HMI and touchscreens Published 5 min read By IMDTouch engineering team

Short answer

No. The engineering project carries the local users, but a Unified panel records which RFID card belongs to which user only in its own user management, with the reader connected directly to the panel. Collect the cards once, enroll them against a prepared user-to-card mapping, verify every login, then export the user list to further Unified panels instead of swiping the cards again.

On this page
  1. What the project can and cannot hold
  2. What carries over from the old Comfort panels
  3. Build the user-to-card mapping first
  4. Enroll each card on the panel
  5. Worked example: one site, five panels
  6. Verify every card before handover
  7. When a card will not log in
  8. Questions asked

No. A Unified Comfort Panel does not take RFID card-to-user assignment from the engineering project. TIA Portal carries the local users, groups and roles, but the link between a card and a user is written only in the panel's own user management, with the RFID reader connected directly to the panel. So yes: you collect the cards and present each one to the new panel, once, in a single planned enrollment session. This article gives the sequence, the arithmetic for a multi-panel rollout and the checks before handover.

What the project can and cannot hold #

The mechanism decides this. The reader reads the serial number (UID) of the presented card, and the panel logs in the user to whom that UID is assigned. That UID-to-user table lives in the panel's own user management; the project download delivers users, groups and roles, and nothing in it writes the table. The operating instructions put the assignment on the device itself, under one hard condition: RFID login only works with a reader connected directly to the HMI device. A reader attached to the engineering PC therefore enrolls nothing, which is another way of saying the cards travel to the panel.

Users and passwords can be engineered and downloaded; the card link cannot. That difference sets RFID apart from the password among the login methods on a Unified Comfort Panel by user management. And because an RFID login matches a UID against the assignment table without reading any password, typing card IDs into password fields enrolls nothing. Leave the passwords as they are and plan the panel session instead.

What carries over from the old Comfort panels #

Your current cards authenticate through RFID card login on a Comfort Panel with PM-LOGON Basic, and the same cards will serve the new panel: the UID is fixed in the card and does not change when or where the card is assigned. What does not carry over is the assignment record. It sits in the old panel's user management, and the only documented import path for a user list with RFID logins runs from one Unified Comfort Panel to another. Keep the cards and the user names, plan one presentation per card on the new panel, and spend no time trying to export the old panel's card database.

Build the user-to-card mapping first #

Before anyone touches the panel, write one line per user:

  • the user name exactly as engineered in the project;
  • the card that person holds, with the UID if the old system lists it, otherwise the holder and the card's marking;
  • two empty boxes: enrolled, login tested.

At the panel you select a name, then present a card. With a stack of collected badges in hand, the sheet is what stops a card landing on the wrong account, and a mis-enrolled card is nasty because it silently gives its holder someone else's permissions. Settle duplicates and gaps on paper first: every card exactly one user, every RFID user exactly one card. Do not start the panel session without the sheet.

Enroll each card on the panel #

  1. Download the project with all local users and confirm every account appears in the panel's user list.
  2. Connect the RFID reader directly to the panel.
  3. Open user management in the panel's Control Panel.
  4. Select the first user from the mapping sheet, and never enroll while unsure which name is selected.
  5. Present that user's card to the reader and confirm the assignment as the operating instructions describe.
  6. Tick the pair on the sheet and take the next user until the sheet is complete.

Worked example: one site, five panels #

Take 30 users and five identical Unified Comfort panels, all on local user management. First panel: 30 cards × 1 presentation each = 30 presentations at the reader. At an example planning allowance of 2 minutes per user (select the name, present the card, confirm, tick the sheet), the session is 30 × 2 min = 60 minutes. Then export the user list from the enrolled panel in the .udz format and import it on each of the other four panels: 4 × 30 = 120 assignments travel inside the file, so the site total is 5 × 30 = 150 assignments, of which only the first 30 ever touched a reader. Collect the cards once, and never plan a swipe session per panel.

Verify every card before handover #

Run enrollment and login tests with the machine in a maintenance state, because every test login changes the active user and with it the permissions in effect at the panel. On the enrolled panel, do the full pass: for each line of the sheet, present the card and confirm the logged-in name is the mapped user. On each imported panel, test one card per role until the import is proven, and write down what you tested. Present one card that was never assigned and confirm the panel refuses it. Handover is the moment the sheet carries a recorded login for every card; a downloaded project with untested cards is not a finished migration.

When a card will not log in #

Work the causes in order:

  • The card was never assigned on this panel. An account that exists proves nothing about its card; redo the enrollment for the right pair.
  • The reader is not connected to the panel itself. Reconnect it and present the card again.
  • The wrong name was selected during enrollment. The giveaway is that the card logs in a different user; reassign it to the mapped user and retest.
  • On a WinCC Unified PC runtime, login with assigned cards is switched off in the runtime's RFID configuration. Enable it and present the card again.

Retest after each fix and record the result next to the mapping line.

Questions asked

Can operators keep using their cards on the old Comfort panels during the migration?

Yes. The assignment on the new panel is a separate record in that panel's user management, and the old panel's PM-LOGON assignment stays untouched in the old panel. The same physical card therefore works on both machines at once, so you can migrate machine by machine instead of cutting over every card in one day.

Does the same rule apply to a WinCC Unified PC runtime?

Yes. The reader connects to the PC runtime system, and the cards are registered in the runtime's RFID card list, administered in My WinCC Unified rather than in the engineering project. The RFID settings there show which cards are assigned to which user and whether login with an assigned card is enabled. With local user management, the runtime also accepts RFID and PM-LOGON login from its local web clients.

Is classic WinCC configured the same way?

No. In WinCC V8.1, when SIMATIC communications modules handle the RFID hardware, the logon via RFID card is configured in the User Administrator. That is engineering-side configuration, unlike Unified, where the assignment is made on the runtime device, so do not carry the expectation from one system to the other.

Do password logins still work after a card is enrolled?

Yes. The password and the RFID card are separate credentials on the same local account; enrolling a card adds a login method and changes nothing about the password. Users can fall back to password login while the cards are being collected and enrolled.

Keep reading

  • Troubleshooting

    Fixing a WinCC Comfort license not valid error in TIA Portal V11 SP2

    The "license WinCC Comfort not valid" dialog at TIA Portal V11 SP2 startup is an engineering-station problem, not a KP1500 Comfort fault: the WinCC Comfort option, its Update 2, the Comfort Panels HSP or a valid license key is missing. Install the option, apply Update 2, import the HSP and repair the key in Automation License Manager, then bring the OP37 project across through ProTool and WinCC flexible before re-targeting the KP1500 Comfort.

    HMI and touchscreens

  • Explainer

    Why a C7-626 panel has no ProSave backup or upload route

    The OP25-based C7-626 implements neither project upload nor ProSave backup and restore, so a failed display leaves nothing to extract. Replacement means confirming the exact model, finding the original editable PLC and operator-panel source projects, and reloading them, with runtime recipe values checked separately.

    HMI and touchscreens

  • Explainer

    Login methods on a Unified Comfort Panel by user management

    A Unified Comfort Panel in TIA Portal V19 selects its login methods from two conditions: local user management or a central UMC domain, and direct panel operation or a web client. A web client always signs in with username and password only. The panel adds RFID cards, Unified Air biometrics and an alias system function with local users, and RFID cards with a central domain when PM-LOGON Unified is installed.