a labeled bridge set until the last machine converts, with its power supply and cables. Store the old project archives with them. The set exists only for recovery if a machine must run before its conversion window; it is not a development platform.