How to Verify an Obsolete HMI Replacement Before Ordering
Short answer
Read the full part number off the installed panel's nameplate before you order anything: the family prefix decides the successor, the cutout drawing decides whether the opening must grow, and the software version decides whether the old project loads. For an obsolete 6-inch IC754 QuickPanel the reported path is the IC755 QuickPanel+ color TFT, which needs a larger cutout and Proficy Machine Edition 8.60 with the latest SIM.
On this page
The number that decides the order is the one on the installed panel's nameplate, not the one in the request email. Transcribe the complete part number — family prefix, size digits, options and the trailing suffix — and gate the order on three checks: the nameplate family matches the published replacement path, the replacement's cutout drawing fits your opening, and your programming software loads the old project. On a 6-inch QuickPanel migration both gates bite: the successor recommended for obsolete IC754 panels, the IC755CSS06RDA QuickPanel+ 6-inch color TFT with resistive touch, needs a larger panel opening than the unit it replaces and a newer Proficy Machine Edition before the old project reloads. Cut the opening or convert the project before those checks pass, and a two-day swap becomes a two-week outage.
Read the nameplate before you trust the request #
Job requests usually carry a truncated string. IC745CGL06MTD-EF parses like this: the catalog ties IC745CGL06MTD to a 6-inch mono/TFT QuickPanel View & Control, and the -EF suffix marks the hardware/firmware version the unit carries — a revision marker, not an option you may drop from the record. The replacement recommendation that circulates for this generation — obsolete IC754 QuickPanels replaced by a QuickPanel+ 6-inch color TFT with resistive touch — is tied to the IC754 family, and the prefix on your door decides whether it applies to your machine. If the swap is part of a bigger replacement project, the selection work is covered in planning an HMI terminal replacement from an older operator panel; the checks below are the gate in front of the order.
Same screen size is not a family match. The 6-inch IC754VSI06STD is a color touchscreen unit documented with RS-232 and RS-485 ports on a 12–30 VDC supply; the IC745CGL06MTD is an earlier family string with a mono/TFT display. Photograph the nameplate, transcribe every character, and make the family prefix the first line of the migration file.
The verification steps, in order #
- Record the full identity. Photograph the nameplate and transcribe the complete part number, suffix included. The suffix is the hardware/firmware revision; quote the whole string whenever you ask about compatibility.
- Match the family, not the diagonal. Set the nameplate prefix against the replacement path before any other check moves.
- Compare cutout dimensions. Measure the existing opening and hold it against the replacement's published cutout drawing for the exact suffix; the panel cut-out reference exists for exactly this comparison.
- Prove the software floor. Open the project in the installed Proficy Machine Edition and retarget it to the replacement model; what a missing target means is covered in the software gate below.
- Back everything up before anything changes. Save the project and record the software version and SIM level you convert under. If no project file survives, recovering the program from the old panel before it powers down for the last time is the fallback, covered in uploading a program from an old touchscreen HMI.
- Order, then cut. Order against the exact current data-sheet string — for the 6-inch QuickPanel+ with View and Control, the data sheet lists IC755CBS06RDA and the blank-bezel IC755CSS06RDACA — and enlarge the opening only when the replacement is in hand and its drawing matches the measured opening. De-energize the cabinet and cover the electronics before cutting; swarf across a live backplane ends more migrations than wrong part numbers do. If the order slips after the opening is already enlarged, close it with NEMA-rated blank covers so the door keeps its rating.
- Commission and prove. Download the converted project, run the panel, and exercise every screen and control path to the controller; check live values at both ends of the link before the machine goes back to production.
Why the same six inches needs a bigger hole #
The old 6-inch QuickPanel View/Control display is documented at 320 × 240 pixels — a 4:3 face on a six-inch diagonal (hardware guide GFK-2305). The QuickPanel+ generation went widescreen; its operator interface manual describes widescreen multi-touch screens (GFK-2847). Same diagonal, different proportions, wider glass. Taking the widescreen face as 16:9 for the arithmetic:
- 4:3 at a 6 in diagonal: the 3-4-5 triangle gives width = 6 × 4/5 = 4.8 in and height = 6 × 3/5 = 3.6 in.
- 16:9 at the same diagonal: the diagonal factor is √(16² + 9²) = √337 ≈ 18.36, so width = 6 × 16 / 18.36 ≈ 5.23 in and height = 6 × 9 / 18.36 ≈ 2.94 in.
The widescreen glass alone comes out about 0.43 in wider and 0.66 in shorter than the face the old opening was cut for, before any bezel difference. An opening sized to a 4.8-in face plus the old bezel will not accept a 5.23-in face plus a new one, so 6-inch replaces 6-inch fails at the first measurement. Enlarge to the replacement's own drawing, never to the diagonal on the order.
The software gate on the migration #
Plan on Proficy Machine Edition 8.60 or later with the latest SIM installed; that is the version floor reported for this IC754-to-QuickPanel+ migration, and the old project reloads onto the new panel once the software meets it. The retarget in step 4 is the proof: the project converts and the new model appears as a valid target, and the floor is met. If the new model is missing from the programming software's model list instead, the installed version is behind — that symptom and its fix are covered in when an HMI model is missing from the programming software. Record the version and SIM level you converted under in the migration file, because the next panel swap starts from that record.
The decision for each nameplate #
- IC754 6-inch on the nameplate: the published path applies. Order the QuickPanel+ 6-inch color TFT — IC755CSS06RDA is the string the recommendation carries — budget the larger opening from its cutout drawing, and bring Proficy Machine Edition to 8.60 with the latest SIM before converting. The old project reloads.
- IC745CGL06MTD-EF on the nameplate: the handed-down recommendation is tied to the IC754 family and is not established for this string. Quote the complete nameplate, suffix included, to the supplier, and hold both the order and the saw until the successor is confirmed in writing.
- Same base number, different suffix: same family, different revision. Quote the full string and let the supplier match the revision.
Questions asked
What does the -EF suffix on IC745CGL06MTD-EF mean?
It marks the hardware and firmware revision the installed unit carries, not an ordering option. Panels sharing a base part number can sit at different revisions, so keep the suffix in the migration file and quote the complete string whenever you ask a supplier about compatibility.
Can the old QuickPanel project be reused on the QuickPanel+ replacement?
Yes, along the migration path: once the programming software meets the version floor, the old project reloads onto the new panel. The QuickPanel+ manual also documents the Copy Project to SD Card utility, which moves View and Control projects between compatible QuickPanel+ units, so a configured panel can seed the next identical machine.
How do I confirm which Proficy Machine Edition version is installed?
The software's own version or about information shows the installed release; a SIM appears alongside it only when one has been installed, so if none is shown, treat it as absent. Compare what it shows against the 8.60 floor before you plan the project conversion, and record the result in the migration file.
Does a 6-inch replacement really need a bigger opening than a 6-inch panel?
When the generations differ, usually yes. The old 6-inch face is 4:3, about 4.8 in wide at a 6-inch diagonal, and a widescreen face at the same diagonal is about 5.2 in wide before bezels. The face is also shorter, so the mounting holes land in different places. Take opening dimensions from the replacement's cutout drawing, never from the diagonal size on the order.
The client's part number and the nameplate disagree. Which one orders the replacement?
The nameplate does. Request strings often come from catalogs or job files and can carry a different family prefix than the unit on the door. Transcribe the nameplate, send the client the exact string you found, and order only against the installed unit's full part number with its suffix.