WinCC redundant S7-1500 channel: SP1 and wizard limits

HMI and touchscreens Published 7 min read By IMDTouch engineering team

Short answer

The dynamic wizard builds redundant links for the S7-400 channel and lists no S7-1500 entries, so it can never make an S7-1500 redundant link. From WinCC V7.5 SP1 the S7-1500 channel serves an S7-1500R/H pair with one connection entry to the R/H CPU's IP address and follows the changeover itself. Two standard S7-1500 CPUs stay a script job: software redundancy that switches the partner address or access point.

On this page
  1. Why the dynamic wizard has no S7-1500 entry
  2. What V7.5 SP1 changes for an S7-1500R/H pair
  3. Configure the single connection to the R/H pair
  4. Two standard S7-1500 CPUs: script the switch
  5. The three redundancy layers side by side
  6. Worked example: counting what you maintain
  7. Verify the changeover before you trust it
  8. The decision for each case
  9. Questions asked

The dynamic wizard in WinCC V7.5 builds redundant links for the S7-400 channel, and it offers no S7-1500 channel entry at all — that is why your wizard list stays empty. It is a design boundary, not a missing option. From WinCC V7.5 SP1 the S7-1500 channel handles a redundant S7-1500R/H system on its own: you create one connection in tag management to the IP address of the S7-1500R/H CPU, and the channel follows the changeover between the two CPUs without a second link or a wizard run. A pair of standard S7-1500 CPUs that is not an R/H system stays a script job: software redundancy that switches the partner address or the access point when the active CPU fails. This page gives the version boundary, the configuration for both cases, and the decision for each.

Why the dynamic wizard has no S7-1500 entry #

The wizard's redundant-link function exists for a channel that needs two parallel connections at the HMI side. The classic setup is one WinCC V7.5 station talking to two S7-400 CPUs through a redundant link the wizard created and wired in one pass. The SIMATIC S7-1200, S7-1500 channel does not appear in that wizard on a V7.5 installation — there is no entry to select, so a wizard-built redundant S7-1500 link cannot be produced. Nothing is broken and nothing is hidden behind an option you have not found.

The reason is that the channel does not need the mechanism. From SP1 it absorbs the changeover itself, so there is no second link for a wizard to build. Keep the wizard for the S7-400 work it was built for and stop looking for an S7-1500 entry: it is not coming, and the single-connection path below replaces it.

What V7.5 SP1 changes for an S7-1500R/H pair #

As of WinCC V7.5 SP1, the S7-1500 channel supports a connection to the redundant system S7-1500R/H. The redundancy itself lives in the PLC project: configure the CPU redundancy completely in STEP 7 and the TIA Portal and load it to both CPUs. In WinCC you do exactly one thing — create the corresponding connection to the IP address of the S7-1500R/H CPU. No second connection, no mirror entry to the partner CPU, no wizard run. The channel and the communication layer under it follow the changeover, so runtime keeps receiving values from whichever CPU is active.

This single-connection path is also why WinCC carries no extra client-side redundancy software for this pairing; the companion article Why WinCC to an S7-1500R/H needs no S7-REDCONNECT walks through that reasoning.

The version boundary is hard: V7.5 without SP1 has no S7-1500R/H path in the channel, so the service pack is not an optional extra for this project.

Configure the single connection to the R/H pair #

  1. Finish the PLC side first. Configure the CPU redundancy fully in STEP 7 and the TIA Portal and download to both CPUs; if the redundancy is incomplete there, no WinCC setting repairs it.
  2. In WinCC, open tag management, select the SIMATIC S7-1200, S7-1500 channel and create one new connection. Enter the IP address of the S7-1500R/H CPU as the connection address — for the pair, that single entry is the whole WinCC configuration. The WinCC Information System documents this under the channel's configuration pages, in the redundant-system section.
  3. Attach your tags to that single connection and set the acquisition cycle each tag needs. Do not add a second connection to the partner CPU; the channel does not want one.
  4. Compile, start runtime and prove the changeover on a bench or in planned downtime: take the active CPU out of service and watch the tags continue from the partner CPU. Force changeovers only with the process stopped or on an isolated bench — never by dropping a CPU under a running line.

Two standard S7-1500 CPUs: script the switch #

An R/H pair is decided when the hardware is ordered. Once a machine runs two standard S7-1500 CPUs — mirrored programs or a shared process image on separate CPUs — the S7-1500 channel has no native multiplexing for them. The working pattern is the same software redundancy long used with standard S7-400 and S7-300 CPUs: keep the connection's endpoint parameters writable and switch them from a script when the active partner fails.

Two variants cover the field:

  • Address switching. Give each CPU its own address, for example 192.168.10.10 and 192.168.10.11, and have the script rewrite the connection's partner address to the standby CPU when the active connection reports failure.
  • Access point switching. When the two CPUs sit on two separate network interfaces at the station PC, point the connection at the access point bound to the interface that reaches the CPU you want. The access point is the PC-side interface assignment for the S7 protocol — the same assignment you set when mapping the protocol to a network card — so switching it moves the connection to the second path, which is also how media redundancy in the network gets exploited.

Trigger the switch on the connection status, not on a process tag value. Prove the endpoints first: set the standby address by hand, confirm both CPUs answer, then automate. Expect to adapt any published sample script — the switching targets, the partner address and the access point, are the documented mechanism, but the sample logic around them rarely fits a project unchanged.

The three redundancy layers side by side #

Redundancy in a WinCC project stacks in layers, and each layer is configured somewhere different:

Layer Protects against Where it is configured WinCC side of the work
S7-1500R/H CPU pair One PLC CPU failing STEP 7 / TIA Portal, finished before any HMI work One S7-1500 channel connection to the R/H CPU's IP address, from V7.5 SP1
Two standard S7-1500 CPUs One PLC CPU failing, on non-R/H hardware A script in your project Partner address or access point switched at runtime
Redundant WinCC servers The SCADA station itself failing WinCC Redundancy option Redundancy editor in WinCC Explorer, General tab: activate the Activate Redundancy check box

A Comfort panel at the same machine is a third client path again: the panel's HMI connection to the redundant system is configured in the TIA Portal project, not in WinCC — Comfort panel redundant H system connection over Ethernet covers how that panel-side connection behaves.

Server redundancy and CPU redundancy are independent: one WinCC server can run against an R/H pair, and two WinCC servers can run against a single CPU. Pick the layers your availability target actually names.

Worked example: counting what you maintain #

Take one WinCC V7.5 SP1 server on a line that today runs an S7-400H pair behind a wizard-built redundant link, migrating to S7-1500 hardware.

Case A — the plant buys an S7-1500R/H pair. Connection entries in WinCC: 1, the single connection to the R/H CPU's IP address. CPUs covered by that entry: 2. Wizard runs required: 0. One entry now serves two CPUs, because the channel takes over the pairing the wizard used to wire.

Case B — the plant keeps two standard CPUs at 192.168.10.10 and 192.168.10.11, example addresses. Connection endpoints: 2, one per CPU address. Switching scripts: 1. Objects you own and test: 2 + 1 = 3.

The arithmetic is the decision: both cases survive one CPU failure, but Case A costs one configuration entry and no code, while Case B costs three objects and a script you maintain for the life of the line.

Verify the changeover before you trust it #

Force the changeover on the bench with a fast counter tag on the connection and a timestamped log around the event. The gap between the last update from the old active CPU and the first from the new one is your acceptance number — the measured figure, in that plant, at those cycles. In WinCC's channel diagnosis, which lists each channel unit and its connection state, confirm the single connection is the only one involved: a second entry flapping during the changeover means a mirror connection was configured, and the channel wants it removed. For the script path, test all four states — A active, B active, only A alive, only B alive.

The decision for each case #

  • S7-1500R/H pair: install WinCC V7.5 SP1 or later, configure the redundancy in TIA Portal, create one connection to the R/H CPU's IP address, and skip the wizard entirely.
  • WinCC V7.5 without SP1: there is no S7-1500R/H path at that level — the service pack is the fix, not a configuration change.
  • Two standard S7-1500 CPUs: no wizard entry exists for the S7-1500 channel in WinCC V7.5; build the software-redundancy switch of partner address or access point in a script, triggered on connection status.
  • Existing S7-400H wizard links: leave them alone — the wizard-built redundant link remains the S7-400 channel's mechanism.

Questions asked

Does the S7-1500 redundant connection need an extra license or add-on?

No extra add-on is documented for it: from WinCC V7.5 SP1 the connection to an S7-1500R/H system is part of the S7-1500 channel's documented behavior, reached with a single connection entry. The separate product is the WinCC Redundancy option, and that one duplicates the WinCC servers themselves rather than the CPU pair. Confirm the installed service pack first, because V7.5 without SP1 has no S7-1500R/H path at all.

Can I use the dynamic wizard after installing SP1?

No. The wizard still lists no S7-1500 channel entry after SP1, and with SP1 you do not need it: a single connection to the IP address of the S7-1500R/H CPU covers the pair and the channel follows the changeover itself. The wizard keeps its own job, building redundant links for the S7-400 channel, and an existing wizard-built S7-400 link keeps working unchanged.

What exactly do I switch in the script for two standard S7-1500 CPUs?

One of two endpoint parameters: the connection's partner address, rewritten to the standby CPU's IP, or the access point the connection uses, which moves the connection to the network interface that reaches the standby CPU. Trigger the switch on the connection failure status, prove both endpoints answer by switching the parameter by hand first, and adapt any sample script's tag names and trigger to your project before trusting it.

How long do tags pause during a changeover?

The changeover runs below the application and your single connection entry stays in place, so the question is how long values pause, not whether the link survives. Put a fast counter tag on the connection, force the changeover on a bench, and log timestamps around it: the gap between the last update from the old active CPU and the first from the new one is your acceptance number for that plant.

Does a Comfort panel at the same machine use this configuration?

No, a Comfort panel is configured in the TIA Portal project with its own HMI connection to the redundant system, not in WinCC's tag management and not through the wizard. It follows the same one-connection principle on the panel side, with no script involved. The panel-side behavior over Ethernet is covered by the companion article on Comfort panel redundant H system connection.

Keep reading

  • Explainer

    Why an S7-1200 runs out of HMI connection resources

    The V3.0 CPU 1214 in this case reserves six HMI connection resources and cannot be upgraded to V4.x firmware, which belongs to a different hardware generation. Six panels plus the two connections WinCC 7.2 runtime opens need eight resources, two more than the CPU has: audit the WinCC project for a duplicate connection, then either move a panel off the CPU or fit a V4.x-generation CPU with twelve reserved HMI connections.

    HMI and touchscreens

  • Explainer

    Why WinCC cannot switch PLC connection IP at runtime

    No WinCC edition exposes a script function that re-points a configured PLC connection to a new IP while the runtime runs. Engineer the switchover into the project: software redundancy in the S7-300 pair with WinCC following the master status, a tag-prefix switch between two tag sets, or a preconfigured alternative connection whose recovery interval you measure on the bench.

    HMI and touchscreens

  • How-to

    Keeping WinCC on S7-1500 furnaces when a supplier pushes its own SCADA

    Keep WinCC as a written requirement in the purchase specification, with the edition, the license owner and the source-project deliverables named. Give the S7-1500 a symbolic interface over OPC UA so the SCADA stays replaceable without PUT/GET access. Accept a supplier-built platform only when it passes written documentation, reference and license checks.