Which License a WinCC Unified PC Engineering Station Needs
Short answer
Configuring a WinCC Unified PC device in TIA Portal needs a WinCC Unified PC ES license — (10k), (100k) or (max.) — or one qualifying WinCC Comfort, Comfort Combo, Advanced, Advanced Combo or Professional license. SIMATIC STEP 7 Professional V18 alone does not cover it, and a Unified Comfort ES or a Powerpack migration license covers other targets, not the PC.

On this page
- What the message is asking for
- Licenses that satisfy a WinCC Unified PC target
- Why STEP 7 Professional alone is not enough
- The Powerpack variant that keeps failing
- Count the entitlements: a worked example
- Check the station step by step
- Trials: documented routes, no automatic fallback
- The decision
- Questions asked
A WinCC Unified PC device in TIA Portal fails with the message License WinCC Unified PC ES was not found when the engineering station holds no qualifying WinCC engineering license for that target. SIMATIC STEP 7 Professional V18 alone does not cover it. The fix is one license from either family: a WinCC Unified PC (10k) ES, WinCC Unified PC (100k) ES or WinCC Unified PC (max.) ES, or — on a station already licensed for classic WinCC — WinCC Comfort, WinCC Comfort Combo, WinCC Advanced, WinCC Advanced Combo, WinCC Professional (512), WinCC Professional (4096) or WinCC Professional (max.). A WinCC Unified Comfort ES licenses panel targets, not the PC device, and a Powerpack migration license does not stand on its own. This article gives the check that finds what is missing on the station and the license decision for each target.
What the message is asking for #
License WinCC Unified PC ES was not found is an entitlement check, not a project fault. ES means Engineering System, and the TIA Portal licensing documentation splits a Unified PC station into two separate licenses: for configuration you need a WinCC Unified PC ES (Engineering System) license, and for use in Runtime you need a WinCC Unified PC RT (Runtime) license. The ES license never runs the machine; the RT license never opens the engineering view.
The check runs against the device type in the project. A WinCC Unified PC target asks for the Unified PC ES entitlement, and a WinCC Unified Comfort Panel asks for WinCC Unified Comfort ES, which is why one station can edit panel projects all week and still refuse a PC device. Adding the device is a separate step from licensing it; Selecting a WinCC Unified PC target in TIA Portal covers the device side.
Licenses that satisfy a WinCC Unified PC target #
Any single license from this table clears the message for the target in the left column. One is enough; duplicates do not improve anything.
| Target in the project | Any one of these licenses clears the check |
|---|---|
| WinCC Unified PC device | WinCC Unified PC (10k) ES, WinCC Unified PC (100k) ES, WinCC Unified PC (max.) ES |
| WinCC Unified PC device, classic WinCC licensing | WinCC Comfort, WinCC Comfort Combo, WinCC Advanced, WinCC Advanced Combo, WinCC Professional (512), WinCC Professional (4096), WinCC Professional (max.) |
| WinCC Unified Comfort Panel | WinCC Unified Comfort ES; WinCC Comfort or higher — WinCC Advanced, WinCC Professional — also qualifies |
The three Unified PC ES levels engineer the same PC target and differ in the runtime scale they license; the licensing documentation annotates the 10k and 100k entries with their counts, so choose the level by the project the PC will run. Unified engineering reaches further than the PC: the product documentation states that WinCC Unified Engineering licenses also enable the corresponding configuration for Basic Panels, Comfort Panels and Mobile Panels, so one Unified PC ES level can serve a station that engineers both the PC screen and the panel targets.
The two Combo entries matter on mixed stations, and the same bundling idea exists on the controller side, where a STEP 7 Professional COMBO license covers classic engineering alongside the newer generation.
Why STEP 7 Professional alone is not enough #
SIMATIC STEP 7 Professional V18 engineers the controller and carries no WinCC entitlement of its own. The licensing documentation treats STEP 7 and WinCC as separately licensed products, and none of the qualifying Unified PC entries ships inside STEP 7. That is the entire content of the original failure: the PLC work opens, the Unified PC device refuses, because the WinCC side of the station is empty. The two licenses are additive, not alternatives — a station that programs the controller and engineers the screen holds a STEP 7 license and a WinCC license side by side in the license manager, and adding the WinCC entitlement leaves the STEP 7 installation untouched.
The Powerpack variant that keeps failing #
A second form shows up in the field: License WinCC Unified PC (10k) ES Powerpack (V16..V19) was not found, reported on a station that also holds a WinCC Unified Comfort ES license. Read the name closely. A Powerpack is the migration license that converts an existing classic WinCC entitlement into the matching Unified one; it rides on a qualifying base license and does not by itself form the full ES entitlement the device checks for. The Comfort ES next to it licenses the panel target, not the PC. Count that station's qualifying Unified PC entitlements and the total is zero, which is exactly what the message reports.
The version range inside the name is the second trap: a license counts only within the TIA Portal generations its name covers, so a station moving to a newer generation re-checks every license against that range. Which WinCC option licenses carry over across TIA Portal versions treats that question on its own.
Count the entitlements: a worked example #
Example inventory, not a measurement. A station reports the not-found message and its license manager shows:
- SIMATIC STEP 7 Professional V18 — controller engineering, no WinCC entitlement: 0 qualifying for the Unified PC target.
- WinCC Unified PC (10k) ES Powerpack (V16..V19) — migration license, not a standalone ES entitlement: 0 qualifying.
- WinCC Unified Comfort ES — panel target only: 0 qualifying for the PC device.
Qualifying Unified PC entitlements: 0 + 0 + 0 = 0, and the check needs at least 1, so TIA Portal refuses the device, matching the field report line for line. Add one WinCC Unified PC (100k) ES and the count becomes 0 + 1 = 1: the device opens for engineering. The other two licenses keep their jobs — the Comfort ES continues to serve panel projects, and the Powerpack now sits on a base entitlement it can migrate.
Check the station step by step #
- Read the exact license name in the message: Unified PC ES points at the PC target, Unified Comfort ES at a panel target.
- In TIA Portal, open
Help > Installed softwareand confirm the WinCC Unified engineering software is installed at all; an option that is not installed cannot find any license. - Open the license manager and review every license installed on the station, not only the newest entry; note anything that is only a Powerpack.
- Open the device in the project and confirm whether the target is a WinCC Unified PC device or a WinCC Unified Comfort Panel.
- Add one qualifying license from the table above for that target, restart TIA Portal and open the device again; the message should not return.
Trials: documented routes, no automatic fallback #
Keep two trial facts separate. Engineering: with the WinCC Unified software installed and unlicensed, the engineering side offers a one-time trial activation, made deliberately rather than granted silently. Runtime: the long-standing field answer was that PC Runtime has no trial license, while the support documentation for V20 publishes a dedicated Simulation & Trial entry for WinCC Unified PC Runtime, support entry 109963699, which points to trial versions of the corresponding Unified ES under support entry 109963850. Neither route changes the decision for a machine that has to run: permanent qualifying ES license for engineering, WinCC Unified PC RT (Runtime) license for runtime, documented trials on the evaluation bench.
The decision #
- Configuring a WinCC Unified PC device: hold any one of WinCC Unified PC (10k) ES, WinCC Unified PC (100k) ES or WinCC Unified PC (max.) ES, or any one of the seven classic WinCC licenses in the table above. SIMATIC STEP 7 Professional alone does not count toward it.
- Configuring a WinCC Unified Comfort Panel: WinCC Unified Comfort ES is the minimum; WinCC Comfort or higher — WinCC Advanced, WinCC Professional — also qualifies.
- Only a Powerpack on the station: add the full qualifying license the migration builds on, from the same table; the Powerpack alone keeps failing the check.
- Running the finished project on that PC: add a WinCC Unified PC RT (Runtime) license; the ES entitlement engineers, it does not display.
Questions asked
Does SIMATIC STEP 7 Professional V18 include a WinCC Unified PC ES license?
No. STEP 7 Professional engineers the controller and carries no WinCC Unified entitlement, so a Unified PC device fails its license check on a station that holds nothing else. The device needs its own engineering license — one WinCC Unified PC ES level (10k, 100k or max.) or one qualifying WinCC Comfort, Advanced or Professional license — and the STEP 7 license keeps its own place beside it in the license manager.
Why does the error name WinCC Unified PC (10k) ES Powerpack (V16..V19)?
That text is the exact entitlement the device looked for. A Powerpack is the migration license that converts an existing classic WinCC entitlement into the matching Unified one, so a message naming the Powerpack means the station holds the migration product but no full ES entitlement for the PC target. Adding one full qualifying license, a Unified PC ES level or a classic WinCC license, clears the check.
Can one license cover engineering and runtime on the same PC?
No. The TIA Portal licensing documentation splits the two sides: configuration of a WinCC Unified PC needs a WinCC Unified PC ES (Engineering System) license and use in Runtime needs a WinCC Unified PC RT (Runtime) license. A station that engineers during the day and displays at the machine holds both, and moving a finished project to another PC means checking that PC's runtime license separately.
Does a WinCC Unified PC ES license also cover panel engineering?
Yes. The product documentation states that WinCC Unified Engineering licenses also enable the corresponding configuration for Basic Panels, Comfort Panels and Mobile Panels, so one WinCC Unified PC (max.) ES license can serve a station that engineers a PC screen and panel targets together. A WinCC Unified Comfort ES alone points the other way: it covers the panels and leaves the PC device reporting its license as not found.
Where are the documented trial versions for WinCC Unified PC?
The support documentation publishes a Simulation & Trial entry for WinCC Unified PC Runtime V20 as support entry 109963699, and that entry points to trial versions of the corresponding Unified ES under support entry 109963850. Activation is deliberate: a missing license does not fall back to a trial on its own, and the engineering side without a license offers a one-time trial activation instead.