Selection guide

Choosing an HMI for an RMC75E Motion Controller

HMI and touchscreens Published 6 min read

Short answer

Buy a panel that supports Modbus/TCP, CSP (DF1 over Ethernet) or EtherNet/IP and handles 32-bit floating-point values in every project function. AutomationDirect C-more suits simple two-axis stations; Red Lion G3 adds programming and advanced features at higher hardware cost with free software. Prove any other panel with a 25.4 mm float round-trip before purchase.

On this page
  1. The two gates every RMC75E panel must clear
  2. Why 32-bit float support fails quietly
  3. Panels with ready example projects
  4. Match the panel to the two-axis job
  5. Bench test: two axes, one RMC75E, Modbus/TCP
  6. The decision for each case
  7. Questions asked

Two gates decide this purchase, and neither is screen size. The panel must support at least one of the RMC75E's documented HMI protocols — Modbus/TCP, CSP (DF1 over Ethernet) or EtherNet/IP — and it must handle 32-bit floating-point values in every project function, not only numeric displays. Two panel families clear both gates with ready example projects: AutomationDirect C-more for a simple two-axis station, Red Lion G3 when you need programming and advanced features and accept higher hardware cost against free software. Any other panel earns a purchase order only after a bench round-trip test on floats.

The two gates every RMC75E panel must clear #

The RMC75E is an Ethernet motion controller. Its axis data — positions, velocities, command values — lives in 32-bit floating-point registers, and its Ethernet port documents several application protocols. Three of them are the ones HMI selection turns on; the remainder of the controller's documented list, including PROFINET and Omron FINS, addresses PLC-side links.

Gate What must be true How the gate fails
Protocol The panel's documented driver list includes Modbus/TCP, CSP (DF1 over Ethernet) or EtherNet/IP The datasheet says "Ethernet" but names no driver for any of the three
Data type 32-bit float works on every object the project uses: entry keypad, display, trend, bar graph, alarm comparator, script Float works on displays only; entry and alarm objects still run on 16-bit integers
Register map RMC registers are reachable by address, or an example project supplies the map The map has to be reverse-engineered before the first screen works

Modbus/TCP is the default when a panel offers all three, and the reasoning is the same as in selecting a Modbus TCP HMI panel for an existing controller: driver first, register map second, connection count third.

Why 32-bit float support fails quietly #

A panel can display a float and still fail the project. Partial implementations put floating-point support on read-only display objects while keypads, alarm limits, trends and scripts stay 16-bit integer. The failure shows up late: the main screen looks right, then an operator types a fractional setpoint and the controller receives a truncated or raw-register number instead.

Over Modbus, those 32 bits travel as two consecutive 16-bit registers, and word order is a second, separate failure from float support. The word-order rules are the same as in displaying a PLC real value over Modbus on an HMI. Do not plan an integer-scaling workaround either way: the controller's data is floating-point end to end, and scaling at both ends costs resolution and adds an error nobody will find at 2 a.m.

Panels with ready example projects #

Delta Motion's downloads page holds example projects for two panel families under its RMC70 examples category, already configured to communicate with an RMC. That removes the register-map gate entirely, which is why these two are the low-risk choices.

Candidate Why it fits Tradeoff Best fit
AutomationDirect C-more Easy to learn and use; inexpensive; example project available Aimed at simpler interfaces Jog, tune and monitor two axes
Red Lion G3 series Programming and advanced features; example project available; software is free Hardware costs more than C-more Recipes, data logging, math at the panel

When the job outgrows both terminals — historian, complex recipes, third-party drivers — run the HMI runtime on industrial panel PCs instead. That runtime must clear the same two gates, and the bench discipline is the one in how to prove a PC-based HMI before replacing panel terminals.

Match the panel to the two-axis job #

Count what the operator does, not what the panel could do. Two axes mean jog and auto controls, live position readout, a tuning screen and maybe a trend — one station's work for one operator. Screen size follows those tasks, the way how to choose an HMI display size by operator task lays it out, and a compact panel that passes both gates beats a large one that displays floats but cannot enter them.

Bench test: two axes, one RMC75E, Modbus/TCP #

Lock out hydraulic pump power and rest both axes on stops before this test: a write to a command register can stroke a live axis.

Inputs:

  • Controller: one RMC75E, two position axes — the application in question.
  • Link: Modbus/TCP over the controller's Ethernet port, fixed address on both ends (the controller accepts manual, BOOTP or DHCP addressing; use manual or a DHCP reservation).
  • Test value: 25.4 mm, an illustrative position number chosen for this test because its fractional part betrays integer-only objects.
  • Test register: one writable 32-bit floating-point register — a command value or user variable, not read-only axis feedback — taken from the register map in the RMCTools help.

Rule in words: IEEE-754 single precision stores one sign bit, an 8-bit exponent biased by +127, and a 23-bit fraction. Modbus moves those 32 bits as two consecutive 16-bit registers, and the panel driver decides which register carries the high word.

Arithmetic:

  1. Integer part: 25 = 11001₂. Fraction: 0.4 = 0.0110 0110 0110...₂, the pattern repeating. So 25.4 mm = 11001.0110011001100110...₂.
  2. Normalized: 1.10010110011001100110011₂ × 2⁴, sign bit 0.
  3. Exponent field: 4 + 127 = 131 = 10000011₂.
  4. Fraction field, 23 bits: 1001 0110 0110 0110 0110 011.
  5. The 32-bit word: 0100 0001 1100 1011 0011 0011 0011 0011₂ = 0x41CB3333.
  6. The two registers: 0x41CB = 16,843 and 0x3333 = 13,107 as raw 16-bit counts.

Enter 25.4 on the panel's keypad, write it to the test register, and read it back through every object type the project will ship.

Panel shows Diagnosis Action
25.4 Float path and word order correct on that object Object passes
About 4.17 × 10⁻⁸ (shown as 4.17E-08) Words swapped: the pair is read as 0x333341CB Set the tag's word-order property, retest
16,843 and 13,107 The object treats the registers as 16-bit integers That object type fails

The swapped reading follows from the same rule: 0x333341CB has exponent field 01100110₂ = 102, so the scale is 2^(102−127) = 2⁻²⁵ ≈ 2.98 × 10⁻⁸, and the fraction gives 1 + 0.400 = 1.400, so 1.400 × 2.98 × 10⁻⁸ ≈ 4.17 × 10⁻⁸.

Decision: the panel passes when every object type — entry keypad, display, trend, alarm comparator, script — returns 25.4 mm, and the same test on the second axis returns the same result. One failing object type anywhere rejects the panel for this project; a panel that displays floats but cannot enter or compare them is a reject, not a configuration job.

The decision for each case #

  • Two axes, jog and tune, lowest cost: AutomationDirect C-more on Modbus/TCP, built from the example project.
  • Programming, data logging or recipes at the panel: Red Lion G3 — higher hardware cost, free software, same example-project starting point.
  • Any other panel: purchase only after it passes both gates on the bench, on the exact firmware you will ship.
  • Historian or SCADA-class features: a PC HMI runtime on a panel PC, held to the same two gates.

Questions asked

Which of the three protocols should the panel use?

Default to Modbus/TCP: it has the widest panel support, the simplest troubleshooting, and the C-more and G3 example projects are built around it. Pick EtherNet/IP when the site already standardizes on that network and the panel documents a suitable driver, and CSP (DF1 over Ethernet) only when a panel offers neither of the other two.

The panel shows 4.17E-08 where 25.4 mm was written. Is the panel faulty?

Not faulty. The two 16-bit words are swapped: 25.4 mm encodes as 0x41CB3333, and read backwards as 0x333341CB it is a valid float near 4.17E-08. If the driver has a word-order property, set it and the display returns 25.4. If it has none, that driver cannot serve this controller.

Can one panel serve the RMC75E and a PLC on the same network?

Yes, when the panel's driver list covers both controllers and the total connection count stays inside the panel's documented limit. Count the work first: jogging and tuning two axes while viewing PLC status is one station's job when the drivers and ports support the combination.

Can I skip the bench test by starting from the example project?

No. The example project clears the protocol and register-map gates, but your own screens add objects the example never exercised: your alarm limits, your trends, your entry keypads. Run the 25.4 mm round-trip on those before the panel is accepted, because inherited screens and new screens fail differently.

Keep reading

  • Selection guide

    How to Select a Low Cost HMI With EtherNet/IP Support

    A low cost HMI qualifies for an EtherNet/IP job only when its installed driver reads and writes your controller's application variables — for Omron NJ/NX that means tag-name access, because device and address codes cannot be used with NJ/NX tag data. An Ethernet port on the datasheet proves nothing. Qualify the driver on the bench first, then compare screen size and cost.

    HMI and touchscreens

  • Explainer

    Feasibility of connecting an Omron NS5 HMI to a Modicon PLC

    Yes, the link is feasible without Vijeo Designer. The NS5 has no Schneider-named driver, but the Modbus entries under its serial Generic Protocol can poll a Modicon PLC configured as a Modbus server; match roles, framing, speed, parity, station address and cable, and prove it read-only before buying a replacement panel.

    HMI and touchscreens

  • Troubleshooting

    Why an Omron HMI Stays Stuck on Program Initializing

    An Omron operator panel stuck on the initializing text is in one of three states: empty project memory, a failed PLC link, or rear DIP switch 1 left on so a reset enters programming mode. Clear the passive causes first — switch positions, cable continuity, matching port settings — and treat the PLC's own error as a separate fault.

    HMI and touchscreens

Why an HMI button press dies in RUN mode on a shared input