Troubleshooting
Fixing a WinCC Comfort license not valid error in TIA Portal V11 SP2
Short answer
The "license WinCC Comfort not valid" dialog at TIA Portal V11 SP2 startup is an engineering-station problem, not a KP1500 Comfort fault: the WinCC Comfort option, its Update 2, the Comfort Panels HSP or a valid license key is missing. Install the option, apply Update 2, import the HSP and repair the key in Automation License Manager, then bring the OP37 project across through ProTool and WinCC flexible before re-targeting the KP1500 Comfort.

On this page
- What the startup message is really reporting
- Fix the engineering station in this order
- Match the panel part number to the WinCC Comfort version
- Bring the OP37 project across in three conversions
- Working the OP37 to KP1500 Comfort chain for a 6AV2124-1QC02-0AX0 panel
- Prove the fix before you trust the station
- Questions asked
The "License WinCC Comfort not valid" dialog that appears when TIA Portal V11 SP2 starts is an engineering-station problem, not a fault on the new KP1500 Comfort. The station is missing one of three things: the WinCC Comfort option itself, the update and hardware support package (HSP) that add the KP1500 Comfort to the catalog, or a valid WinCC Comfort license key. Fix them in that order — install the option, apply its Update 2, import the Comfort Panels HSP, then put the key right in Automation License Manager — and the panel hardware stays untouched. With the station clean, the OP37 project travels through ProTool and WinCC flexible 2008 SP2 before it is re-targeted to the KP1500 Comfort.
What the startup message is really reporting #
The dialog is station-side and it has exactly three sources. Each leaves a different trace, so identify yours before changing anything:
- No WinCC Comfort option installed. TIA Portal V11 SP2 ships in several editions, and a STEP 7-only or WinCC Basic installation carries the framework without the Comfort editor. The portal runs, but the Comfort option cannot be licensed because it is not there.
- License key missing or invalid. The key lives in the Automation License Manager repository — on a local disk, a license key disk or dongle, or a license server. A key that was never transferred, was moved elsewhere, or shows as invalid produces this dialog, and it survives every reboot until the key stack is corrected.
- Comfort Panels HSP missing. Without the HSP for this TIA Portal version the KP1500 Comfort is not in the device catalog, and the unresolved device type cascades into the same license and module complaint at startup.
Fix the engineering station in this order #
- Confirm the installed edition. Open the Windows program list (Programs and Features, or Apps on Windows 10) and check for the entry
SIMATIC WinCC Comfort V11.0 + SP2. If the list shows onlySIMATIC STEP 7 Basic V11.0 + SP2orSIMATIC WinCC Basic V11.0 + SP2, the Comfort editor cannot be licensed. Run Setup from the installation medium, choose the modify route, enable the WinCC Comfort item and complete the install. - Apply the update. Install TIA Portal V11 SP2 Update 2; the service pack by itself does not fully support the KP1500 Comfort, and the HSP in the next step installs on top of it.
- Import the Comfort Panels HSP. Download the HSP package for TIA Portal V11 SP2 from Siemens Industry Online Support and extract it. In TIA Portal open
Options > Support Packages, clickAdd from file systemand select the extracted.hspfile. The KP1500 Comfort then appears in the device catalog; restart TIA Portal so the new device description is loaded. - Repair the key in Automation License Manager. Open Automation License Manager and inspect the local repository and any connected license server for the WinCC Comfort key. If it is missing or marked invalid, transfer it again from the license medium: connect the medium with
Edit > Connect Target System, set the target to Local, and transfer the key. If the key exists on no disk, dongle or server, the station has no license to activate — that gap closes with a license from the vendor, not with a tool. Keys that keep vanishing after a restart point at the storage side, so read why WinCC license keys disappear on an embedded IPC. - Open the migrated project and compile. The KP1500 Comfort device must show no unknown-device marker, and the compile must run without a license dialog.
Match the panel part number to the WinCC Comfort version #
Read the part number off the rating plate before spending time on the migration. The last characters set the minimum engineering version, and no V11 repair moves that gate:
| Rating plate part number | Configurable with WinCC Comfort from | Station that works |
|---|---|---|
| 6AV2124-1QC02-0AX0 | V11 SP2 | V11 SP2 with Update 2 and the Comfort Panels HSP |
| 6AV2124-1QC02-0AX1 | V14 SP1 with HSP | V14 SP1 or later, with its Comfort Panels HSP |
The AX1 data sheet describes the same hardware family — key operation, a 15-inch widescreen TFT display with 16 million colors, a PROFINET interface — but the two suffixes are not interchangeable: the AX1 revision cannot be configured from V11 SP2. If the plate shows the AX1 number, stop repairing the V11 station and move the final migration to a station with V14 SP1 and its HSP.
Bring the OP37 project across in three conversions #
The OP37 project never reaches TIA Portal directly; it is converted step by step, the same staged logic as migrating a WinCC 7.0 project to TIA Portal in two stages:
- ProTool: re-target the panel. Open the OP37 project in ProTool and change the device to the MP377 15" Touch. Save the project.
- WinCC flexible 2008 SP2: convert the file. Use the Open ProTool project command and keep the MP377 15" Touch as the target; if you skipped the ProTool step, the same command lets you pick the nearest successor, the OP377, instead. Save the result as a WinCC flexible project.
- TIA Portal V11 SP2: migrate to Comfort. Run the TIA Portal migration on the WinCC flexible project, then change the HMI device from the MP377 to the KP1500 Comfort.
- Re-assign the navigation keys. Screens, tags and alarms come across untouched; the function keys, soft keys and screen-change buttons on every screen must be matched to the KP1500 Comfort key layout. This is the only rework.
- Compile, download, run. Compile, transfer the project to the panel and press through every screen once. Do the first download with the machine in a safe state, because the transfer interrupts whatever the panel was displaying.
One warning for the station: installing WinCC flexible beside a newer TIA Portal is a known way to break the newer installation, so read why installing WinCC flexible breaks TIA Portal V13 before putting both on one engineering PC.
Working the OP37 to KP1500 Comfort chain for a 6AV2124-1QC02-0AX0 panel #
Inputs, with their source:
- Source project: an OP37 configured in ProTool — the replacement case in the field.
- Target panel: KP1500 Comfort, part number 6AV2124-1QC02-0AX0 from the rating plate.
- Engineering station: TIA Portal V11 SP2 with the WinCC Comfort option, Update 2 and the Comfort Panels HSP installed.
- Bridge tool: WinCC flexible 2008 SP2.
Rule. A panel accepts a project only when the installed WinCC Comfort version is at least the minimum its part-number revision requires, and the OP37 project leaves ProTool only through WinCC flexible.
Arithmetic.
- Minimum for the AX0 revision: WinCC Comfort V11 SP2.
- Station as built: V11 SP2 plus the update and the HSP.
- Compare: V11 SP2 plus the update meets or exceeds V11 SP2, so the requirement is satisfied and the KP1500 Comfort can be targeted.
- Same test on the AX1 revision: the minimum is V14 SP1, the station is V11 SP2, and V11 SP2 is below V14 SP1, so the requirement fails and no V11-era update closes that gap.
Result. Three conversions on one station — OP37 to MP377 15" Touch to KP1500 Comfort — with the navigation keys as the only rework before the first download.
Decision. With the AX0 suffix on the plate, stay on this station and run the chain as written. With the AX1 suffix, the deciding threshold is that V14 minimum: anything below it cannot configure the panel, so upgrade the engineering station instead of reinstalling V11 SP2.
Prove the fix before you trust the station #
- TIA Portal starts with no license dialog, before any project is opened.
- Automation License Manager shows the WinCC Comfort key as valid on Local or the license server.
- The device catalog lists the KP1500 Comfort, and the migrated project carries no unknown-device marker.
- The compile finishes without a license message.
- The download completes and the panel runs the migrated screens, with every navigation key verified once.
Questions asked
Why does the license dialog appear before any project is open?
The license check runs when TIA Portal loads the WinCC Comfort option at startup, not when a project compiles or downloads, so the dialog appears over an empty portal. Nothing on the panel is queried during that check: the KP1500 Comfort can be unplugged and the message is identical, which rules the hardware out as the cause.
Why is WinCC flexible needed as a bridge for the OP37 project?
TIA Portal has no ProTool import, so the project must first be saved by WinCC flexible. Its last release is the only tool with the Open ProTool project command, which converts the ProTool data and saves it in a format the TIA Portal migration can read. Without that stage there is no file to migrate, and the OP37 project never reaches the Comfort world.
The rating plate shows 6AV2124-1QC02-0AX1. What changes?
Only the final stage. The ProTool re-target to the MP377 15 inch Touch and the WinCC flexible conversion stay the same, but the last migration and the device change to the KP1500 Comfort must run on a station with WinCC Comfort V14 SP1 and its HSP, because that revision cannot be configured from V11 SP2 at all. No V11 update adds it.
Where do I enter the license key inside TIA Portal?
Nowhere, because TIA Portal has no key entry dialog. Automation License Manager administers every key: open it, look under the local repository or the connected license server, and transfer the WinCC Comfort key there from the license medium. Once the manager shows the key as valid, TIA Portal picks it up on the next start.