TP700 Comfort SD card access through the web server HTML pages

HMI and touchscreens Published 5 min read

Short answer

TIA Portal over a TS Adapter IE is not the documented route to the card's files; the integrated web server of the Comfort panel is. Enable the HTML pages option, define a web-server account at the panel itself under Control Panel, WinCC Internet Settings, Web Server, and log in from a browser.

On this page
  1. Why the web server is the route
  2. Enable the HTML pages in the project
  3. Create the web-server account at the panel
  4. Which image the panel runs
  5. Read the files from the browser
  6. Worked example: first-time access to CSV logs on a new TP700 Comfort
  7. When the panel itself is the problem
  8. Questions asked

You cannot browse a TP700 Comfort SD card from TIA Portal through a TS Adapter IE; teleservice reaches the panel for download and diagnosis, not its file system. The documented route to the historical CSV files and recipe files on the card is the panel's integrated web server: enable the HTML pages option, create a web-server account locally on the panel, and read the files from any browser on the plant network. This article walks that route end to end; if your problem is instead an SFTP client that cannot see the data logs, the article on why HMI SFTP cannot see the SD card data log files covers that side.

Why the web server is the route #

The Comfort panel ships with an integrated web server that the vendor documents as included with the panel at no extra cost. When the HTML pages option is activated in the project, the web server starts automatically with the runtime and serves the panel's standard service pages, which include file access to the storage locations the panel exposes, among them the SD card with its CSV archives and recipes. Teleservice through a TS Adapter IE gives TIA Portal a transfer path for program download and online checks; it was never a file browser for the card.

Enable the HTML pages in the project #

  1. In the TIA Portal project for the panel, open the runtime settings and activate the HTML pages option.
  2. Compile and download the project. The web server starts with the runtime once this option is set.
  3. Note the panel's IP address from the Control Panel network settings; you need it for the browser step.

On a PC runtime the standard service pages are installed even when the option appears cleared, so this step matters mainly for panels.

Create the web-server account at the panel #

From V13 images onward there is no default web-server credential, so the account must be defined on the panel itself:

  1. Open the Control Panel on the TP700 Comfort.
  2. Select WinCC Internet Settings.
  3. Open the Web Server tab and click User Administration; the UserDatabase-Edit dialog opens.
  4. In the User manager tab click Add, then define the user name and password permitted to access the web server.
  5. Close the dialogs and confirm the settings.

These are web-server credentials in their own user database. Accounts from the HMI application's user administration do not authorize the HTML pages, which is why a correct runtime user is rejected at the web login. Whether the account can be created remotely through teleservice or a program download is not documented; do it locally at the panel. If a pre-existing account blocks you and nobody knows its password, the documented procedure is to define your own account in the Web Server tab, not to guess at factory values.

Which image the panel runs #

Older images are reported with a factory web password; from V13 on there is none. Identify the installed image before you assume anything:

Panel image Default web credential Your decision
V11 or V12 Reported factory password exists Change it or add your own account; do not leave it in service
V13 or later None Define a web-server user in WinCC Internet Settings, Web Server

A freshly commissioned HMI does not prove the factory credential applies; check the image version in the Control Panel.

Read the files from the browser #

  1. Enter the panel's IP address in a browser on the plant network.
  2. Log in with the web-server account you created.
  3. Open the service pages and navigate to the file area; confirm the historical CSV files and the recipe files on the SD card are listed and can be opened or saved.
  4. If login fails, go back to the Web Server tab and verify the user list before anything else.

One safety note: the web server is a login to your operator station, so keep it on the controlled plant network, give the account a real password, and do not forward it to the Internet without the network protection your site requires.

Worked example: first-time access to CSV logs on a new TP700 Comfort #

Inputs: the panel is new, the thread-type case, running a V13 image (from the Control Panel image version); the project's HTML pages option is enabled (runtime setting from step one); the panel's address is 192.168.1.50 (example address from the Control Panel network settings); the target files are the CSV archives written to the SD card by the data log configuration.

Rule in words: with no default credential on a V13 image, access equals one enabled option plus one locally defined account plus one browser session to the panel's address.

Arithmetic: there is nothing to multiply, only to count. 1 enabled option (HTML pages) + 1 web-server account (defined in WinCC Internet Settings, Web Server) + 1 browser session to 192.168.1.50 = 1 working file view of the card's CSV logs.

Result: after those three steps the file pages list the SD card archives, and the recipe files can be opened from the same pages.

Decision: if the login is rejected after this, the fault is in the account, not the network; correct it in the Web Server tab and retry. If the pages open but the card is not listed, confirm the card is seated and the data log actually wrote files, then reopen the file pages.

When the panel itself is the problem #

If the panel will not present its web pages at all, will not boot, or the unit is being replaced anyway, a PC-based HMI runtime on an industrial panel PC gives you the same web-server and file access through the runtime's own service pages.

Questions asked

Is there a default web-server password I can use on a new panel?

Only an older image is reported to ship with a default credential: V11 and V12 images are reported with a simple numeric factory password. A V13 or later image has no default password at all, so the account has to be created at the panel. Never rely on a factory credential for a running machine; set your own web-server account at commissioning.

Are the HTML pages and HMI runtime users the same account list?

No. The web server uses its own user database, maintained separately from the project's user administration in WinCC. Adding an operator in the engineering tool does not create a web login, and a web login does not grant runtime permissions. If a login fails on the HTML pages, check the web-server user list in the panel's Control Panel, not the HMI user groups.

Does the integrated web server need a separate license?

No. The vendor documents the Comfort panel's integrated web server as included with the panel. What you must enable is the HTML pages option in the runtime settings so the server starts with the project, and a defined web-server account. WebUX or SmartServer remote viewing is a different feature with its own requirements.

Why is the SD card invisible to an SFTP client on the same panel?

The SFTP service exposes the transfer directory the panel's file system maps for external access, which is not the whole card. The web server's file pages read from the card through the panel's own service, which is why CSV logs and recipes show up there. A dedicated article on why HMI SFTP cannot see the SD card data log files covers the SFTP side.

Keep reading

  • Selection guide

    Replacing a Local HMI With a Phone App on a PLC

    Yes, where the access is documented: a phone app reads and writes controller tags like an HMI over a tag-level driver in the app, pages served by the controller itself, or a Modbus TCP mapped block. Keep the sequence in the PLC and give the phone a small validated data contract; go phone-only on machines touched at service visits and keep a station where an operator works every shift.

    HMI and touchscreens

  • Selection guide

    Where WinCC Unified Runtime Can Run and Remote HMI Options

    The Unified runtime executes only on a PC, a Panel IPC, a Unified Comfort Panel or the MD-34 tablet; a browser or Sm@rtServer VNC client displays it and never replaces the host. With no PC in the cabinet, a Unified Comfort Panel is the host and the tablet browser is the client. If a safety function must travel with the operator, no Unified mobile panel exists and the design stays Comfort-based.

    HMI and touchscreens

  • How-to

    Where to enter Sm@rtServer credentials in WinCC Runtime Advanced

    Enter the remote user and password in Windows Control Panel under WinCC Runtime Advanced Internet, on the Remote tab, behind Change Settings in the Server tab of the dialog that opens. The Sm@rtServer checkbox in the project's runtime settings only enables the server. Record the listening port shown there and use it with the PC's address in Sm@rtClient.

    HMI and touchscreens

Set an Idle Screen Timeout That Returns to the Main Page