Explainer
Comfort Panel in STEP 7 V5.x: why a device proxy, not a GSDML
Short answer
Siemens publishes no standalone GSDML for the 0AX1 Comfort Panel refresh, so you cannot insert it into STEP 7 V5.x HW Config as a generic PROFINET device. The documented path is a Device Proxy exported from the WinCC (TIA Portal) project, with the panel present in the TIA catalog through a version-matched HSP such as V14 HSP 0211. Per-panel fault diagnosis over PROFINET then comes from the PNIODiag block in the STEP 7 CPU.

On this page
When a STEP 7 V5.x project must live beside Comfort Panels programmed in WinCC (TIA Portal), the first instinct is to look for a GSDML file and insert the panel into HW Config like any PROFINET IO device. For a Comfort Panel that search dead-ends: Siemens publishes no standalone GSDML for the 0AX1 hardware refresh of the TP1500 Comfort (6AV2124-0QC02-0AX1), and the GSDML of the earlier 0AX0 series does not fit the refreshed device. The documented path is a Device Proxy exported from the WinCC (TIA Portal) project, with the panel present in the TIA catalog through a version-matched Hardware Support Package. Diagnosis of dropped panels over PROFINET is then done with the PNIODiag block in the S7 CPU.
Why no GSDML exists for the 0AX1 panel #
A Comfort Panel is a PROFINET IO device with a real stack: its slots carry the device access and the HMI tag interface, plus diagnostic submodules. But Siemens' intended workflow configures HMI panels inside WinCC / TIA Portal, where the panel is a TIA device, not a generic PN slave described by a GSD file. The first-series panels (order numbers ending 0AX0) were published as GSDML files, which is why they insert cleanly into STEP 7 V5.x HW Config. The 0AX1 refresh was never released as a public GSDML; it arrives through the TIA Portal catalog, delivered by a Hardware Support Package (HSP).
The symptom of forcing the old file is exact: HW Config accepts the insertion, but at PROFINET startup the device reports that the inserted and the configured module are not the same, typically as the module-substitute diagnostic. The old file describes the old slot layout, the new panel answers with its own, and the connection never reaches data exchange.
The documented path: HSP plus Device Proxy #
Two steps bring the 0AX1 panel into a combined STEP 7 V5.x and WinCC project:
- Update the TIA catalog. Install the cumulative HSP that matches your TIA Portal major version and contains the 0AX1 order numbers, for example V14 HSP 0211 on a V14 SP1 installation, via the support packages option of the TIA Portal. HSPs are cumulative and version-locked: an HSP built for another major version will not install.
- Export and install the Device Proxy. In the WinCC project, export the HMI station as a Device Proxy archive; in STEP 7 V5.x install that archive into the S7 project. The panel appears in HW Config as a PROFINET IO device with its slot map and tag interface, while configuration ownership stays with the WinCC project. STEP 7 V5.x is used only for tag exchange, cross-reference and diagnostics. The same proxy mechanism appears on the controller side when a WinCC PC runtime needs to reach a PLC it cannot address directly, as covered in connecting an S7-400H to WinCC Professional with a Device Proxy.
The same tool family has one extra dependency worth knowing: the Device Proxy function for SIMOTION controllers requires SIMOTION SCOUT TIA V4.4 or later, which is why SIMOTION device proxy initialization fails after MP277 migration when that component is missing. If you are new to the STEP 7 side of such a split project, a general background article on what STEP 7 is in a PLC project, and which one you need, is worth reading first.
Diagnosing dropped panels over PROFINET with PNIODiag #
The Device Proxy makes the panel visible to the CPU; it does not by itself evaluate faults. When several panels hang on one PROFINET system and one drops out, the requirement is to identify which one and show it on a master panel. The Siemens-shipped answer for STEP 7 V5.x is the PNIODiag diagnostic package: a block generated from the STEP 7 V5.x project that runs in the S7 CPU, evaluates the PROFINET IO (and PROFIBUS DP) diagnostics of the configured devices, and exposes structured results with device name, address, slot, channel and error type. The WinCC panel then reads those results as ordinary tags. For how the alarm side of such a connection looks on a Comfort Panel, see showing a PLC connection fault on a Comfort Panel alarm display.
Worked example: bringing five TP1500 Comfort panels (0AX1) into a STEP 7 V5.5 project #
The case: an S7 CPU programmed in STEP 7 V5.5, five Comfort Panels programmed in WinCC V14 SP1 over PROFINET, one master panel that must show which panel dropped out.
Inputs
- TIA Portal V14 SP1 owns the HMI projects (given by the thread).
- Panel order numbers end 0AX1; no public GSDML exists (documented in the Siemens support entries).
- Catalog update: V14 HSP 0211, cumulative for the V14 line (Siemens support entry on support packages).
- Panel count: 5; one master panel reads diagnostics, up to 4 others can drop.
Rule
Each HMI station is exported once from its WinCC project as a Device Proxy archive and installed once into the STEP 7 V5.5 project. PNIODiag is generated from that STEP 7 project, so every installed proxy is automatically inside its evaluation scope.
Arithmetic
- Proxy exports: 5 panels x 1 archive each = 5 archives to install in STEP 7 V5.5.
- HSP installs: 1 (the cumulative V14 HSP 0211 covers all 0AX1 order numbers in one pass).
- PNIODiag instances: 1 block set in the CPU, evaluating 5 PROFINET IO devices.
- Diagnostic tags to read on the master panel: 5 devices x 1 status each = 5 status tags minimum, plus the device-name and error-type fields PNIODiag delivers per device.
Result and decision
The decision: abandon the GSDML search entirely; install V14 HSP 0211 once, export 5 Device Proxies, and generate PNIODiag once. If a sixth 0AX1 panel is added later, add one more proxy export and regenerate the diagnostics; no GSDML step ever enters the procedure. If the panel count or the CPU's PROFINET load grows so that the cyclic diagnostic evaluation becomes too slow, evaluate the diagnostic buffer event-driven instead of cyclically — above roughly a dozen panels per CPU, switch to that event-driven evaluation.
What each path really requires #
| Case | GSDML published? | What STEP 7 V5.x needs |
|---|---|---|
| Comfort Panel, order number ends 0AX0 | Yes | Direct insertion in HW Config from the published file |
| Comfort Panel refresh, ends 0AX1 | No public download | Device Proxy export from WinCC (TIA Portal) plus a version-matched cumulative HSP (e.g. V14 HSP 0211) |
| Any of the above, with fault diagnosis over PROFINET | — | PNIODiag generated from the STEP 7 V5.x project, results read by the master panel as tags |
The engineering decision in one line: for a mixed STEP 7 V5.x and WinCC (TIA Portal) project, the panel lives in TIA, the proxy carries it into STEP 7, and PNIODiag carries its faults back out. Opening a service request with Siemens is the only route if a standalone GSDML is ever truly required — but for this workflow none is needed.
Questions asked
Can I keep the old 0AX0 GSDML and just rename the device?
No. The 0AX0 GSDML carries the slot layout of the first-series panel; the 0AX1 refresh answers with a different slot set, so the PROFINET connection ends in the module-substitute fault and the HMI tag interface stays down. Renaming the device does not change the slots it reports, so the mismatch stays.
Does the Device Proxy let STEP 7 V5.x configure the panel's screens or alarms?
No. The proxy only places the panel in the STEP 7 hardware configuration as a PROFINET IO device with its slot map and tag interface. Screens, alarms and runtime settings remain owned by the WinCC (TIA Portal) project; STEP 7 V5.x only exchanges tags, cross-references them and supplies the diagnostic data to the CPU.
Do I need a newer TIA Portal to export the proxy?
You need the TIA Portal version that owns the HMI project and whose catalog contains your panel order number. For a V14 SP1 project that means a cumulative HSP of the V14 line with the 0AX1 entries, for example V14 HSP 0211. An HSP built for another TIA major version will not install, so match the HSP line to your installation.
Is PNIODiag required, or can the panel itself report a neighbor's failure?
If the diagnosis must run over PROFINET, PNIODiag in the STEP 7 V5.x CPU is the shipped way to evaluate PROFINET IO diagnostics and expose them as readable structured data; a Comfort Panel on its own does not act as a diagnostics master for other IO devices. Reading those results into your master panel is then a normal tag connection.