Selection guide
Sizing Controller I/O Limits and Selecting an HMI Panel
Short answer
One controller cannot take this job: its documented limit of 24 digital inputs loses to the 35 the machine room needs, so the I/O splits across two controllers at 21 and 14 inputs. The voltage-capable inputs on the 12/24 RCE model carry the transmitters directly, resistance temperature probes go through transducers or a two-channel module, and a Basic-class panel covers the static status screens.

On this page
Split the digital inputs across two controllers before any other decision. The documented ceiling for one LOGO! 8 controller of the 0BA8 generation is 24 digital inputs, and this machine room counts 35 in total — a shortfall of 11 that no program optimization can close. The two-controller schedule already proposed, 21 inputs on the first controller and 14 on the second, fits every documented category with margin. The voltage-capable inputs on the 12/24 RCE model carry the transmitters directly, the resistance temperature probes go through transducers or a two-channel RTD module, and a Basic-class panel covers a screen set of static objects, status lights and live values. This article runs each check and ends with the decision for every case.
The four limits that decide the controller count #
The LOGO! system manual states the maximum for one 0BA8 controller as 24 digital inputs, 20 digital outputs, 8 analog inputs and 8 analog outputs. These are four independent ceilings: spare capacity in one category buys nothing in another, so compare each category on its own and let the worst category decide. Exceeding any single one forces a second controller even when the other three are half empty.
| I/O category | Limit for one controller | Machine room total | Verdict |
|---|---|---|---|
| Digital inputs | 24 | 35 | Over by 11 — a second controller is required |
| Digital outputs | 20 | 20 (8 on the first, 12 on the second) | At the ceiling in total, but the split leaves 12 and 8 spare |
| Analog inputs | 8 | 6 (4 plus 2) | Under by 2 |
| Analog outputs | 8 | Not yet specified | Close the schedule before ordering |
Checking the two-controller schedule against the 0BA8 limits #
The inputs come from two places: the project's own I/O table gives LOGO1 21 digital inputs, 8 digital outputs and 4 analog inputs, and LOGO2 14 digital inputs, 12 digital outputs and 2 analog inputs; the LOGO! system manual gives the per-controller limits. The rule: every controller must sit at or below each of the four category limits on its own.
- LOGO1: digital inputs 21 against a limit of 24, fits with 3 spare; digital outputs 8 against 20, fits with 12 spare; analog inputs 4 against 8, fits with 4 spare.
- LOGO2: digital inputs 14 against 24, fits with 10 spare; digital outputs 12 against 20, fits with 8 spare; analog inputs 2 against 8, fits with 6 spare.
- Single-controller counter-check: 21 + 14 = 35 digital inputs, 8 + 12 = 20 digital outputs, 4 + 2 = 6 analog inputs. The input count alone misses by 11.
Result: both controllers fit every stated category, while a single controller fails on digital inputs before the other categories even matter. The decision that follows: build two controllers, and treat the three spare inputs on LOGO1 as the entire growth budget, because at the system level 35 against 24 leaves nothing on the table.
Matching the analog signal types to the terminals #
A channel count is not electrical compatibility. On a 24 VDC supply the LOGO! 12/24 RCE exposes four inputs — I1, I2, I7 and I8 — that can each read a 0-10 V signal, which exactly covers LOGO1's four analog inputs provided none of those terminals is also claimed as a digital input in the schedule. A PT100 or PT1000 probe cannot land on such a terminal directly. Two documented paths exist: an external transducer per probe that outputs 0-10 V or 0/4-20 mA, or the two-channel RTD expansion module — a four-point temperature list therefore needs four transducer channels or two RTD modules. A transducer with a current output needs a receiving channel that accepts current; on a voltage-only input it reads wrong.
Working out which analog inputs the water side of this project really needs is its own sizing step; the walkthrough of which analog inputs a water monitoring system needs applies the same listing method to a treatment plant.
The schedule names no analog outputs at all. Any dosing stage, modulating valve or remote indication that needs a commanded signal must be counted now: the ceiling of 8 per controller is generous, but an unknown line in an approval table is not approval.
Choosing the panel from the visualization task #
The stated scope is static objects, status lights, two-color device icons, and numeric level, pressure and temperature values. That is exactly the workload a Basic-class panel is built for — the KTP900 Basic named for this project covers it — and wanting a large screen to reduce switching between screens is a layout choice that stays within Basic. Comfort class matters when the screens need scripting, deeply nested faceplates, cross-controller alarm history or several protocols at once; nothing in this scope needs any of that.
One panel watching both controllers is a normal architecture — each controller takes one connection from the panel — but the panel's connection budget still needs counting; the method in counting HMI device connections for an extrusion machine upgrade applies directly, and why one HMI cannot watch twelve LOGO controllers at once explains why even two controllers behind one panel deserve that check. Verify that the panel's engineering tool ships a LOGO! driver before purchase, not after.
If you would rather serve the screens as a web page from a small computer than buy a dedicated terminal, that role belongs to industrial panel PCs and touchscreen computers, which run the visualization software at the machine in place of the operator panel.
Commissioning checks that decide acceptance #
- Close the analog-output line in the schedule, then re-run the limit table above against the final counts.
- Reserve I1, I2, I7 and I8 in the terminal plan if they read 0-10 V — a digital function silently assigned to one of them breaks the analog plan.
- Size the circuit program and test it with every function running at once. Blocking under heavy loading has been reported on this controller family with no reproducible threshold documented; treat it as a commissioning risk to test, not a specification to trust.
- Validate the KNX link through the CMK2000 module and the Modbus link through the CIM separately from the control program, each with its own addressing and timeout test.
- Verify analog scaling end to end: inject a known signal at the terminal and confirm the engineering value shown on the panel.
On the first full run, inhibit the pump and heater contactor outputs and prove the controller-to-controller handshake and the behavior on a lost inter-controller link with the outputs disabled — a stalled program must leave the plant safe, not merely displayed wrong.
The decision, case by case #
- One controller for everything: rejected — 35 digital inputs miss the 24-input limit by 11.
- Two controllers at 21/8/4 and 14/12/2: accepted — every category fits, with 3 spare inputs on LOGO1 and 10 on LOGO2.
- Voltage transmitters on I1, I2, I7 and I8: accepted, with those terminals reserved in the schedule.
- PT100/PT1000 probes: accepted through 0-10 V transducers or two-channel RTD modules; a current-loop transducer only where a current input exists.
- Analog outputs: unresolved until counted — do not order hardware until that schedule line closes.
- Panel: a Basic-class unit such as the KTP900 Basic is accepted for this static, status-only scope; Comfort class only if scripting or cross-controller alarm history enters it.
Questions asked
Can one controller ever take all 35 digital inputs?
No. The documented maximum for one 0BA8 controller is 24 digital inputs, and expansion does not raise that ceiling, so the schedule must shed at least 11 inputs to a second controller. The proposed split of 21 and 14 leaves 3 spare inputs on the first controller and 10 on the second.
Do the PT100 temperature probes connect straight to the controller?
The controller's analog inputs read a voltage signal only. A PT100 or PT1000 probe goes through an external transducer that converts it, or onto a dedicated two-channel RTD expansion module, so a four-probe temperature list needs four transducer channels or two modules.
Does a Basic-class panel really cover a large, mostly static screen?
Yes, for this scope. Screen size is a layout decision, and Basic-class panels exist in large sizes that handle static objects, two-color icons and live numeric values. What moves you up a class is functionality such as scripting, deeply nested faceplates, alarm history or several protocols, not inches. Pick the size from how many hierarchy levels the operator must navigate, then confirm the Basic engineering tool renders the layout legibly.
