How-to
Setting Up a Weintek HMI as a Central RFID Login Server
Short answer
Your existing HID proximity cards work, and no PC is needed: one HMI acts as the login server. Program the reader for keyboard emulation, add the Barcode Scanner/Keyboard driver, store each card UID as the account password on the server, and let clients log in with LW-1074 as user name, BARCODE 1 as password and a macro on FLAG 0.

On this page
- Will your existing HID proximity cards work with the login feature?
- Why does the reader detect the card but the HMI keeps waiting?
- How do you store each card UID on the server HMI?
- How does a scan turn into a login on each client HMI?
- Can a PC be the central login server instead of an HMI?
- How many client HMIs can one login server serve?
- How do you verify the setup before you roll it out?
- Should you use the smart card plugin or the barcode server method?
- Questions asked
Yes — your existing HID proximity cards work, and one HMI can act as the login server for every other HMI on the line, with no PC anywhere in the credential path. The setup described here ran on a cMT-FHDX-820 with EasyBuilder Pro v6.09.02.651 and an Elatec TWN4 reader reprogrammed for keyboard output. Each client HMI receives the card UID as scan data through the Barcode Scanner/Keyboard driver, submits it as the password with the user name from LW-1074, and a macro fired by FLAG 0 executes the login against the server. You enroll each card once, on the server HMI, instead of once per machine.
Will your existing HID proximity cards work with the login feature? #
Yes: the HID ISOProx II 1386-RF proximity card and the Elatec TWN4 Palon panel both operate at 125 kHz, so the cards you already issue are compatible — the work is on the reader's output side, not the cards.
That pair is the tested hardware: a TWN4 Palon panel with part number T4PK-F02TR6-P reading 1386-RF cards. The frequency match settles the RF question and nothing else. It says nothing about what bytes leave the reader over USB, and it is the USB side that decides whether the HMI ever sees a UID. Buy nothing new; keep the cards and the reader, and configure the output as the next section shows.
Why does the reader detect the card but the HMI keeps waiting? #
Because detection and data delivery are two separate links: the reader's LEDs only prove a transponder was read, while the prompt asking for a card stays open until usable UID bytes arrive through the driver — and keyboard emulation is the output mode that closes that link.
Reader support pointed at CDC and CCID; neither resolved the stuck prompt. The configuration that worked reprograms the reader to simulate a keyboard and receives it in the project through the Barcode Scanner/Keyboard driver:
- Program the reader for keyboard emulation output.
- Add the Barcode Scanner/Keyboard device to the EasyBuilder Pro project.
- Scan a card while watching
BARCODE 1; the UID must appear there. - Watch
FLAG 0: it is OFF while reading and returns ON after the data is read successfully.
If BARCODE 1 stays empty, stop at this layer. No account, password or login-command change on the server can repair scan data that never reached the HMI.
How do you store each card UID on the server HMI? #
On the server HMI, open the default Add account window (window 71), put the operator's initials under Name, scan the card, then press the combo button to write that UID into the account's Password field — the UID is the password, and nothing else goes in it.
- Designate one HMI as the remote login server and create the user accounts on it.
- Add a Barcode Scanner/Keyboard device to the server project and connect the enrollment reader.
- Open the default Add account window (window 71) and enter the operator's initials or another readable name in the Name field.
- Scan the operator's card, then press the combo button to transfer the scanned RFID UID into that user's Password field.
- Store only the UID in Password.
Easyweb 2.0 can manage these server accounts over the network, so routine administration does not mean reopening the project.
How does a scan turn into a login on each client HMI? #
FLAG 0's return to ON after a successful read fires a macro that maps BARCODE 1 to the password, supplies the user name through the HMI system address LW-1074, and executes the login command against the server HMI.
On every client:
- Configure the HMI to authenticate against the remote server HMI.
- Add the Barcode Scanner/Keyboard driver, and program that client's reader for keyboard-style output.
- Start a macro from the
FLAG 0transition — OFF while reading, ON when the read succeeds. - Map
BARCODE 1to the password andLW-1074to the user name. - Execute the login command only after both fields hold data.
| Item | Role in the login |
|---|---|
BARCODE 1 |
The scanned UID, submitted as the password |
FLAG 0 |
Read status; its return to ON is the trigger |
LW-1074 |
The user-name side of the credentials |
| Login command | Runs last, after both fields are filled |
Do not use the local user index for this login: it addresses the users stored on the client itself, so a correct UID reads as invalid when the accounts live on the server. This is also the honest limit of auto login here — the card supplies only the password, so the operator's name must reach LW-1074 by selection or because the macro writes it. If the machine controller separately needs to know who signed in, sending the active HMI user to the PLC with login macros covers that hand-off. Card login identifies operators; it is not a safety function, so keep interlocks and E-stop hardware independent of it.
Can a PC be the central login server instead of an HMI? #
No: in this method the credential store is another HMI configured as a remote login server, and no PC runtime is documented or field-proven for that role — put the server on an HMI you keep powered, reachable and backed up.
Central storage is the whole point. The smart card plugin alternative keeps each UID on the HMI where the card was scanned, which is the behavior behind why RFID card assignment happens on the panel and not in the project, while a Comfort Panel RFID login with PM-LOGON Basic identifies operators through that vendor's own login block. The barcode/keyboard method instead turns the UID into ordinary credential data that any client can submit to the server.
Worked example, one line of 8 machines and 25 operators: per-HMI enrollment means 8 × 25 = 200 card-to-user assignments, and one reissued card means 8 edits. The server method means 25 assignments on one HMI, and a reissued card is 1 edit. That arithmetic decides it: multiple machines, one server.
How many client HMIs can one login server serve? #
There is no limit on the number of HMI clients that may log in, so availability — not a connection count — decides the design: every client's credential check passes through that one server HMI.
Give the server's power supply and network link the same engineering respect as any machine on the line. Per client, the work is identical at any count: the driver, the keyboard-mode reader and the macro.
How do you verify the setup before you roll it out? #
Prove the chain link by link on one client, then repeat the login from a second client with the same centrally stored account — that second login is the test that proves the server path rather than any local one.
- Scan a known card and confirm the reader responds.
- Confirm
BARCODE 1holds the expected UID andFLAG 0returns ON after the read. - Confirm the macro writes the UID only into the password field, and that the user name matches an account stored on the server HMI.
- Log in from more than one client HMI with the same account.
- Open the Operational Log and confirm the entry names the operator you enrolled.
- Save a project backup of the server HMI before rollout; if EasyBuilder Pro throws an error on a cMT-FHDX-820 backup file, this cMT-FHDX-820 HMI backup file error fix covers it.
Should you use the smart card plugin or the barcode server method? #
Use the plugin only for a single standalone HMI; the moment a second machine needs the same cards, the server method wins on every count that matters: one enrollment per card, one place for credential changes, and an audit trail that names people.
Standalone machine: the plugin is simpler and needs no server. Two or more machines, or cards that get reissued: the server method, exactly as set out here. Either way the cards stay the same ones your operators already carry.
Questions asked
What happens to client logins if the server HMI goes offline?
Clients hold no local copy of the central accounts, so a powered-off or unreachable server HMI stops authentication on every client at once: no card and no password works until the server is back. Restore the server first, before you troubleshoot any client.
Can you export user accounts from one HMI and import them into another?
There is no documented direct export of user login data from an HMI for import into another, which is exactly the gap this design closes. Enroll each card once on the server HMI and every client authenticates against that store, so nothing ever needs copying between machines.
What happens if the UID is used as both user name and password?
The login still succeeds, but the Operational Log then records the card code rather than a person, so the trail cannot distinguish one operator from another. Keep the operator's initials in the Name field and store only the scanned UID as the password.
What do you do when an operator loses a card or joins the line?
Scan the new card at the server HMI and press the combo button to write its UID into that operator's Password field. Every client uses the new credential at the next login, and the lost card stops working because its UID no longer matches any account.


