Keyboard-only WinCC 7.0 Runtime operation needs TAB Sequence

HMI and touchscreens Published 5 min read

Short answer

WinCC 7.0 Runtime runs without a mouse once each screen has a TAB Sequence configured in Graphics Designer: the object types are enabled for tabbing, the focus order is set across the setpoint fields and command buttons, and the sequence is tested online. Arrow-key behavior identical to an older HMI is not part of that guarantee and must be verified separately per screen.

On this page
  1. How does WinCC 7.0 Runtime support operation without a mouse?
  2. Where is the tab order configured in Graphics Designer?
  3. How do you set the sequence across setpoint fields and START/STOP buttons?
  4. How many Tab presses does one operator round trip take?
  5. Will the arrow keys behave like the previous HMI?
  6. What does the runtime acceptance test prove?
  7. Questions asked

Operators coming from an older HMI expect to select a feed location, type a setpoint and press START without touching a mouse. In WinCC 7.0 that works, but not by default and not through the arrow keys: the mechanism is the TAB Sequence of each screen, configured in Graphics Designer before the Runtime test. This article gives the configuration path, a worked press count and the acceptance test that proves it.

How does WinCC 7.0 Runtime support operation without a mouse? #

Keyboard-only operation of WinCC 7.0 Runtime is configured per screen through the TAB Sequence in Graphics Designer, and a migrated station was proven to run without a mouse once that sequence was in place. The Tab key moves keyboard focus from one selectable object to the next, in the order you defined, so the operator walks the screen with Tab and operates each focused object from the keyboard. What this does not deliver is automatic equivalence with the old HMI's up, down, left and right arrow navigation; that is a separate question, answered below.

Where is the tab order configured in Graphics Designer? #

The tab order lives in Graphics Designer under the Edit menu: TAB Sequence, where you first choose which object types take part and then define the order in which keyboard focus moves across the screen. The workflow has two parts. First, open the settings through Edit / TAB Sequence / Tab Order and, in the Object Types dialog, activate the object types that may receive focus on this screen. Second, edit the sequence itself in Graphics Designer and click the participating objects in the order the operator needs. Screens edited this way are stored as picture files, and each picture carries its own sequence.

How do you set the sequence across setpoint fields and START/STOP buttons? #

A workable order puts the objects in the sequence the operator physically walks through: location selector first, setpoint field second, command buttons last, so one Tab press advances one step of the task. Do it in this order:

  1. Open the Runtime picture in Graphics Designer and list every object an operator must reach: I/O location selectors, setpoint entry fields and the START/STOP buttons. Anything left out of this list is unreachable by Tab, so write the list from the production workflow, not from the screen layout.
  2. Open Edit / TAB Sequence / Tab Order, choose Settings, and activate the object types from your list in the Object Types dialog.
  3. Edit the sequence by clicking the participating objects in workflow order: all location selectors and their setpoint fields in the sequence the operators feed material, then the command buttons.
  4. Save the picture and start Runtime with the keyboard only. Step through the whole sequence once with Tab before any value entry, and note any object that never receives focus.
  5. When a focused field must change a value by key presses instead of typed text, the function-key increment pattern in select a value by touch and change it with HMI function keys is the approach to reuse on the entry fields.
  6. Repeat steps 1 to 4 for every migrated picture; the sequence does not propagate between screens.

One safety note: run the first keyboard-only test against test tags or an isolated bench, because a misplaced Tab order can put a START button one press away from a setpoint field on a live line.

How many Tab presses does one operator round trip take? #

Count the Tab presses from the sequence itself: each press advances exactly one position, and after the last object in the sequence the focus returns to the first object of that screen. Take an example screen with eight tab stops in workflow order: positions 1 to 3 are three feed-point selectors, positions 4 to 6 their setpoint fields, position 7 the START button and position 8 the STOP button. The operator needs feed point B with a setpoint of 6500 kg, which sits inside the supported entry range of 40 to 7000 kg.

  • Focus begins on position 1. Reaching selector B at position 3 takes 3 − 1 = 2 presses.
  • Reaching setpoint field B at position 4 takes 1 more press; the operator types 6500 and confirms.
  • Reaching START at position 7 takes 7 − 4 = 3 presses.

The round trip costs 2 + 1 + 3 = 6 presses, and a full cycle back to position 1 costs 8. If that count is too long for the takt time, interleave the sequence per feed point (selector, field, buttons) rather than grouping all selectors first, which cuts the worst trip on this screen to 4 presses. Do the same arithmetic on your real screen before you accept it, not after.

Will the arrow keys behave like the previous HMI? #

Arrow-key navigation identical to the previous HMI is not guaranteed by the TAB Sequence; the confirmed result is keyboard-only operation through Tab focus, so the four arrow keys are a separate item to test. During the online test, press up, down, left and right on a focused selector and record what each key actually does on that screen. If the old pattern appears, document it as verified behavior for that screen only. If it does not appear, commit to Tab-plus-entry as the operating method and train the operators on it, rather than promising arrow parity that the configuration does not provide.

What does the runtime acceptance test prove? #

The acceptance test passes when an operator completes the full production workflow on every migrated screen with the keyboard alone: no skipped object, no trapped focus, and the command controls reachable last. Run it like this:

  1. On the isolated bench, navigate with Tab only to each feed-point selector and confirm focus lands visibly on every one.
  2. Enter setpoints at both ends of the supported range, 40 kg and 7000 kg, plus a mid value, and confirm the written tag value each time.
  3. Reach the START and STOP buttons by Tab and activate them from the keyboard while watching the PLC tags they write.
  4. Reject the screen if focus skips an object, wraps before the command buttons, or lands on the command buttons ahead of the setpoint fields.
  5. Record the pass per screen, including the arrow-key observations, and repeat the whole test after any later edit to that picture.

The decision: configure the TAB Sequence on every screen, accept each screen on the keyboard-only test above, and treat arrow-key behavior as verified per screen or not offered. That is the complete, documented path to mouseless WinCC 7.0 Runtime operation.

Questions asked

Is the tab sequence configured once for the whole WinCC project?

No. The TAB Sequence belongs to the individual screen picture edited in Graphics Designer, so a station with twelve migrated pictures needs twelve sequences and twelve online tests. A copied screen carries its own order with it; a newly drawn screen has none until you define it.

Does the WinCC on-screen monitor keyboard replace the physical keyboard here?

No. The monitor keyboard is a separate on-screen keyboard option, and it is not part of this fix. The TAB Sequence only orders where keyboard focus goes for a physical keyboard; it does not draw keys on the screen and does not require the monitor keyboard to be enabled.

Can a START or STOP button be operated once it holds keyboard focus?

That is confirmed in the online test, not assumed: the tab sequence documentation covers the focus order, not the activation key of every object type. Press the activation key on the focused button while watching the PLC tag it writes, and only accept the screen when the write happens without the mouse.

What do I record for the arrow keys after the acceptance test?

Record, per screen, what each of the four arrow keys actually did during the test: moved focus, moved within a field, or did nothing. If the old arrow-key behavior is mandatory and the test shows it is missing, budget explicit per-key configuration or operator retraining instead of promising parity from the TAB Sequence.

Keep reading

  • How-to

    Running a WinCC 7.0 project on another PC without a new build

    No. WinCC has no compile-to-EXE option: the destination PC needs WinCC Runtime of version 7.0 or higher, installed and licensed, and you transfer the project files to it. A newer WinCC opens and converts the project; an older release will not open it.

    HMI and touchscreens

  • Troubleshooting

    TP177B color PN/DP OS update fails: version set and image fix

    The transfer is refused because the project, the engineering version and the panel image are not a compatible set. Install Hotfix 7 for WinCC flexible 2005 SP1, which supplies the TP177B image and downgrades the panel to it, or keep the panel's newer version with at least WinCC flexible 2008 SP1; then convert the project from TP177B mono to TP177B color PN/DP and transfer over MPI.

    HMI and touchscreens

  • Troubleshooting

    What WinCC V11 needs to run a PC as an HMI

    WinCC V11 Professional in TIA Portal configures and downloads HMI projects; it does not make the PC a runtime station by itself. To run the PC as an HMI you install WinCC Runtime Advanced for panel-class projects or WinCC RT Professional for SCADA, each on its own runtime license. When the Advanced setup stops at the Sebu_winccv11 check, the image carries classic SIMATIC packages the V11 SP2 compatibility list does not clear, so clean the machine and reinstall.