IMDTouchKnowledge BaseShop main store

How-to

Deploying a compiled WinCC Runtime Advanced project to a separate PC

HMI and touchscreens Published 5 min read By IMDTouch engineering team

Short answer

Compiling a WinCC Advanced HMI in TIA Portal V14 generates the runtime file in the project's HMI subdirectory. Copy that file to the target PC — which needs WinCC Runtime Advanced installed and a matching runtime license, but no TIA Portal — and open it to start runtime, or download the HMI station directly over a configured transfer connection.

On this page
  1. What the target PC must already have
  2. The deployment procedure, step by step
  3. File copy or download: pick by connectivity
  4. Why there is no save-to-file button in V14
  5. When the download button stays greyed out
  6. Recompiled edits must travel again
  7. The decision
  8. Questions asked

Compiling a WinCC Advanced HMI in TIA Portal V14 already produces the deployable file: it is written into the HMI subdirectory of the project folder. Copy that compiled runtime file to the target PC, which needs WinCC Runtime Advanced installed and a matching runtime license but no TIA Portal, and open it to start runtime. If the target PC is reachable over the network, skip the file copy and download the HMI station directly, the same way you download a PLC. What TIA V14 no longer gives you is the explicit save-to-file function you may remember from WinCC flexible — the compiled file is the deliverable, and the two routes below are the only ones you need.

What the target PC must already have #

Three things, checked before you move any file:

  • Runtime software. WinCC Runtime Advanced, matching the application version. Order it through the vendor or an authorized distributor, and state the exact version you need when you do — a generic WinCC installer is not the answer.
  • A runtime license key. PC-based WinCC runtimes require a license key, and the tiers are graded by tag count; the licensing documentation names a runtime with 128 tags as one example. Worked example: an HMI configured with 60 tags needs a tier covering at least 60, so a 128-tag runtime license covers it with 68 tags of headroom (128 − 60 = 68). Match the tier to your configured tag count, not to the other way around.
  • No TIA Portal. The engineering system is not needed on the runtime PC and copying it there does nothing useful. For the full PC-side checklist — operating system, runtime installation, license — the guide on what WinCC Runtime Advanced needs on an S7-1200 HMI PC lists the requirements. The pattern is not WinCC-specific either: a deployment target must have its own licensed runtime system installed, the same dependency the article on VeriStand deployment requiring its licensed system installed describes for its tool.

The deployment procedure, step by step #

  1. Compile the HMI station. In TIA Portal V14, compile the WinCC Advanced station and resolve every reported error until compilation completes. A failed compile leaves either no runtime file or a stale one.
  2. Find the compiled runtime file. On the engineering PC, open the project folder and look in the HMI subdirectory of the project path; the compile step writes the runtime file there. Check the file's modification time against the moment you compiled — it should match, which is how you tell it apart from older builds and engineering files.
  3. Move the file. Copy the runtime file to removable media or a network share and place it on the target PC in a folder you will find again.
  4. Start it. With WinCC Runtime Advanced installed and licensed on that PC, opening the file — double-click works — starts the runtime with your application loaded. For the differences you may hit on a V14 application, the article on running a TIA Portal V14 HMI on WinCC Runtime Advanced walks the launch side.
  5. Or download instead. If a transfer connection between the engineering PC and the runtime PC exists, select the HMI station and use the download command, exactly as you would download a PLC program.

File copy or download: pick by connectivity #

File copy Download over connection
Connection needed None; removable media carries the file A configured transfer connection between the two PCs
What moves One compiled runtime file The whole HMI station, from TIA Portal
Prerequisite on the target Runtime installed and licensed Runtime installed and licensed, transfer settings reachable
First check when it fails File timestamp and file association with the runtime Download button availability, then transfer diagnostics

The decision follows directly from the wiring: if no connection to the target exists, use the file copy — compile, take the file from the HMI subdirectory, copy it, open it. If a configured connection exists, use the download; it is faster on repeat deployments and cannot pick up the wrong file.

Why there is no save-to-file button in V14 #

WinCC flexible had a dedicated function that stored the project as a PC file, and TIA Portal V14 dropped that separate command because compilation itself produces the runtime file. You are not missing a menu item; the file you are looking for is already sitting in the project's HMI subdirectory after a successful compile.

When the download button stays greyed out #

A greyed download command points at the engineering environment, not at the target. First, end any running HMI simulation — an active simulation occupies the runtime and blocks the download. If the command is still greyed after that, close and reopen the project, reselect the HMI station, and save your changes before looking again. Once the button is available but the transfer starts and then aborts, the problem has moved to the connection: the troubleshooting article on fixing a WinCC PC station download comms error from TIA Portal V13 covers that branch. Stopping a simulation and reopening the project will not fix a missing runtime installation, a wrong runtime version, or an unreachable target — those need their own corrections.

Recompiled edits must travel again #

The runtime file is a snapshot of the last successful compilation. Edit screens afterwards and the copy on the runtime PC keeps showing the old screens until you recompile and redeploy; the article on why an HMI edit needs a new runtime download explains the mechanism. Keep the engineering project as your editable master and treat every runtime file as disposable output of a dated compile.

The decision #

  • Runtime PC with WinCC Runtime Advanced installed and licensed, no network path: compile, copy the file from the HMI subdirectory, open it on the target. Done.
  • Configured transfer connection in place: compile once and download; skip the removable media.
  • Download button greyed out: stop the simulation, reopen the project if needed, then download.
  • Download available but the transfer aborts: troubleshoot the transfer path, not the project.

One safety note before handover: a successful launch proves the application executes, not that it talks to the machine correctly. Verify tag reads, button writes and alarm behavior against the live controller on a controlled test before the screen is put in front of operators.

Questions asked

Does the runtime PC need TIA Portal installed?

No. TIA Portal is the engineering tool and stays on the PC that edits and compiles the project. The runtime PC needs only a matching WinCC Runtime Advanced installation and a valid runtime license key. Without that runtime software the copied file cannot start at all, and without the license key the installed runtime will not run the project.

What license does a PC-based WinCC runtime need?

PC-based WinCC runtimes require a license key, and the variants are graded by tag count. The licensing documentation names a WinCC runtime with 128 tags as one example tier. Pick the tier that covers the number of tags your HMI actually configures, and check the license before the first launch rather than after it fails.

Can I view the application on a PC without deploying a runtime?

If a Comfort panel such as a TP1200 is already mounted on the machine, its web-client mirroring function can display the panel's running application on the PC over the network. That is viewing an application executed on the panel, not a deployment: the panel keeps running the project, and no runtime is installed on the PC.

Why does my copied file still show the old screens?

The runtime file reflects the last successful compilation. Screens edited after that compile, or a compile that failed, never reach the copied file. Recompile until it completes without errors, confirm the file's timestamp in the HMI subdirectory has updated, and copy the fresh file over the old one on the runtime PC.

Keep reading

  • Selection guide

    How to Prove a PC-Based HMI Before Replacing Panel Terminals

    Use an isolated bench controller to compare candidate PC-based HMI runtimes. Test the read path, one write to a spare test tag, touch response, communication loss and automatic recovery. Check the deployed license on the target PC.

    HMI and touchscreens

  • How-to

    Migrating a WinCC PC Runtime project to a Comfort panel

    There is no whole-project conversion from a WinCC PC runtime station to a TP1500 Comfort panel. Copying screens inside TIA Portal is supported, but each object, faceplate and system function must be dispositioned and reconfigured for the Comfort system. Advanced sources transfer with the least rework, Professional sources need object-by-object reconciliation, and a Unified source should move to a Unified Comfort panel instead of being converted.

    HMI and touchscreens

  • How-to

    Backing Up an M172 Controller and HMIST6400 Runtime Files

    Yes. The M172 keeps its compiled application on the controller, and you can pull it with the engineering software, over FTP, or to a USB pendrive through a system function; the HMIST6400 saves its compiled project from the hardware menu. Neither file is editable source, and the HMI project runs only on the firmware tied to its EOTE version, so record that firmware with the backup.

    HMI and touchscreens