HMI and touchscreens Published 9 min read By IMDTouch engineering team

Short answer

An H system that keeps control running proves nothing about the HMI: WinCC OA is reported to connect to an S7-400H but to lack the vendor's redundant-connection option for that system; treat any release as unproven until its driver documentation and a bench test prove switchover behavior. Test with a changing value, alarm events and a command feedback check, and accept only a measured stale interval inside the process limit.

On this page
  1. Does WinCC OA support switchover on this redundant CPU?
  2. What is the difference between connecting to an H system and supporting switchover?
  3. What does the redundant-connection option do that an ordinary S7 connection does not?
  4. Can two ordinary connections to both CPUs replace a redundant connection?
  5. How do you measure what a switchover does to the HMI?
  6. What interruption can the process accept during a switchover?
  7. Which hardware should run the new SCADA client?
  8. WinCC or WinCC OA: which one should this line get?
  9. Questions asked

Switchover support is not something an HMI inherits from the controller. A redundant S7-400H keeps the process running when the primary CPU hands over, but the operator station still has to survive the handover on its own connection. WinCC OA is reported to support the H-PLC connection while lacking the vendor's redundant-connection option, RedConnect, for that system; WinCC and WinCC OA differ release by release, so the only capability you can defend is the one written in the driver documentation for your exact version and proven on a bench. This article separates connectivity from switchover capability, shows what the redundant-connection option does, gives the bench test with a changing value, alarm events and command feedback, and ends with the decision for each case.

Does WinCC OA support switchover on this redundant CPU? #

On the evidence available today, it connects but it does not switchover-proof: WinCC OA is reported to support the H-PLC connection while lacking RedConnect support for that H system, so plan the migration assuming the operator station reconnects after a handover rather than riding through it.

Treat that as a reported status from deployments, not a permanent specification, because capability moves with releases on both the SCADA side and the CPU firmware side. Before anything is ordered, get a statement from the vendor in writing for your exact driver version and CPU firmware that names the switchover mechanism, or names its absence. An entry in a compatibility list answers only the connectivity question, which is the same reason why an HMI terminal is not compatible with a PLC by brand alone matters here: a brand match and a list entry are not a feature statement.

What is the difference between connecting to an H system and supporting switchover? #

Connecting and surviving a handover are two different capabilities. A driver that lists the H-PLC can read and write whichever CPU is active; switchover support means the driver keeps or recovers that data path within a defined time when the standby CPU becomes primary.

The H system exists to keep control continuous, and it owes the operator station nothing. A line that runs straight through a handover is the redundancy working as designed, even while the operator picture sits on stale values, so a running process is not evidence that an HMI passed anything. Judge the replacement by its connection model: which endpoints it opens, how it detects that the active partner went away, and what it does next — reconnect, move to a second configured path, or wait for someone at the screen. The existing Wonderware platform's driver documentation describes that class of behavior in writing: its driver switches to the standby device when the active device fails to communicate and retries the failed path at slow poll. Find that sentence in the old system's documentation before it is retired, because a replacement that documents no equivalent mechanism silently removes a capability the plant already has.

What does the redundant-connection option do that an ordinary S7 connection does not? #

A redundant connection keeps one logical S7 link alive across the handover: with RedConnect-style support the client holds paths toward both CPUs and the takeover happens inside the driver, while with an ordinary connection the session drops and the new primary has to rebuild it from its side.

Siemens documents this rebuild pattern for its redundant R/H systems, and the matching clause for your controller lives in the H-system manual. The client-side consequence is an interruption whose length is set mostly by the driver's timeout, retry interval and resubscription time, not by the controllers. Connection behavior at a handover is specified per device class: a Comfort panel has its own documented redundant H system connection over Ethernet, a PC client with a driver option has another, and neither behavior transfers to the other as an assumption.

Can two ordinary connections to both CPUs replace a redundant connection? #

Only if the project defines who owns each value and each command: two independent connections can leave the client reading the standby CPU while writing the primary, or resending a command the controller already executed, so they are a design task and not a drop-in substitute.

If you take that route, write four things down before a screen is drawn: data ownership per tag, write routing, the failure-detection threshold for each path, and the recovery behavior when a path returns. Do not retry commands blindly after a reconnect — the command may have reached the controller before its acknowledgment was lost — so completion must come from application-level feedback such as a done-bit or a controller-side event, never from the driver's write result alone. A successful communication write is not proof that the requested process action happened.

How do you measure what a switchover does to the HMI? #

Run the handover on a bench and time four things: how long values stay stale, how many alarm events the gap touches, whether a command completes, and whether recovery stays recovered. Use a changing test value with timestamps, because a frozen plausible number is not evidence of a good link.

Condition to force What to record What the reading decides
Normal operation, no fault Changing value, its timestamp, data quality flags, connection state The baseline every later reading is judged against
Switchover, primary to standby, using the documented procedure Last good update time, first fresh update time, quality flags during the gap The measured stale interval that passes or fails against the supervision budget
Loss of one network path Whether updates continue and through which route Whether the network has a second path at all, independent of the controllers
Restoration of the failed part Connection state, update continuity, reconnect count Whether recovery settles instead of oscillating

Measure loss and recovery separately, with the driver's actual timeout, retry settings, data quality behavior and display update cadence in place, because those client settings contribute most of the number. A client that raises its connection alarm during a planned bench disconnect is behaving normally; the reading that matters is the measured recovery time, which is the situation behind why an HMI shows communication error popup 40001 on the bench.

Attribute every anomaly before changing configuration — driver, tag or screen, as laid out in is it the driver, the tag or the screen? diagnosing HMI values. Alarm events inside the gap cannot be reported by a client that was disconnected, so log them on the controller side and compare after recovery, using the counter's final value to measure catch-up. Test command completion on a nonhazardous write and compare the request with controller feedback. Force the switchover only on a bench system or under an approved commissioning plan with the documented switchover procedure, never by pulling power or network cables on an operating line.

What interruption can the process accept during a switchover? #

The limit is a process decision, so set it before testing; for example, allow the operator picture to be stale for at most 10 seconds per handover. Any driver whose measured stale interval stays under that budget passes; one that exceeds it needs the redundant-connection option or a redesign.

Worked example, with example inputs that are not vendor limits: the test tag is a PLC counter incremented every 1 second, and the supervision budget is 10 seconds. In a bench run, the last good update is timestamped 12:00:00 and the first fresh update after the handover arrives at 12:00:06, so the stale interval is 12:00:06 minus 12:00:00, which is 6 seconds. The pass rule is a measured stale interval no longer than the budget, so 6 seconds against a 10 second budget leaves 4 seconds of margin and this driver passes for data continuity. If a second run shows the first fresh update at 12:00:12, the stale interval is 12 seconds and misses the budget by 2 seconds, so that driver fails until the redundant-connection option, the reconnect timers or the network path change.

What moves the number: the driver's timeout and retry settings dominate on a flat bench network, resubscription adds its own delay, and every router between client and CPUs stretches the interval, which is why the measurement belongs on the hardware and topology you will actually deploy.

Which hardware should run the new SCADA client? #

The verdict above is about software, but the client still runs on a computer at the line, and a handover test is only valid on the hardware class you will deploy. Run the bench acceptance on the intended industrial panel PC, then roll that class out to the line.

A migration that retires the old operator station puts the WinCC or WinCC OA runtime on a touchscreen computer built for continuous duty in the cabinet, which is the job of industrial panel PCs. Match the configured runtime device version to the runtime installed on that panel, and verify host operating system support and license compatibility as checks separate from the driver's switchover capability. Whichever hardware class passes on the bench is the class that goes to the machine, so the measured stale intervals carry over.

WinCC or WinCC OA: which one should this line get? #

Pick the platform whose release documents the switchover capability your supervision limit requires. If the line cannot tolerate a stale interval, choose the WinCC configuration that documents a redundant H-system connection; if a budgeted interruption is acceptable, WinCC OA's connectivity plus a passed bench test is a defensible choice.

Capability Classic WinCC SCADA WinCC OA
H-PLC connection to the redundant CPU pair Documented in current releases; verify your release pair Reported as supported
Redundant S7-400H connection across a handover Historically positioned here as the RedConnect option; confirm the release pair in writing Reported as not available for the S7-400H
What the operator sees at a handover One logical connection maintained, when the option is licensed and configured Session drop, then driver reconnect to the new primary
Acceptance evidence Statement in writing for the release pair, then the bench measurement Statement in writing for the release pair, then the bench measurement
Project-level strengths Redundancy-first lines, multi-client SCADA architectures Custom look and feel, reusable objects, easier interfaces to other systems

The decisions, case by case:

  • Supervision must be continuous through a handover: require a documented redundant S7-400H connection in your exact SCADA release. On current reports that points to the classic WinCC environment, where adding a second redundant S7-400H system to WinCC SCADA is a documented pattern, and away from WinCC OA until the vendor states the option exists for your release.
  • The process accepts a budgeted stale interval: either platform qualifies after a passed bench test; configure data-quality indication on the screens, controller-side alarm buffering for the gap, and feedback-checked commands.
  • The old client's documented failover behavior is a requirement in its own right: the replacement must document an equivalent mechanism, or the migration removes a capability the plant already has.

The WinCC OA strengths in the table are genuine project-selection criteria, and none of them is switchover support.

Questions asked

What should I ask the vendor before ordering the new SCADA platform?

Ask for four things in writing: that the exact driver release connects to your S7-400H firmware; whether a redundant-connection option for that H system exists in that release and how it is licensed; the documented reconnect mechanism and what triggers it; and any switchover interruption the vendor has measured on its own test bench. Keep the replies as acceptance references.

What happens to the HMI connection at the instant the standby CPU takes over?

The running sessions drop and the new primary rebuilds them. Siemens documents this for the S7-1500R/H: the new primary re-establishes the connections the redundant system had successfully and actively established, so the client sees an interruption while that handshake runs. Read the H-system manual for your controller for the matching clause and size the client's reconnect timers against it.

Is the redundant-connection option a license I have to order separately?

Treat it as an ordering item of its own, not part of the SCADA base license. Confirm the option release matches both the SCADA release and the redundant CPU firmware, confirm the license covers every client that will hold the redundant connection, and verify activation on the runtime machine as a separate step before the bench test.

Does the same acceptance test apply if the operator station is a dedicated panel instead of a PC?

Yes, with the panel's own documentation. A panel-class station has its own H-system connection behavior and driver feature set, so request the capability statement for that exact panel model and firmware, then run the same bench measurement: a changing value with timestamps, controlled alarm events, a feedback-checked command, and the measured stale interval judged against the supervision budget.

Keep reading

  • Troubleshooting

    Comfort panel redundant H system connection over Ethernet

    A TP1900 Comfort panel cannot be configured in WinCC flexible, so the redundant connection to a 412-H station is engineered in the WinCC environment of TIA Portal: the panel talks to the active CPU over Ethernet, and a PROFINET media redundancy ring in client role protects the cable path. Accept the result with two separate tests: a controlled CPU changeover and a single-cable removal.

    HMI and touchscreens

  • How-to

    Running a V17 PLC project with WinCC Unified V18 HMI

    Yes: keep the validated PLC program in its TIA Portal V17 Update 6 project and engineer the HMI in a separate V18 project. Export the PLC proxy data, import it into the V18 project as a proxy device, and refresh that proxy data after every relevant PLC change. A Unified panel may also run a newer image than the version configured in engineering.

    HMI and touchscreens

  • Selection guide

    Which HMI replaces a K-TP 178 micro on an S7-200CN PLC

    The S7-200CN stays in service: it runs the same PPI protocol on its RS-485 port as every S7-200, so the discontinued K-TP 178 micro can be replaced by any HMI with a documented S7-200 PPI driver. Select on the driver, the serial port, V/M/I/Q addressing and your screen functions, and match baud rate and station address at both ends before commissioning.