Explainer
Secure mode password protection for an HMI control panel
Short answer
Switch on Secure Mode in the panel's Control Panel and give it a password: from the next restart the Control Panel opens only with that password, so operators cannot change settings or passwords. Before adding an option package such as SIMATIC HMI Option+, match its documented engineering-version requirement — TIA Portal V15 — to the tool you actually run; a project configured in WinCC Comfort V11 does not qualify the panel.
On this page
- How do you stop operators opening the panel Control Panel after a restart?
- What does Secure Mode actually lock, and what does it leave open?
- How do you set the Secure Mode password on the panel?
- What happens if the Secure Mode password is lost?
- Does a working WinCC Comfort V11 project prove the panel accepts SIMATIC HMI Option+?
- What do you check before transferring an HMI option package to this panel?
- Can the option and the password lock go on the same panel, and in what order?
- Questions asked
Two separate questions sit behind this panel: keeping operators out of the device-level Control Panel after every restart, and whether the SIMATIC HMI Option+ package can go onto a TP700 Comfort that was configured with WinCC Comfort V11. The answers are a device setting and a version check. Secure Mode in the panel's Control Panel, with a password assigned, blocks Control Panel access after restart while leaving the running screens untouched. Option+ is a different matter: its specification requires TIA Portal V15, and a V11 station does not meet it, so the option route runs through the required engineering version, not through the panel that already transfers cleanly. This article gives the setting, the order of work, the worked version check and the decision for each case.
How do you stop operators opening the panel Control Panel after a restart? #
You enable Secure Mode in the panel's own Control Panel and assign a password there; from the following restart the panel demands that password before the Control Panel opens, so operators keep running the screens while losing access to settings, network data and password management. The Control Panel is the panel's device layer, reachable again after every boot, which is why a lock that lives only in the runtime session does not survive a restart.
Secure Mode is stored on the panel, so the prompt returns after each restart without anyone re-entering anything, and it guards the whole entry rather than individual dialogs: a user with the password sees everything in the Control Panel, a user without it sees none of it. That closes the case that matters here — an operator restarting the terminal at shift start cannot reach the network parameters, the transfer settings or the panel's own user management. What the same operator can do inside the running screens is a separate question, taken up next.
What does Secure Mode actually lock, and what does it leave open? #
Secure Mode locks the panel's Control Panel — the device-level layer holding network, transfer and security settings — and it does not lock anything your HMI project exposes in runtime, so recipe edits, screen navigation and project user accounts stay governed by the project's own user management.
The split matters because the two layers answer different fears. If the fear is an operator opening the Control Panel and changing the panel's addresses, transfer mode or passwords, Secure Mode is the whole answer. If the fear is an operator editing a recipe or writing to a tag from a screen, Secure Mode does nothing: those actions sit inside the project and are controlled by the users and groups the project defines. Most machines need both layers locked, with different passwords and both records kept. Match the fix to the fear: panel settings and panel passwords go to Secure Mode, tags and recipes go to the project's user management.
How do you set the Secure Mode password on the panel? #
Open the panel's Control Panel, go to the settings area that handles security, switch Secure Mode on, and enter the password twice; the change applies on the device itself and needs no re-transfer of the project from the engineering station.
Reach the Control Panel from the running screens through the panel's own access to it — the same entry that will later ask for the password. Enter the password, confirm it and apply, and hold it to your site's credential rules for length and storage: the panel enforces whatever its security dialog asks, and your rules should not be looser. Do the whole sequence on the bench before the panel returns to service, and run the restart test there. Nothing in the sequence touches the project file, so there is nothing to transfer afterwards and no version question to settle.
What happens if the Secure Mode password is lost? #
Nothing in the panel's settings recovers a lost Secure Mode password, so the credential goes into the site's password store the day you set it; if it is lost anyway, the way back is the vendor's documented service path, not anything reachable from the Control Panel.
That service path works outside the panel's settings and typically ends with the panel reloaded, so plan to set the panel's settings and the project up again afterwards. The vendor-documented route for a panel with no stored backup is the one described in Recovering access to a password-protected HMI panel without a backup. Give at least two people per shift a way to produce the password: a machine whose settings cannot be reopened invites improvised changes on live equipment.
Does a working WinCC Comfort V11 project prove the panel accepts SIMATIC HMI Option+? #
No: the Option+ specification requires TIA Portal V15, and the version that configured the panel is not the version the option is validated against, so a clean V11 transfer proves nothing about whether this option runs on this panel.
The evidence that decides the option question is the option's own documentation, not the project's transfer history. Siemens documents SIMATIC HMI Option+ under support entry 109754400 as a package that adds functions to SIMATIC industrial PCs and Comfort Panels, and states the engineering version the option requires. The project that already transfers cleanly was built without the option, so its clean record is not evidence about the option's requirements. This is the same tool, target and firmware separation applied when checking HMI engineering software before a panel replacement: the engineering tool, the target model and the firmware each get their own check, and the tool check comes first because it gates the other two. The specification's version requirement covers the option workflow, so the older station is outside it regardless of what the panel itself accepts.
What do you check before transferring an HMI option package to this panel? #
Check four things in order — the option's documented engineering-version requirement, the panel's ordering number in that version's device catalog, the panel's installed firmware against the option's stated range, and a bench transfer — and only the panel that passes all four gets the option.
Worked check for the case this article answers; the version figures and the ordering number are documented inputs, the firmware is left untested here because the tool question fails first:
| Input | This case | Decision the row forces |
|---|---|---|
| Option's documented engineering version | TIA Portal V15 | the workflow must run in this version |
| Engineering station in use | WinCC Comfort V11 | 15 - 11 = 4 major versions short; the check fails here |
| Panel ordering number in the required catalog | 6AV2 124-0GC01-0AX0 | confirm before any transfer |
| Panel firmware | untested here | compare with the option's stated range once the tool passes |
The arithmetic is the whole verdict: the installed version sits 4 major versions below the requirement, so the workflow fails at the first input and the firmware and transfer steps never come into play. Do not produce or transfer the option from the V11 station.
Moving the option work to the required engineering version means that version installed with its HMI components present. If the newer TIA Portal shows no HMI option at all, the install is missing the HMI engineering component, and the fix is in TIA Portal shows no HMI option: install WinCC Engineering. Reselect the exact ordering number in that version's device catalog: if it is not offered, the option route for this panel ends there; if it is offered, compare the firmware with the option's stated range and finish on the bench.
Can the option and the password lock go on the same panel, and in what order? #
Yes, and the order is: settle the engineering-version question first, transfer and bench-test the option, then enable Secure Mode as the last step, because a panel whose settings you cannot reach is a harder panel to rework if the option misbehaves.
Secure Mode is a device setting applied from the panel itself, so it does not depend on the project or the option and can be applied after everything else. Work the sequence in this order:
- Settle the engineering-version question and, if it fails, move the option work to the tool version the specification requires.
- Transfer and test the option functions on the bench, with the project and firmware in their final state.
- Enable Secure Mode, set the password, and put it in the site credential store.
- Restart twice: confirm the prompt appears and a wrong password is refused, then confirm the project starts on its own.
- Return the panel to the machine only then.
The decisions, one line each. To stop operators changing panel settings or passwords after a restart, enable Secure Mode and assign the password, and do it on the bench first. To put SIMATIC HMI Option+ on this TP700 Comfort, first move the option workflow to the engineering version its specification requires — a transfer attempted from the old station is outside the option's specification even though the base project transfers cleanly. If the required catalog does not list the ordering number 6AV2 124-0GC01-0AX0, the option route for this panel is closed and the functions the option promises stay off this machine.
Questions asked
Does SIMATIC HMI Option+ work with WinCC Comfort V11?
The option's specification requires TIA Portal V15, so a V11-only station is outside it. Plan the option workflow in the required engineering version, reselect the panel's ordering number in that version's device catalog, and only then handle firmware and a bench transfer. If the documentation for a specific Option+ function states otherwise, that statement governs.
What exactly gets stored on the panel when I set the Secure Mode password?
The setting and its password are stored on the panel itself, which is why the prompt returns after every restart and why the project file on the engineering PC neither contains nor restores it. Treat the panel as the only place the lock lives, and keep the password recorded outside it.
How do you test the lock before the panel returns to the machine?
On the bench, restart twice and write down both results: the Control Panel must ask for the password and refuse a wrong entry, and the second start must bring the project up on its own with the screens running. A lock that also blocks the process is a fault to fix, not a security win, so keep the panel on the bench until both lines read pass.
Does a project transfer remove the Secure Mode lock?
A project transfer does not remove the lock, because it lives in the panel's device settings rather than in the project file. After any re-transfer, restart once and confirm the Control Panel still asks for the password before the panel goes back into production.