Explainer
What running an HMI project runtime on a PC without the panel takes
Short answer
A Pro-face panel project runs on a PC two documented ways: GP-Pro EX simulation on the engineering PC, or the licensed Pro-face PC runtime in its temporary demonstration mode. Both replace only the panel; a physical S7-300 reached over Ethernet stays the confirmed PLC partner, and a connection to WinAC or a Siemens simulator remains unconfirmed.
On this page
- Can a Pro-face HMI project run on a PC without the panel?
- What does GP-Pro EX simulation do on the PC?
- How does the PC runtime connect to a physical S7-300 over Ethernet?
- How long can the PC runtime run without a license?
- Does the same setup work with WinAC or a Siemens PLC simulator?
- How do you verify the PC test bench before trusting it?
- When does the project go back on real hardware?
- Questions asked
You can run a Pro-face operator-panel project on a PC without the panel. Two paths are documented: GP-Pro EX simulation on the engineering PC, and the licensed Pro-face PC runtime installed on a standard computer in its temporary demonstration mode. Both replace only the panel — the confirmed PLC partner is a physical S7-300 reached over Ethernet with the project's own communication settings. A connection to WinAC or a Siemens PLC simulator is a different case: the available evidence does not confirm it, and this article gives it a decision rather than a shrug. The sections below cover what each path does, the licensing window, the Ethernet connection, verification, and when the project goes back on real hardware.
Can a Pro-face HMI project run on a PC without the panel? #
Yes, on two documented paths: the GP-Pro EX simulation built into the engineering tool runs the project on the engineering PC, and the licensed Pro-face PC runtime, installed on a standard computer in its temporary demonstration mode, executes the project as the panel would.
Both paths replace the panel only. The PLC side keeps whatever the real machine has, and the project keeps its own communication settings, so a result on the PC is a result about the project and the PLC — not about a panel you do not have. What neither path confirms on its own is the PLC partner: the confirmed one is a physical S7-300 over Ethernet, and simulated PLCs are a separate question answered further down.
Decision: if the goal is to see the project run and talk to a real S7-300, both paths are available. Pick between them by how long the test needs to live, which is a licensing question, not a technical one.
What does GP-Pro EX simulation do on the PC? #
GP-Pro EX simulation runs your screen project on the engineering PC with no Pro-face hardware attached, and the simulation manual documents a procedure for checking display-unit operation and PLC interaction on the computer, including running the simulation against an external PLC simulator.
That makes simulation the right tool for screen-behaviour work: logic on screens, alarm lists, screen changeover, tag display. Two limits matter. First, simulation is tied to the engineering tool and the PC it runs on; it is a development-time function, not a standing operator station. Second, an external PLC simulator is a general capability — which Siemens simulator products the S7 Ethernet driver can actually reach through it is not established by the documentation at hand, so do not book a Siemens simulator into the plan on the strength of that sentence alone.
Decision: use GP-Pro EX simulation for everything that is about the screens themselves, and treat PLC-side behaviour as a separate test with its own evidence.
How does the PC runtime connect to a physical S7-300 over Ethernet? #
It connects as the panel would: the project keeps the driver type, controller address and port settings it already uses for the real panel, the S7 link stays on ISO-on-TCP at TCP port 102, and the PC takes the panel's place on the Ethernet segment.
The PLC needs an Ethernet interface — on an S7-300 that means a communication processor or an integrated PN interface — and it must be reachable from the PC. Give the PC an address on the same subnet: for example, a PC on 192.168.1.50 with a 255.255.255.0 mask against a controller on 192.168.1.10 needs no gateway entry. Pro-face to Siemens over Ethernet is a long-established pairing, and the same driver serves the physical panels and the PC runtime, so nothing in the project changes.
Decision: with a physical S7-300 on the bench, this connection is the confirmed architecture. Keep the project's real communication settings instead of inventing a test configuration you would have to undo before startup.
How long can the PC runtime run without a license? #
Pro-face documents a 10-day demonstration window for a freshly installed runtime — usable for that period only, not restored by uninstalling and not convertible to a free license — while a full runtime license is required for each PC that runs it permanently.
The licensing detail behind that: the runtime is licensed software, Pro-face documents one license for each PC, with a runtime-only license intended for a second or subsequent PC. The license is floating — deactivation and activation move it between machines — it is perpetual once activated, and activation runs through the manufacturer's activation software. The demonstration window is the short-test tool: install, run the bench work inside the window, and expect the runtime to stop when it closes. Uninstalling does not buy a second window.
Decision: demonstration mode covers a bounded bench test. The moment the PC becomes a standing operator station, it needs its own activated runtime license.
Does the same setup work with WinAC or a Siemens PLC simulator? #
No confirmed path exists: the available evidence establishes a physical S7-300 over Ethernet as the PLC partner and does not establish that the Pro-face S7 Ethernet driver reaches WinAC or a Siemens PLC simulator, so treat that combination as an unproven compatibility test.
GP-Pro EX simulation does document running against an external PLC simulator in general, but the documentation available does not name a Siemens simulator or WinAC as a verified partner. The open point is the network: the driver must reach whatever Ethernet interface the simulator exposes, and project execution on the PC alone proves nothing about that. The failure mode to clear is exactly the class of problem described in why HMI simulation cannot talk to a simulated PLC. WinAC adds a second dependency, because it runs the PLC program on the PC, so you also need the Siemens engineering tool to build and download that program — if that tool choice is unfamiliar, the guide to what STEP 7 is in a PLC project and which one you need walks through it.
Decision: for a confirmed bench, put a physical S7-300 on the Ethernet segment. If only a simulator exists, verify driver-to-simulator reachability first, and do not schedule the project around it.
How do you verify the PC test bench before trusting it? #
Verify on an isolated bench with test tags you have checked in the PLC, not production addresses: confirm displayed values follow the controller, perform one permitted write from the runtime, and note timestamps so update behaviour is measured, not assumed.
Start the runtime with the project's real communication settings, change a value at the controller and watch it arrive on screen, then write from a screen object to a tag that is safe to move and confirm the new value at the controller. The same acceptance approach used for testing an HMI simulation against a live PLC applies here unchanged. For disconnects and restarts, measure loss and recovery separately against the driver's own timeout rather than eyeballing the screen.
Worked example, the bench budget — these are my planning numbers, not a vendor figure. You plan two hours of testing each day. The demonstration window is 10 days long, so the arithmetic is 10 days × 2 h/day = 20 h of bench time. Because the window cannot be paused or restored by uninstalling, it closes on calendar day 10 whether you used the full 20 h or stopped at 8 h; install the runtime the day the PLC arrives, not the week before.
Decision: the bench is trustworthy once values follow the controller and one write lands. Before that, it is a picture, not a test.
When does the project go back on real hardware? #
When the bench test passes, the project returns to the hardware the machine will actually run: the original Pro-face panel if it exists, or — if the operator station itself is being replaced or migrated — a PC-based panel running the same runtime.
The PC runtime you validated is the same software family that serves panel PCs and open-frame units, so a PC-based operator station is a supported target rather than a workaround. If that is the direction, the class of hardware built for the role is industrial panel PCs, mounted and rated for the cabinet instead of sitting on a bench tower.
Decision: bench PC in demonstration mode for the test; an activated runtime license on proper panel hardware for anything that stands at the machine.
Questions asked
Does the demonstration clock pause when the PC is switched off?
Pro-face documents the demonstration installation as usable for 10 days only and states that uninstalling does not restore it; the documentation does not spell out whether powered-off time is excluded. Treat the window as calendar days that run on their own: install the runtime when the bench PLC is actually available, and keep the sessions you planned inside it rather than spreading thin work across the whole window.
Can one runtime license cover several PCs at the machine?
No. Pro-face documents one license for each PC that runs the runtime, with a runtime-only license intended for a second or subsequent PC. The license is floating: deactivation on one machine and activation on another move it, and the documentation sets no limit on the number of activations, so several PCs can share one license one at a time, but never simultaneously.
What changes on the PLC side when the PC replaces the panel?
Nothing in the project. The driver type, controller address and ISO-on-TCP port settings stay exactly as they were for the real panel; the PC simply occupies the panel's place on the Ethernet segment. The PLC keeps its own address, and the PC needs an address on the same subnet, so no gateway entry and no project edit are required. That is what makes the bench result transferable to the real machine.
Is the PC runtime the same software that runs on a Pro-face panel PC?
It is the same runtime family Pro-face sells for its panel PCs and open-frame units, installed temporarily on a standard computer. The difference is licensing: a panel carries its own runtime entitlement, while a standard PC needs an activated runtime license of its own or falls back to the temporary demonstration window. The validated project, screens and driver move across unchanged.