Troubleshooting
Getting ALARM_S texts from STEP 7 CFC onto a Comfort Panel
Short answer
The texts do not travel over the panel's runtime connection. Add a proxy PLC in WinCC V13 that references the SIMATIC Manager project, bind its data to the Comfort Panel, and the ALARM_S texts configured on the controller appear at the panel; the CFC project stays authoritative in SIMATIC Manager.

On this page
- Why does a working PLC connection deliver values but no alarm texts?
- What is the proxy PLC in WinCC V13?
- How do you create the proxy PLC and connect the Comfort Panel to it?
- How do the CFC alarm signals become panel alarms?
- Why does an alarm appear with a missing or old text?
- Why does the alarm never appear at all?
- How do you prove the whole path with one test?
- Questions asked
The texts will not come through the connection the panel already has. A Comfort Panel on a live S7 connection reads and writes tags, but ALARM_S message definitions stay in the STEP 7 project until WinCC holds an engineering reference to it. For a controller engineered in CFC under SIMATIC Manager, that reference is the device proxy PLC of WinCC V13: the proxy opens the controller's current project data, the panel's alarms bind to it, and the texts configured in the PLC project appear at the panel. The checks below take you from a panel that shows values but no alarm texts to a working alarm path, with the CFC charts left exactly where they are.
Why does a working PLC connection deliver values but no alarm texts? #
Because the runtime connection and the alarm engineering data are two separate channels: the connection moves tag values, while the ALARM_S texts stay in the STEP 7 project and travel only through an engineering reference.
A tag that updates proves the address, the driver and the cable. It proves nothing about texts, because texts are engineering data, not runtime data:
- The runtime connection carries values: process tags read and written while the machine runs.
- The engineering data carries definitions: symbols, data blocks, alarm configuration and message texts, all maintained in SIMATIC Manager.
- A manually created HMI connection gives the panel the first channel only.
Read the symptom as it is: live values with missing alarm texts is the normal picture of a missing proxy, not of a broken network, and rebuilding the connection will not change it.
What is the proxy PLC in WinCC V13? #
It is an engineering stand-in for a controller maintained outside TIA Portal: the device proxy PLC gives WinCC direct access to the SIMATIC Manager controller and its current data, such as symbols and data blocks.
Nothing moves out of the controller project. The CFC charts, the alarm configuration and the message texts stay in SIMATIC Manager and stay authoritative; the proxy is initialized from that project's file and mirrors its compiled state for the HMI engineering. At runtime the panel still talks to the real controller over its configured connection, because the proxy exists in the engineering tool only.
The same idea runs the other way when the work starts from the STEP 7 V5.x side: there the Comfort Panel itself appears as a device proxy rather than a GSDML file, which is explained in why a Comfort Panel in STEP 7 V5.x needs a device proxy.
One version limit: WinCC V13 is the release documented for this route, and the Comfort Panel configured in the project must be a target that this engineering release supports. On a later release, read that release's own integration description before repeating the steps.
How do you create the proxy PLC and connect the Comfort Panel to it? #
Back up both projects, then add a device proxy in the WinCC project and initialize it via the SIMATIC Manager project file, which loads the controller's compiled data into the HMI engineering.
Work in this order:
- Compile the SIMATIC Manager project and note the revision; the proxy mirrors exactly the state you compile.
- Add a device proxy in the WinCC project and initialize it via that project's file.
- Configure an HMI connection with the device proxy, and point the connection at the real controller's network address, because the proxy itself is not a runtime partner.
- Connect PLC tags from the device proxy with HMI tags, including every tag the alarm configuration needs.
- Compile the panel project and download it to the Comfort Panel.
Dialog names differ between releases, so follow the workflow of the installed release rather than any similarly named import: a wrong file type loads without an error and silently leaves the alarm data behind.
How do the CFC alarm signals become panel alarms? #
The controller generates the event and the panel only presents it: you bind the panel's alarm configuration to the signals the proxy now carries, in the documented order — tags first, then alarms with their acknowledgement behavior.
In the chart, the alarm is raised and cleared by the ALARM_S system functions: SFC 17 triggers the signal and SFC 18 acknowledges it, and the panel shows the engineered text for that signal. On the panel side the alarm configuration runs in a fixed order:
- Create tags, because the alarm configuration builds on them.
- Configure the alarms: message classes, texts, acknowledgement behavior, and the associated values bound so the text can show a process value.
The configuration of ALARM_S messages is identical to that of ALARM_D messages, so the same two steps serve both, and associated process values display for either. An associated value is only as good as its binding: if the wording is right but the number inside the text is wrong, re-check the tag that value is bound to, not the proxy.
Why does an alarm appear with a missing or old text? #
Because the text path is stale or incomplete: either the proxy still reflects an older project state, the active panel language has no text for the event, or the panel runs an earlier compiled build.
Check in this order:
- Stale proxy: it was initialized before the last change to the texts. Refresh it from the current SIMATIC Manager project, then recompile and download the panel project.
- Missing language: the text exists, but not in the language selected at the panel. If another language shows correct wording, fix the language set and its texts; the connection is fine.
- Old build: the panel runs an earlier compiled project. Compare the loaded revision with the engineering and download the current configuration.
- Wrong value inside a correct text: the associated-value binding points at the wrong tag.
Why does the alarm never appear at all? #
Because the event itself, not the text, is missing: confirm the controller actually raises the alarm, that the HMI connection is up, and that the panel's alarm view includes this alarm class and is not filtering it.
- Generation: raise the event through an approved commissioning test, and never defeat an interlock to force an alarm.
- Service support: the panel must support the alarm service the controller uses, a question which alarm service an S7-400H and Comfort Panel support answers before you chase texts.
- Connection: read the connection status and one live value over the same connection; fix communications before judging alarms.
- Display: check that the alarm view includes the event's alarm class and that no filter hides it; if the event shows in another view, correct the view, not the PLC.
Keep the two symptom families apart: a missing event is never a text problem.
How do you prove the whole path with one test? #
Trigger one known ALARM_S event on an isolated bench and read the alarm counts before and after: unacknowledged alarms must go from zero to one on trigger and back to zero on acknowledgement, with one new buffer entry.
Run the test with the chart able to raise one event on demand, and note the clock time at each step. Worked example with example values:
- Start: 12 entries in the alarm buffer, 0 unacknowledged alarms.
- Trigger the test event once: unacknowledged 0 + 1 = 1, buffer 12 + 1 = 13.
- Acknowledge at the panel: unacknowledged 1 - 1 = 0, buffer stays at 13.
- The new entry must show the configured text with its associated value in the active language; the two noted times give the display delay to compare against the configured update cycle.
The decision for each case: a controller engineered in CFC under SIMATIC Manager gets the device proxy in WinCC V13, and the PLC project stays authoritative there; a controller engineered together with the panel in TIA Portal needs no proxy, because the integrated configuration carries the alarm data; a panel that only displays values needs nothing from this workflow.
Questions asked
Does the proxy PLC need the controller online when it is created?
No. The proxy is initialized from the SIMATIC Manager project file on the engineering computer, so the controller can stay offline and even powered down. The proxy mirrors the compiled state of that file; going online matters later, when the panel's runtime connection is tested against the real controller.
Where does the proxy keep its copy of the controller data?
Inside the WinCC project. Once initialized, the device proxy is a project object that carries the imported symbols, data blocks and alarm definitions until you refresh it. That stored copy is why an unchanged proxy keeps serving old texts even after the SIMATIC Manager project was edited.
Is a proxy needed when the controller is engineered in TIA Portal?
No. When controller and panel sit in one TIA Portal project, the alarm definitions transfer through the integrated project data and no proxy exists or is needed. The proxy is specifically the bridge to controllers maintained in SIMATIC Manager.
Which document describes the proxy workflow?
The Siemens application description 'Integrated Configuration with WinCC (TIA Portal) and SIMATIC Manager' covers the device proxy PLC, the initialization from the project file and the access to symbols and data blocks. Use the revision that matches the installed WinCC release, since the workflow is release-specific.
Can the missing texts simply be rebuilt as ordinary HMI alarms?
Not as a first move. Re-creating the event as a discrete alarm in the panel moves the evaluation from the controller to the HMI, so the panel and the PLC program can disagree about what is alarmed and when it clears. Repair the controller-alarm path first and record any substitute as a documented deviation.


