Troubleshooting

Get past the application password into PanelView Plus configuration

HMI and touchscreens Published 8 min read

Short answer

Touch the white square that appears for one to two seconds in the lower-left corner during boot to open Configuration Mode, then use file management to delete the MER, font and log files blocking the firmware upgrade. If no square appears, search the documentation printed from the original project for the passwords, then download a one-screen version 4 MER with a Goto Config button.

On this page
  1. How do I get past a password-protected application on a PanelView Plus?
  2. Where should I look for the application password before deleting anything?
  3. How do I catch the white square during startup?
  4. What do I do when the white square never shows up?
  5. How do I build a temporary MER that gets me into Configuration?
  6. Which files do I delete, and how much space is enough?
  7. How do I run the firmware upgrade once the space is free?
  8. When is replacing the terminal the better call?
  9. Questions asked

A locked application does not lock the terminal: Configuration Mode still exists behind it, and its file management screens delete the MER, font and log files standing in the way of the firmware upgrade. Touch the brief white square that appears in a corner during boot. When the square does not show, find the credentials in the documentation printed from the original project first, and only then replace the runtime with a one-screen version 4 MER whose only control is a Goto Config button. This article walks those routes in the order worth trying, with the storage arithmetic that tells you when the terminal is ready for the firmware package.

How do I get past a password-protected application on a PanelView Plus? #

Touch the small white square in the lower-left corner of the display during the one to two seconds it appears at boot, and the terminal opens Configuration Mode instead of the application, where file management lets you delete the stored files.

The application password protects the runtime screen the terminal auto-starts at power-up; it does not protect the terminal's own boot sequence. What you see at power-up decides the route:

  • The application starts and demands a password: the MER auto-launched. Search the project documentation for credentials before you delete anything.
  • A white square flashes in a corner during boot: touch it inside its window and you land in Configuration Mode.
  • No square at all: the prompt depends on the firmware revision and a safe-mode setting. Try the keyboard route, then the temporary MER.
  • Configuration opens but storage is short: work through file management until free space crosses the number the firmware package states.

Work in this order: documentation first, boot prompt second, temporary MER third. Deletion is the step that frees the space, never the first move on the panel.

Where should I look for the application password before deleting anything? #

Search the printed documentation generated from the original FactoryTalk View project first, because the exported documentation lists every login and password in plain text, and credentials found there open the application without touching the running files.

That is how the case that established this procedure ended: the original program was located, its documentation was printed to PDF, and every login and password sat in the output, not hidden. Reproduce it like this:

  • Locate the original FactoryTalk View project and any documentation generated from it, on the engineering workstation or in the integrator's records.
  • Print or export the documentation again if the paper copy is gone, and search the output for credential entries.
  • Enter the recovered credentials at the application login, then use the application's own controls to stop it and reach the terminal menus.
  • File the credentials with the panel's maintenance records before any firmware or file change.

This is the only route that leaves the running application untouched, which is why it comes first. When no project, no documentation and no backup exist at all, the problem is credential recovery rather than disk space, and recovering access to a password-protected HMI panel without a backup covers that ground.

How do I catch the white square during startup? #

Power-cycle the terminal, or press its reset control with a non-conductive probe such as a toothpick, and watch the corner where the prompt appears from the first boot image until the application loads.

The window is short and unforgiving: the square renders, boot continues, and the password screen returns if you miss it. Watch the display continuously from the moment power goes in — do not wait for the application. The prompt was reported low in the corner on compact units in this family, so watch that corner first and the bottom edge of the display generally.

If the terminal's startup behaves differently from this, the wider set of startup routes is in how to enter configuration mode on a touch HMI, including terminals with no touch prompt at all.

What do I do when the white square never shows up? #

Fall back to the keyboard route or a temporary MER, because the prompt depends on the terminal's firmware revision and its safe-mode setting, and in one reported case it appeared only after the firmware was upgraded to version 5.

The setting that governs the prompt is Detect safe mode request at startup. On PanelView Plus 6 and 7 it sits on the Startup Options tab, in the Boot section, under Safe Mode; on the older generation the path is Control Panel, then System, then Start-up Options, then Boot Option. Turning it on requires already being in Configuration Mode — exactly what the password denies — so when the square never shows, the setting cannot rescue you. One report on a PanelView 1500 brought the prompt up by holding F12 during boot with a keyboard attached; treat that as a reported fix for that model and spend one restart trying it. The route that always works is the temporary MER below.

The related symptom of a terminal at flash capacity with no configuration access at all is covered in PanelView Plus 600 with no config button and full flash.

How do I build a temporary MER that gets me into Configuration? #

Create a one-screen project saved for a version 4 runtime with a single Goto Config button, download it set to launch on completion, and the terminal boots straight into a screen whose only job is opening Configuration.

  1. Create a new project in version 4 — or build it in FactoryTalk View Studio 5 and pick the older runtime revision when you create the MER, since Studio saves runtime files in older revisions.
  2. Give the project exactly one screen.
  3. Put exactly one control on the screen: the Goto Config button.
  4. Enter the communication parameters the installation actually uses — the driver and path the retired application talked over — because the download otherwise lands a terminal with nothing to say.
  5. Download the MER to the terminal with Run application after download checked.
  6. Check Replace Communications only when the temporary project's communication settings must overwrite the terminal's stored configuration; leave it unchecked when the existing setup must survive.
  7. At runtime, press the button and go straight to file management.

That revision choice follows the vendor's recommendation to run a MER of the same revision as the terminal's firmware, and this terminal still sits on old firmware. Two consequences to plan for: the download replaces the application, so keep any copy of the original MER you can find; and user accounts download with the runtime file, which is why the login you could not find disappears — keeping PanelView Plus user passwords after an MER download explains that behavior.

Which files do I delete, and how much space is enough? #

Delete the retired application's MER, its fonts and the accumulated log files after copying them off the terminal, and keep deleting only until the free space crosses the number stated in the upgrade instructions for your exact model.

There is no universal megabyte figure, because each firmware package sets its own requirement; your two numbers are the free space file management reports and the requirement printed in the package's upgrade document. Worked example, illustrative — the arithmetic is the transferable part:

  • Requirement in the upgrade document: 15 MB free.
  • Free space reported by file management: 3 MB.
  • Files listed: 9 MB MER from the retired application, 2 MB of fonts, 4 MB of logs.

Deleting the MER and the logs gives 3 + 9 + 4 = 16 MB free, which clears the 15 MB requirement with 1 MB of margin, so the fonts stay. Had the requirement read 18 MB, the same deletions would leave you 2 MB short and the fonts would have to go as well: 16 + 2 = 18 MB, at the line with nothing to spare — a position to avoid on flash storage, so delete them only if the numbers force it and re-check before starting the upgrade.

Rules while you delete:

  • Copy any file off the terminal that you might want back, especially logs with process history and the MER if no other copy exists.
  • Delete through the file management screens and let each operation finish; do not cycle power mid-delete.
  • Completely erasing memory is not the goal — cross the stated requirement with the fewest deletions and stop.

How do I run the firmware upgrade once the space is free? #

Load the firmware package for your exact model onto a flash card and run the card-based procedure, since both the vendor's guidance and field practice for this generation favor the card over Ethernet or serial download routes.

Firmware packages come from the manufacturer's support site and differ by model, so confirm the terminal's full catalog number — not the size label like 1000 — before you download anything. Follow the package's own step-by-step upgrade document for the preparation list: required free space, card preparation, and the load sequence. Once the new firmware is in, re-save the real application's runtime at the matching revision before restoring it, so the terminal is not left running a mismatched MER.

If the upgrade utility itself rejects the terminal or the revision, that limit and its workaround are in when the firmware upgrade utility cannot upgrade an HMI terminal.

When is replacing the terminal the better call? #

Replace it when the manufacturer no longer publishes firmware for the exact model or the storage cannot hold the runtime you need, and put a PC-based panel running the vendor's Windows runtime in its place.

The engineering investment survives the swap: PanelView Plus applications are built in FactoryTalk View Studio for Machine Edition, and that Machine Edition runtime also runs on Windows touchscreen computers, so a terminal whose firmware path has dead-ended can hand its application to industrial panel PCs at the machine. Check the runtime license, the runtime version on the target machine, and host operating system support as three separate verifications before you commit the panel.

Questions asked

Does the application password travel with the MER file?

Yes. User accounts and security settings download as part of the runtime file, which is why a terminal's login behavior changes after every MER download and why the temporary application works. The password you cannot find lives in the application you replace, so a minimal project with no security configured leaves the path to Configuration open.

Why does the temporary project need communication parameters at all?

Because the one-screen runtime replaces the application that held the terminal's working driver and path. If the new project carries no communication setup, the terminal comes up with nothing to talk over and you inherit a second problem while solving the first. Enter the same driver and path the retired application used.

What does the Replace Communications checkbox do?

It overwrites the communication configuration stored on the terminal with the settings in the project being downloaded. Check it only when the temporary project carries the driver and path the installation really uses; leave it unchecked when the terminal's existing communication setup is correct and must survive the swap.

Do I need to wipe the terminal completely before a firmware upgrade?

No. The upgrade needs free space, not an empty terminal. Delete the files the package instructions make room for — typically the retired MER, the fonts and the logs — after copying off anything worth keeping. A full erase is not part of the documented procedure and only costs you files you may want back.

Keep reading

  • Troubleshooting

    Why a PanelView 5310 Says Not a Valid Device for an MER File

    The message is a platform mismatch, not a terminal fault. An .mer file is a FactoryTalk View Machine Edition runtime for PanelView Plus 6 and 7 terminals, while the PanelView 5310 belongs to the PanelView 5000 family and runs Studio 5000 View Designer projects. Either run the .mer on a PanelView Plus or a PC with the Machine Edition runtime, or rebuild the application as a View Designer project.

    HMI and touchscreens

  • How-to

    Convert an Old MER File to FactoryTalk View 13

    Renaming a v4.0 .mer or picking a newer runtime in Studio converts nothing: the documented path is restoring the runtime in FactoryTalk View Studio, auditing what came back, and rebuilding what did not. Plan for alarm messages to be lost on a v4.0 restore.

    HMI and touchscreens

  • How-to

    One FactoryTalk View ME Project Builds One PanelView Runtime

    One FactoryTalk View ME project creates exactly one .mer runtime, and that runtime runs on one PanelView Plus terminal. Two terminals therefore take the same .mer loaded on both, or two separate projects. For one controller and two identical 2711P terminals, build once and load twice; split into two projects only when screen size, resolution or communication targets differ.

    HMI and touchscreens