Selection guide
Choosing an HMI for an RMC75E Motion Controller
Short answer
Buy a panel that supports Modbus/TCP, CSP (DF1 over Ethernet) or EtherNet/IP and handles 32-bit floating-point values in every project function. AutomationDirect C-more suits simple two-axis stations; Red Lion G3 adds programming and advanced features at higher hardware cost with free software. Prove any other panel with a 25.4 mm float round-trip before purchase.
On this page
Two gates decide this purchase, and neither is screen size. The panel must support at least one of the RMC75E's documented HMI protocols — Modbus/TCP, CSP (DF1 over Ethernet) or EtherNet/IP — and it must handle 32-bit floating-point values in every project function, not only numeric displays. Two panel families clear both gates with ready example projects: AutomationDirect C-more for a simple two-axis station, Red Lion G3 when you need programming and advanced features and accept higher hardware cost against free software. Any other panel earns a purchase order only after a bench round-trip test on floats.
The two gates every RMC75E panel must clear #
The RMC75E is an Ethernet motion controller. Its axis data — positions, velocities, command values — lives in 32-bit floating-point registers, and its Ethernet port documents several application protocols. Three of them are the ones HMI selection turns on; the remainder of the controller's documented list, including PROFINET and Omron FINS, addresses PLC-side links.
| Gate | What must be true | How the gate fails |
|---|---|---|
| Protocol | The panel's documented driver list includes Modbus/TCP, CSP (DF1 over Ethernet) or EtherNet/IP | The datasheet says "Ethernet" but names no driver for any of the three |
| Data type | 32-bit float works on every object the project uses: entry keypad, display, trend, bar graph, alarm comparator, script | Float works on displays only; entry and alarm objects still run on 16-bit integers |
| Register map | RMC registers are reachable by address, or an example project supplies the map | The map has to be reverse-engineered before the first screen works |
Modbus/TCP is the default when a panel offers all three, and the reasoning is the same as in selecting a Modbus TCP HMI panel for an existing controller: driver first, register map second, connection count third.
Why 32-bit float support fails quietly #
A panel can display a float and still fail the project. Partial implementations put floating-point support on read-only display objects while keypads, alarm limits, trends and scripts stay 16-bit integer. The failure shows up late: the main screen looks right, then an operator types a fractional setpoint and the controller receives a truncated or raw-register number instead.
Over Modbus, those 32 bits travel as two consecutive 16-bit registers, and word order is a second, separate failure from float support. The word-order rules are the same as in displaying a PLC real value over Modbus on an HMI. Do not plan an integer-scaling workaround either way: the controller's data is floating-point end to end, and scaling at both ends costs resolution and adds an error nobody will find at 2 a.m.
Panels with ready example projects #
Delta Motion's downloads page holds example projects for two panel families under its RMC70 examples category, already configured to communicate with an RMC. That removes the register-map gate entirely, which is why these two are the low-risk choices.
| Candidate | Why it fits | Tradeoff | Best fit |
|---|---|---|---|
| AutomationDirect C-more | Easy to learn and use; inexpensive; example project available | Aimed at simpler interfaces | Jog, tune and monitor two axes |
| Red Lion G3 series | Programming and advanced features; example project available; software is free | Hardware costs more than C-more | Recipes, data logging, math at the panel |
When the job outgrows both terminals — historian, complex recipes, third-party drivers — run the HMI runtime on industrial panel PCs instead. That runtime must clear the same two gates, and the bench discipline is the one in how to prove a PC-based HMI before replacing panel terminals.
Match the panel to the two-axis job #
Count what the operator does, not what the panel could do. Two axes mean jog and auto controls, live position readout, a tuning screen and maybe a trend — one station's work for one operator. Screen size follows those tasks, the way how to choose an HMI display size by operator task lays it out, and a compact panel that passes both gates beats a large one that displays floats but cannot enter them.
Bench test: two axes, one RMC75E, Modbus/TCP #
Lock out hydraulic pump power and rest both axes on stops before this test: a write to a command register can stroke a live axis.
Inputs:
- Controller: one RMC75E, two position axes — the application in question.
- Link: Modbus/TCP over the controller's Ethernet port, fixed address on both ends (the controller accepts manual, BOOTP or DHCP addressing; use manual or a DHCP reservation).
- Test value: 25.4 mm, an illustrative position number chosen for this test because its fractional part betrays integer-only objects.
- Test register: one writable 32-bit floating-point register — a command value or user variable, not read-only axis feedback — taken from the register map in the RMCTools help.
Rule in words: IEEE-754 single precision stores one sign bit, an 8-bit exponent biased by +127, and a 23-bit fraction. Modbus moves those 32 bits as two consecutive 16-bit registers, and the panel driver decides which register carries the high word.
Arithmetic:
- Integer part: 25 = 11001₂. Fraction: 0.4 = 0.0110 0110 0110...₂, the pattern repeating. So 25.4 mm = 11001.0110011001100110...₂.
- Normalized: 1.10010110011001100110011₂ × 2⁴, sign bit 0.
- Exponent field: 4 + 127 = 131 = 10000011₂.
- Fraction field, 23 bits: 1001 0110 0110 0110 0110 011.
- The 32-bit word: 0100 0001 1100 1011 0011 0011 0011 0011₂ = 0x41CB3333.
- The two registers: 0x41CB = 16,843 and 0x3333 = 13,107 as raw 16-bit counts.
Enter 25.4 on the panel's keypad, write it to the test register, and read it back through every object type the project will ship.
| Panel shows | Diagnosis | Action |
|---|---|---|
| 25.4 | Float path and word order correct on that object | Object passes |
| About 4.17 × 10⁻⁸ (shown as 4.17E-08) | Words swapped: the pair is read as 0x333341CB | Set the tag's word-order property, retest |
| 16,843 and 13,107 | The object treats the registers as 16-bit integers | That object type fails |
The swapped reading follows from the same rule: 0x333341CB has exponent field 01100110₂ = 102, so the scale is 2^(102−127) = 2⁻²⁵ ≈ 2.98 × 10⁻⁸, and the fraction gives 1 + 0.400 = 1.400, so 1.400 × 2.98 × 10⁻⁸ ≈ 4.17 × 10⁻⁸.
Decision: the panel passes when every object type — entry keypad, display, trend, alarm comparator, script — returns 25.4 mm, and the same test on the second axis returns the same result. One failing object type anywhere rejects the panel for this project; a panel that displays floats but cannot enter or compare them is a reject, not a configuration job.
The decision for each case #
- Two axes, jog and tune, lowest cost: AutomationDirect C-more on Modbus/TCP, built from the example project.
- Programming, data logging or recipes at the panel: Red Lion G3 — higher hardware cost, free software, same example-project starting point.
- Any other panel: purchase only after it passes both gates on the bench, on the exact firmware you will ship.
- Historian or SCADA-class features: a PC HMI runtime on a panel PC, held to the same two gates.
Questions asked
Which of the three protocols should the panel use?
Default to Modbus/TCP: it has the widest panel support, the simplest troubleshooting, and the C-more and G3 example projects are built around it. Pick EtherNet/IP when the site already standardizes on that network and the panel documents a suitable driver, and CSP (DF1 over Ethernet) only when a panel offers neither of the other two.
The panel shows 4.17E-08 where 25.4 mm was written. Is the panel faulty?
Not faulty. The two 16-bit words are swapped: 25.4 mm encodes as 0x41CB3333, and read backwards as 0x333341CB it is a valid float near 4.17E-08. If the driver has a word-order property, set it and the display returns 25.4. If it has none, that driver cannot serve this controller.
Can one panel serve the RMC75E and a PLC on the same network?
Yes, when the panel's driver list covers both controllers and the total connection count stays inside the panel's documented limit. Count the work first: jogging and tuning two axes while viewing PLC status is one station's job when the drivers and ports support the combination.
Can I skip the bench test by starting from the example project?
No. The example project clears the protocol and register-map gates, but your own screens add objects the example never exercised: your alarm limits, your trends, your entry keypads. Run the 25.4 mm round-trip on those before the panel is accepted, because inherited screens and new screens fail differently.