Troubleshooting
Why a Comfort Panel touch calibration is not saving
Short answer
A Comfort Panel keeps the old touch mapping when the calibration routine ends without its final step: one touch on the display within 20 seconds of the closing instruction. If an accepted calibration still leaves an offset, test a system screen against runtime — an offset in both points at the touch mapping or sensor, an offset only in runtime points at the project.
On this page
- What the calibration routine actually writes
- The closing touch that saves or skips the new mapping
- Retest with the closing touch made deliberately
- System screen against runtime screen
- Why the mouse works while the touch is off
- Read the offset pattern before changing anything
- What the earlier recompile and download did
- Decision for each case
- Questions asked
The calibration is not saving because the routine ends without its acceptance step. After the last calibration cross, the panel puts up a closing instruction that asks for one more touch on the display, and that touch has to land within 20 seconds. Reading that instruction calmly takes longer than the window, so the routine exits without action and the panel keeps the old mapping. That is why a recalibration can complete and change nothing, and why no project download can fix it. Work the checks in order: retest the calibration with the closing touch made deliberately, compare a system screen with a runtime screen to tell a refused save from a touch-mapping or sensor fault, then read the offset pattern before you touch the project.
What the calibration routine actually writes #
A touch calibration builds the coordinate mapping between the touch sensor and the displayed image, and it does that in two separate operations: collect touches at displayed reference points, then accept the result. The Comfort Panels operating instructions in the Siemens Industry Online Support entry with ID 49313233 give the procedure in the panel's Control Panel: open the Touch tab, select the number of calibration points, press Recalibrate, then touch the center of each calibration cross until the next one is shown. Collecting the reference touches proves nothing on its own. The mapping changes only if the routine reaches and passes its last step, so a completed-looking sequence with a missed acceptance leaves the old mapping live.
The closing touch that saves or skips the new mapping #
The last step is a timed confirmation. A long instruction text on the panel asks you to touch the display within 20 seconds, and when the window expires the procedure ends without action: the previous calibration stays in use and nothing on screen announces the failure. That produces an honest report of a recalibration that changed nothing, because every cross was touched correctly. The repair is procedural, not electrical: read the closing instruction before you start the routine, then touch as soon as the text appears instead of reading it against the clock.
Retest with the closing touch made deliberately #
Run the whole routine once with the closing touch made deliberately:
- Leave a USB mouse attached so you can drive the Control Panel even while touch is offset.
- Open the panel's Control Panel, then the
Touchtab, and select the number of calibration points — keep the offered default for a uniform offset. - Press
Recalibrateand touch the center of each calibration cross until the sequence completes. - When the closing instruction appears, touch the display immediately, inside the 20-second window.
- Prove the save on the spot: move the mouse aside, touch a harmless Control Panel control, and confirm the panel selects the control directly beneath your finger.
System screen against runtime screen #
If an offset survives a calibration you watched get accepted, find out which layer owns it. A system screen such as the Control Panel sits outside the application's button layout, so it exercises the touch mapping alone. Test only on harmless controls and never on live process buttons — put the machine in a controlled state before any runtime-screen test.
| Observation | Meaning | Next move |
|---|---|---|
| Offset on system screens and runtime screens | Touch mapping or sensor, not the project | Repeat calibration with the closing touch; if it persists, read the offset pattern |
| System screens align, runtime does not | The application layer | Compare the deployed project with the intended one; test mouse and touch on the same control |
| Mouse selects correctly, touch does not | Expected: the mouse bypasses the touch mapping | Not evidence about the project; keep testing with touch |
| Same displacement everywhere | A translation in the mapping | Calibration corrects a translation |
| Error grows toward the screen edges | Scale or alignment | Accepted calibration, then sensor inspection |
| Erratic selections or dead areas | Surface or hardware | Clean and inspect the glass before recalibrating |
Why the mouse works while the touch is off #
The USB mouse drives the pointer directly and never passes through the touch sensor's coordinate mapping, so a mouse can operate every runtime button correctly while every touch lands 50 mm to the right. That coexistence is normal and it is why the mouse is a stopgap, not a diagnostic pass: correct mouse behavior clears neither the mapping nor the project. If the touch surface turns out to be damaged, Using a Mouse and VNC When an HMI Touchscreen Fails covers the mouse-and-remote-access arrangement that keeps the line running while the panel waits for repair.
Read the offset pattern before changing anything #
A 50 mm displacement in the same direction everywhere is a translation, and translation is precisely what a calibration corrects — a refused save explains the whole symptom without invoking hardware. An error that grows toward the edges points at scale, which the calibration crosses also fit, so a repeat offender after accepted saves points at the sensor instead. Record the direction and the approximate distance at several separated screen locations rather than writing down only that touch is inaccurate, and repeat touches at one location to separate a fixed offset from unstable input. Do not move application buttons to compensate: it hides the fault, leaves the system screens wrong, and the next accepted calibration undoes it. If calibration keeps failing or drifting after a properly accepted save, Touch calibration fails or drifts: separate the real causes splits the remaining causes — sensor, controller and mounting pressure on the glass.
What the earlier recompile and download did #
The earlier fix is a second-hand report: the panel improved after the project was recompiled and re-downloaded. Treat it as a report, not a mechanism. Compilation prepares the application for execution and a transfer restarts runtime and often the panel itself; neither writes the touch mapping, so the download cannot be the repair. The realistic explanations are that a calibration was accepted during that visit, closing touch included, and the credit went to the recompile, or that the offset was intermittent. Do not build the repair plan around a recompile. Change one variable per test and record before and after for calibration, restart and project transfer separately, so the next occurrence leaves a history instead of a story.
Decision for each case #
- Offset on system screens and runtime screens, same direction everywhere: the mapping is not saving. Retest the calibration and make the closing touch inside the timed window, then prove it on a Control Panel control. This is the reported case, and this is the fix.
- The routine closed with no request for a final touch, or the final touch was missed: nothing was saved and nothing was lost. Start again immediately.
- System screens align but runtime does not: leave calibration alone. Inspect the deployed project — compare screens and objects, and test mouse against touch on the same control.
- Offset persists after a calibration you watched get accepted, especially if it grows toward the edges or touches land erratically: the sensor or its glass is failing. Clean and inspect, and route physical damage to repair. When an older panel is not worth repairing, the terminal can be replaced by a PC-based operator station — see industrial panel PCs and touchscreen computers.
Questions asked
How many calibration points should I select on the Touch tab?
Keep the offered default when the error is a uniform sideways displacement, because that fault is a translation and any of the point counts corrects it. Raise the count when the error changes across the screen, so the panel can fit scale as well as shift. The number of points is selected on the Touch tab beside the Recalibrate button, and the choice does not remove the closing confirmation touch.
What happens to the old calibration when the routine times out?
Nothing is written and nothing is lost. When the closing touch misses the 20-second window, the routine ends without action and the panel keeps the previous mapping, so you can start again immediately.
Does a restart or a project download store the calibration?
No. Compilation prepares the HMI application and a transfer restarts it; neither writes the touch mapping. The only acceptance step is the timed touch at the end of the calibration routine. If a download seemed to fix the offset once, the calibration was almost certainly accepted during the same visit, and the credit went to the wrong action.
When is the offset a touch sensor fault instead of a calibration problem?
When a calibration you know was accepted still leaves an error that grows toward the edges of the screen, or touches land erratically or not at all in one area, the sensor or its glass is failing rather than the mapping. Contamination, a swelling seal or external pressure on the glass gives the same signs. Clean and inspect the surface first, then route physical damage to repair or replacement.