Unified Comfort Panel simulation fails in VMware

HMI and touchscreens Published 5 min read

Short answer

In a reported TIA Portal V16 trial, Unified Comfort Panel simulation in VMware guests started after Activate secure download was cleared in WinCC Unified Configuration, with the same empty project. Run that as a controlled single-change diagnostic on an isolated engineering VM, and keep secure download active for transfers to a real panel.

On this page
  1. Why an empty project still fails
  2. Secure download and the startup boundary
  3. The single-change diagnostic
  4. Worked example: the V16 trial in two VMware guests
  5. Baseline checks before changing anything
  6. If the retest still fails
  7. What a passing test proves
  8. Questions asked

Your Unified Comfort Panel simulation can fail before even an empty screen opens. In one reported TIA Portal V16 trial it failed in VMware on both a Windows 7 x64 and a Windows 10 x64 guest, while a conventional Comfort Panel simulated in the same VM. The simulation started after a single setting changed: Activate secure download, cleared in WinCC Unified Configuration. That result is a diagnostic, not a deployment setting. Run it as a controlled single-change test on an isolated engineering VM, and keep secure download active for any transfer to a physical panel.

Why an empty project still fails #

HMI simulation runs the configured operator interface without the physical panel. The reported project held one empty main screen and no HMI tags, which removes controller communication and nearly all application logic from the fault search. When a project that minimal still will not start, the fault sits in the simulation environment or its configuration, before the first screen is drawn. Editing graphics or rebuilding tag connections cannot fix a startup that dies at that boundary.

Secure download and the startup boundary #

Secure download is the protected project-transfer function of the Unified runtime, and its switch in the configuration application is Activate secure download, reached at the Secure download step. Transfer and runtime execution are different operations, yet the simulation launch depends on the configuration prepared around the runtime, so a fault at that boundary can stop even an empty project. The conventional Comfort Panel simulating in the same VM proves the virtual machine runs the older simulation path. It proves nothing about the separate Unified stack, so treat it as a comparison, not an approval.

The single-change diagnostic #

Make the first test reproducible, then change exactly one thing:

  1. Stop the failed simulation attempt so the next launch is a distinct test.
  2. Open WinCC Unified Configuration in the Windows guest that holds the Unified installation.
  3. Walk through the configuration application to the Secure download step.
  4. Clear Activate secure download, then finish the workflow so the changed selection is retained.
  5. Launch simulation again on the same empty project, with project content and virtual-machine configuration untouched.
  6. Record whether the main screen now opens.

This switch protects project transfer, so make the change only on an isolated engineering machine; a panel that will receive downloads keeps secure download active.

Worked example: the V16 trial in two VMware guests #

This is the reported case itself, so every input comes from that installation.

Inputs and their source:

  • Engineering installation: TIA Portal V16 trial with WinCC Unified, from the reported case.
  • Virtual machines: 2 VMware guests, Windows 7 x64 and Windows 10 x64.
  • Project content: 1 empty main screen and 0 HMI tags.
  • Baseline: 2 launches, one per guest, with 0 reaching the main screen.
  • Change before the retest: 1 setting, Activate secure download cleared in WinCC Unified Configuration.
  • Retest: 1 launch, on the unchanged project and the unchanged VM.

The rule, in words: a retest attributes the outcome to a change only when exactly one input differs from the baseline, so count the changed inputs before you read the result.

The arithmetic:

  • Changed inputs = settings (1) + project content (0, still 1 empty screen and 0 tags) + VM configuration (0) = 1.
  • Baseline: 0 starts ÷ 2 launches = 0.
  • Retest: 1 start ÷ 1 launch = 1.

Result: with exactly 1 changed input, the outcome moved from no start to a start, so the startup failure in this installation is attributed to the secure-download configuration.

Decision: at a changed-input count of 1 with a passing retest, stop and run local simulation with the setting cleared on that VM. At a count of 2 or more, the comparison is void: restore the baseline and rerun with a single change.

Baseline checks before changing anything #

Record each of these readings before the diagnostic:

  • Device target: read the project's device configuration and confirm the failing test aims at a Unified Comfort Panel, not the conventional Comfort Panel used for comparison.
  • Startup message: capture the complete text and any identifier before touching settings. The reported case's message is not available, so never assign a cause from the workaround alone.
  • Versions: the installed Unified simulation runtime must match the TIA Portal version and its updates. One reported refusal named exactly that mismatch, even with the same update level on both sides, so read the message instead of assuming. The same discipline applies to the panel itself; see matching an HMI panel image to its TIA Portal project version.
  • Simulator address: under TIA Portal Settings, Simulation, HMI simulation, the simulator's host address defaults to 127.0.0.1. With engineering and runtime in the same guest, leave it there.

If the retest still fails #

The new message picks the next path:

  • A message naming a certificate or trust item points back at the transfer-security configuration; recheck what the Secure download step retained.
  • A message naming a version points at the simulation runtime against the TIA Portal version, updates included.
  • A message naming a license points at the engineering license rather than at simulation; WinCC Unified project will not open with a Comfort or Advanced license covers that failure class.
  • No clear message: try the reported installation-level fix, uninstalling WinCC Professional before installing WinCC Unified on the same station. Record it as its own single change, exactly like the first.
  • Once the runtime starts on a project that has tags, verify the PLC tags and the runtime services; the empty test project never exercises either.

What a passing test proves #

A start verifies the workaround, not the application: an empty project tests no controller connection, data quality or screen update. Confirm three readings:

  • Retention: reopen the Secure download step; the switch is still cleared for the workaround test.
  • Repeatability: stop the simulation and launch it again; the same empty screen opens with no further change.
  • Isolation: the project still holds 1 empty screen and 0 tags, so the pass belongs to the original minimal test.

Before the physical panel receives its first download, complete the transfer configuration with secure download active.

Questions asked

In which order do I start simulation when a simulated PLC is involved?

Start the HMI simulation in WinCC first, then S7-PLCSIM; the vendor documentation specifies that order. The empty test project never opens a PLC connection, so PLCSIM is not needed for the startup test. Add it only after the runtime starts and your project holds tags that need values.

Why does simulation fail for a user who did not install TIA Portal?

When TIA Portal or S7-PLCSIM was installed by someone else, the documentation requires the simulating account to belong to a specific user group it names. Check that group membership against the simulation documentation and add the account before you troubleshoot versions, certificates or licenses.

Should secure download stay off on the real panel?

No. Activate secure download protects project transfer to the panel, and the reported change belongs on an isolated engineering VM used for local simulation only. A physical panel that receives downloads over the plant network keeps the option active, with its transfer protection configured as documented.

When must the simulator listen address change from 127.0.0.1?

Only when the components are split. The default works while the engineering station and the simulated runtime are the same machine or guest. If the simulation is addressed from another machine, set the host address under TIA Portal Settings, Simulation, HMI simulation to an address that machine can actually reach.

Keep reading

  • Troubleshooting

    WinCC Unified project will not open with a Comfort or Advanced license

    A WinCC Comfort or Advanced engineering license can cover WinCC Unified engineering from TIA Portal V16, but installing the classic WinCC tools does not install the Unified editor. During setup you must tick WinCC Unified Engineering in the installation scope yourself. Add that component first; only then look at the license.

    HMI and touchscreens

  • Troubleshooting

    Why TIA Portal V20 finds 0 compatible Unified Comfort panels

    The '0 compatible devices' scan and the 8020AB0019A5FFF4 load error both come from one gap: the WinCC Unified support in TIA Portal V20, the project's HMI device version and the panel image are not all V20. Install the V20 update, set the device version to 20.0.0.2, flash Panel Image V20, and load with the interface set to Ethernet and the panel's IP entered directly.

    HMI and touchscreens

  • How-to

    Unified Comfort Panel image updates when two versions are needed

    TIA Portal can hold only one installed panel image per major version and device type, so installing the V21 Update 2 image overwrites Update 1 on the engineering PC. Upgrade every affected panel to Update 1 first, then install Update 2, or extract image packages to separate folders and install them per panel through ProSave or USB.

    HMI and touchscreens