Comparison
WinCC HMI Panels Compared by Their System Limits
Short answer
Compare Basic Panels, Comfort Panels, Unified Comfort Panels and Runtime Advanced by running your project's five counted demands, tags, screens, alarms, recipes and logging volume, against each family's documented limit tables. One exceeded maximum eliminates a candidate; the smallest passing row wins; when no panel row passes, a PC runtime sized by license and hardware is the answer.
On this page
- Which WinCC HMI devices am I choosing between?
- Where do I find the system limits for each WinCC panel family?
- Which numbers do I count in my own project first?
- How else do Basic, Comfort, Unified Comfort and Runtime Advanced differ?
- What does the comparison look like on a real project?
- Which family does the comparison pick for my machine?
- When does the answer become a PC instead of a panel?
- Which engineering software does each family need?
- Questions asked
Select a WinCC HMI device by its documented system limits, not by which family sounds more capable. The four choices are Basic Panels, Comfort Panels, Unified Comfort Panels and Runtime Advanced on a PC; each takes its maxima from a different document, and only the counts in your own project decide between them. This article names the tables to open, shows which five demands to count from the project, walks one worked example through the arithmetic, and ends with the decision rule: one exceeded maximum eliminates a candidate, the smallest row that passes everything is the hardware to buy, and a PC runtime is the answer when no panel row passes.
Which WinCC HMI devices am I choosing between? #
Four device families carry WinCC projects at the machine: Basic Panels for small single-machine visualization, Comfort Panels for the full classic function set, Unified Comfort Panels as the successor family with a web runtime, and Runtime Advanced running on a PC.
Each name describes a runtime as much as a screen. Basic Panels and Comfort Panels are closed devices with onboard runtime, Runtime Advanced is software running on PC hardware, and Unified Comfort Panels are closed devices whose runtime serves web clients. The vendor's migration guide states the lineage plainly: Unified Comfort Panels follow the previous Comfort Panels, and Unified Basic Panels follow the previous second-generation Basic Panels, so a replacement plan that begins with an existing terminal usually lands in the Unified line.
All four are engineered in the TIA Portal environment, but not all with the same product: Basic and Comfort projects use the classic WinCC engineering products, and Unified targets need WinCC Unified engineering. The full mapping of engineering tools to panel hardware is set out in the article on which HMI software works with which HMI panel hardware. If the decision is not yet narrowed to WinCC hardware at all, read the comparison of industrial HMI device types and how to choose between them first.
Where do I find the system limits for each WinCC panel family? #
Each family publishes its maxima in a different set of tables, so the comparison begins by opening three documents: the classic system-limit tables for Basic and Comfort Panels, the performance-feature tables for Unified Comfort Panels, and the runtime license specification for Runtime Advanced.
The Comfort Panel documentation says its tables of system limits exist so you can assess whether a project conforms to the limits of a given HMI device, model by model, and the Unified Comfort operating instructions, Siemens support entry 109773257, carry the same kind of performance-feature tables for the Unified line. Open the set that matches the documentation version of your installed engineering software, because maxima are revised between generations and a row copied from the wrong version selects the wrong panel.
Runtime Advanced has no fixed device table to read: its ceiling is the PC hardware plus the installed runtime license tier, and the per-device variable limit is checked in the engineering tool itself, as shown in the article on PowerTags versus the variables-per-device limit in TIA Portal HMI.
Which numbers do I count in my own project first? #
Count five demands from the real project or the legacy export before any table is opened: tags, screens, alarms, recipes and logging volume, because those are the columns the limit tables compare.
- Tags: sum the external tags exchanged with the controller and the internal memory tags, because both consume the runtime's tag capacity.
- Screens: count every screen the project compiles, including diagnostic and system screens, not only the process views an operator opens.
- Alarms: add discrete and analog alarms together, both the ones arriving from the controller and the ones configured in the project.
- Recipes: record the number of recipes and the records the largest one holds; the largest recipe is the number the table cares about.
- Logging: multiply logged tags by sample rate, bytes per sample and retention; this demand decides archive size and, more often than any other column, panel versus PC.
How else do Basic, Comfort, Unified Comfort and Runtime Advanced differ? #
Passing the limits check leaves real differences: Unified Comfort Panels run a web-based runtime and ship with one Client Operate and one Client Monitor on board, Comfort Panels carry the classic runtime's full function set, Basic Panels stay capped at machine-level tasks, and Runtime Advanced scales with its PC.
Unified Comfort Panels are also the family with a published size span for this comparison, documented from 7 up to 21.5 inches; Basic and Comfort ranges are published per model, so the exact model number, not the family name, is what a table row belongs to.
| Property | Basic Panels | Comfort Panels | Unified Comfort Panels | Runtime Advanced (PC) |
|---|---|---|---|---|
| Runtime at the machine | WinCC Basic | Classic WinCC runtime | WinCC Unified, web clients | WinCC Runtime Advanced |
| Engineering product | WinCC Basic in TIA Portal | WinCC Comfort or WinCC Advanced in TIA Portal | WinCC Unified in TIA Portal | WinCC Advanced in TIA Portal |
| Limits documented as | Per-model system-limit table | Per-model system-limit table | Per-model performance-feature table | PC hardware plus runtime license tier |
| Documented size span | Published per model | Published per model | 7 to 21.5 inches | Any display the PC drives |
| Succession | Succeeded by Unified Basic Panels | Succeeded by Unified Comfort Panels | Current Unified family | PC option, outside that succession |
What does the comparison look like on a real project? #
A worked example makes the method concrete: take a mid-size bottling-machine retrofit whose legacy runtime exports 1,150 external tags and whose rebuild adds 300 internal tags for HMI-side calculations and trends.
- Tags: 1,150 external + 300 internal = 1,450 tags the runtime must serve.
- Screens: 34 process and diagnostic screens + 4 system screens = 38 screens compiled into the project.
- Alarms: 265 discrete + 155 analog = 420 alarms the runtime must manage.
- Recipes: 6 recipes, the largest holding 250 data records; the largest recipe is the checked number.
- Logging: 180 tags logged at 1 sample per second gives 180 × 86,400 seconds per day = 15,552,000 samples per day. At an assumed 8 bytes per sample, an example figure since the project's tag data types set the real size, that is 15,552,000 × 8 = 124,416,000 bytes, roughly 124 MB per day. Retaining 30 days requires 124,416,000 × 30 = 3,732,480,000 bytes, about 3.7 GB of archive capacity.
Those five numbers are the whole demand side. The supply side is read from each candidate family's table, in the documentation version that matches the installed engineering software.
Which family does the comparison pick for my machine? #
The elimination rule is absolute: if one demand exceeds a candidate's documented maximum, that candidate is out, and spare screens do not pay for missing tag capacity.
- Basic Panel: the answer when a row covers all five demands; it serves a single machine with no web clients and keeps the smallest engineering product.
- Comfort Panel: the answer when the Basic rows fail or the application needs the classic function set; take the smallest Comfort size whose full row passes 1,450 tags, 38 screens, 420 alarms and the logging demand.
- Unified Comfort Panel: the answer when the project migrates from a Comfort terminal or needs web clients; check the Unified performance-feature table for the exact size inside the documented span, never the classic Comfort table.
- Runtime Advanced on a PC: the answer when no panel row passes. In the bottling retrofit the binding demand is the archive: if the chosen panel row's logging capacity falls below the 3.7 GB the 30-day retention needs, a PC runtime ends the search, because its archive lives on PC storage you size yourself.
If any alarm backs an operator action that guards the machine, treat the alarm column as the first one checked and never substitute a row that carries fewer of them. Before any hardware is ordered, confirm that the workstation's engineering software supports the chosen target; that pre-order check is exactly what the guide to checking HMI engineering software before a panel replacement walks through.
When does the answer become a PC instead of a panel? #
Three findings push the project off panels: a demand no panel row covers, a need for more simultaneous operate clients than the included pair, and an architecture that already puts a computer at the machine.
Runtime Advanced and a Unified PC runtime both make the license part of the selection: the license tier sets how many variables the runtime serves, the PC sets storage and speed, and the two are specified together. When the comparison lands there, the hardware to specify is one of the industrial panel PCs: a touchscreen computer built for cabinet-door mounting that runs the runtime next to the machine.
Which engineering software does each family need? #
Each family checks out against a different engineering product, and the version on your workstation must list the exact panel model, so verify the tool, the target model and the firmware as three separate checks.
Basic, Comfort and Runtime Advanced targets are configured with the classic WinCC engineering products in TIA Portal; Unified Comfort Panels are configured with WinCC Unified engineering, and the engineering version has to know the panel. An older engineering version can report zero compatible Unified Comfort devices even though the hardware is current, as traced in the article on why TIA Portal V20 finds 0 compatible Unified Comfort panels, so match the engineering version to the panel generation before promising a model. If the device catalog shows no entry for the panel at all, the engineering product or version is wrong rather than the hardware, which is the situation the article on an HMI model missing from the programming software resolves. Unified panels receive operating-system updates as complete images, and a mixed fleet can need two image versions side by side, the case the article on Unified Comfort Panel image updates when two versions are needed lays out, so treat firmware as part of the selection.
Questions asked
Is there one official spreadsheet comparing every WinCC HMI device?
No single all-devices spreadsheet is published. The vendor keeps per-family performance-feature tables: classic system-limit tables for Basic and Comfort Panels, separate performance-feature tables for the Unified Comfort Panels, and a license specification for Runtime Advanced. Build your own comparison sheet from those documents and record the document name, version and publication date beside every number you copy, so the selection stays traceable when a generation revision moves a limit.
Can a Comfort Panel project be moved to a Unified Comfort Panel directly?
Not by a simple device swap. Unified Comfort is a different runtime, so the vendor publishes a dedicated migration guide and the project goes through that migration path before it compiles for the new target. Expect screens, scripts and archives to be converted rather than reused untouched, and plan bench time to retest alarm behavior and logging after the migration.
How many remote clients can connect to a Unified Comfort Panel at once?
Each Unified Comfort Panel includes one Client Operate and one Client Monitor, so one full-operation client and one monitoring client are on board before anything is added. Additional clients are enabled by adding client licenses. Count the simultaneous operators and viewing stations first, then size the license count to that number rather than to the panel size.
What fails first when a project exceeds a panel's documented limit?
The engineering system stops the project at compile or download instead of letting an oversized project reach the panel, so the failure appears on the engineering workstation first. When it does, cut the demand, with fewer internal tags or a slower logging rate, reassign the project to a larger model row in the same family, or move it to Runtime Advanced on a PC where the license tier sets the ceiling.
Does a larger screen size within one family carry higher system limits?
Limits are published per model, so treat every size as its own table row and verify that exact model instead of assuming the biggest display carries the family's best limits. Choose the diagonal for the operator interface, viewing distance and cut-out first, then confirm the chosen model's row against the counted project demands; if the row fails, step up within the family or move the project to a PC runtime.