Troubleshooting
PanelView Plus 7 ping times out while RSLinx connects
Short answer
A ping timeout on a PanelView Plus 7 that still accepts transfers and appears in RSLinx usually means the terminal's ICMP echo response is disabled in Windows CE, not that the cable or IP settings are wrong. Confirm one current RSLinx transaction and the subnet against the terminal's own address, exit the ME runtime, and enable the ping response there.
On this page
- Why does a PanelView Plus 7 answer RSLinx but time out on ping?
- Is the RSLinx icon proof the terminal is reachable right now?
- Which checks confirm the cable and addresses before you change the terminal?
- Example: do 192.168.1.10 and 192.168.1.100 share a subnet on the bench cable?
- Where is the ping-response setting, and how do you reach it safely?
- Which observation decides what you fix first?
- How do you verify the fix without breaking the application?
- Questions asked
Your PanelView Plus 7 loads an application and shows up in RSLinx, yet ping from the laptop times out. That split usually means the terminal's ping response is switched off in Windows CE, not that the cable or the address is wrong: the application path and the echo path are different services, and this terminal can serve one while ignoring the other. Confirm a current transaction first, because a stale RSLinx icon and a disabled echo reply look identical from the laptop. Then exit the runtime, enable the response, and verify with the same ping that failed.
Why does a PanelView Plus 7 answer RSLinx but time out on ping? #
Ping and application traffic are different services: ping sends ICMP echo requests, while RSLinx browsing and application transfer run on their own TCP/IP exchanges, so the terminal can accept a download and still drop every echo request.
RFC 792 defines the echo request and the echo reply as ICMP message types in their own right, separate from the TCP and UDP traffic a transfer service uses. When the terminal's echo response is disabled, the request still arrives, the network stack declines to answer, and no reply travels back; Command Prompt reports a timeout on every attempt even though another service at the same address is healthy.
The off switch exists on purpose: a terminal that never answers echo traffic stays out of ICMP-based network mapping and the echo flooding examined in an ICMP echo flood packet analysis.
Keep three layers apart while you test. The physical link is the two Ethernet interfaces agreeing on a connection. The IP path is the laptop sending toward the right address out the right interface. The service response is the terminal answering the specific traffic you sent. Link lights cover the first layer, a fresh transfer proves its own service path, and ping tests only echo behavior; none of the three replaces another.
Is the RSLinx icon proof the terminal is reachable right now? #
No: when the browse display is not auto-refreshing, RSLinx keeps previously discovered terminals on screen without the disconnected marker, so an icon proves the terminal was seen at some point, not that packets reach it now.
Treat the icon as a record, not a measurement. Run a current operation to the address: repeat the transfer on the bench, or on a running machine open a live read-only session through the engineering software instead of downloading. Record whether that operation succeeds; that result, not the icon, is your evidence of present connectivity, and it decides which row of the fault table below applies.
Which checks confirm the cable and addresses before you change the terminal? #
Five checks settle the path in a few minutes: read the address from the terminal's own configuration screen, match the laptop adapter with ipconfig, confirm both hosts share one subnet, inspect route selection with route print, then run ping against that exact address.
- Read the terminal's IP address and subnet mask from its own network configuration screen, not from an old printout or a laptop note.
- Run
ipconfigon the laptop and pick out the adapter the bench cable is plugged into; ignore the other adapters for now. - Compare the two addresses under their masks; a direct cable needs both hosts in one subnet, and the example below shows the arithmetic.
- Run
route printif the laptop also has Wi-Fi, VPN or virtual adapters active; an overlapping network pulls the echo request out the wrong interface. - Run
pingwith the exact address from step 1; testing a different address makes every later observation misleading.
If a fresh transfer succeeds through this same cable and address, stop treating the cable as the suspect. Swapping cables, re-addressing the terminal or reinstalling communication software burns the outage window when the only thing missing is the echo reply.
Example: do 192.168.1.10 and 192.168.1.100 share a subnet on the bench cable? #
Yes: masking both addresses with the terminal's 255.255.255.0 mask leaves 192.168.1.0 for each, so the direct connection is valid at the IP layer and the timeout is not an addressing fault.
The inputs, both read rather than assumed:
- Terminal configuration screen: 192.168.1.10, mask 255.255.255.0.
- Laptop bench adapter from
ipconfig: 192.168.1.100, same mask.
Network of the laptop: 192.168.1.100 AND 255.255.255.0 = 192.168.1.0.
Network of the terminal: 192.168.1.10 AND 255.255.255.0 = 192.168.1.0.
The networks match and the host parts differ, so the cable can carry unicast traffic. Now ping 192.168.1.10 times out on every attempt while a transfer to that same address completes; the decision is the disabled echo response, and the addressing work is finished.
Change one figure and the verdict flips: a terminal set to 192.168.10.10 under the same mask sits in network 192.168.10.0, which does not match 192.168.1.0, so nothing crosses the cable until the address is corrected, and in that case the transfer fails alongside ping.
Where is the ping-response setting, and how do you reach it safely? #
The setting lives in the terminal's Windows CE network configuration, outside the running FactoryTalk View ME application, so you reach it only by exiting the runtime through its authorized exit or configuration path.
Work in this order:
- Record the current startup configuration, meaning which application starts automatically, so you can restore it exactly.
- Stop the runtime through the terminal's authorized exit. On a running machine this blanks the operator's screen, so schedule the stop with production first.
- If the exit or the configuration area is password-protected, use the authorized administrator account or the vendor's documented reset; the route is described in getting past the application password into PanelView Plus configuration. A ping timeout never justifies working around access controls.
- In Windows CE, open the network configuration and enable the ping or ICMP echo response; read the setting's description to confirm it governs echo requests before changing anything else.
- Apply the change by the documented procedure, restart only if that procedure requires it, then return to the runtime and restore the intended startup behavior.
Which observation decides what you fix first? #
One fresh transaction decides it: success alongside ping timeouts sends you to the echo setting, and any failure of that transaction sends you back to the path before the terminal is opened.
| Observation | Decision |
|---|---|
| Fresh transfer or live session succeeds; ping times out | Echo responses are disabled; enable them in Windows CE |
| Icon present, no current operation attempted | Treat the listing as stale; refresh and run a live operation first |
| Transfer and ping both fail | Addressing, adapter selection or physical link; run the five checks |
| Ping replies arrive; transfer fails | Path is good; troubleshoot the transfer service and software configuration |
The last row is the mirror image of this fault and is worked separately in why an HMI transfer fails in Initial Start Mode despite ping.
How do you verify the fix without breaking the application? #
Repeat the identical test, same adapter, same cable, same address, and a change from timeouts to replies names the echo setting as the cause; then confirm the runtime and controller data before you close the job.
- Run
pingagain to the same address and read the reply summary, not just the first line. - Refresh RSLinx and confirm a current operation succeeds; the icon alone still proves nothing.
- Confirm the intended application starts and shows its screens. With a controller attached, check live values: question marks there mean the controller communication path needs attention, a different fault covered in PanelView Plus question marks on live values.
- If a restart was required, recheck ping behavior and application startup together.
Timeouts that persist after the response is enabled, while application traffic still flows, put the filter on the laptop side: check how the laptop firewall handles echo replies before you reopen the addressing work.
Questions asked
Does ping need a port opened on a firewall to work?
No. ICMP is its own IP protocol with no TCP or UDP port, so a firewall must pass echo requests and echo replies by message type, not by port number. Opening the ports used by the transfer service never fixes a ping timeout, which is why the terminal's control is a response setting rather than a port exception.
Should ping responses stay enabled after troubleshooting?
On an isolated control network with no route to office traffic, leave them enabled: the setting changes nothing about which application services answer, and maintenance checks rely on the replies. Where the segment sits behind managed filtering or the site hardens terminals against scanning, follow the site's ICMP policy instead, and record the choice you made.
Could a duplicate IP address cause this symptom?
Rarely in this exact form. A duplicate address disturbs application traffic as well, so transfers and browse operations fail intermittently instead of splitting cleanly. The tidy split, every echo request timing out while a fresh download succeeds, points at the response setting; a duplicate announces itself through failing transactions first.
How many ping requests make a fair test?
Command Prompt's ping sends four echo requests, about one second apart, then reports sent, received and lost counts. Judge the terminal on all four: one lost reply can be an ARP delay on a freshly connected cable, while four timeouts against a working transfer session confirm the response is disabled.