Why a Copied Project Reports a User Rights Error

HMI and touchscreens Published 7 min read

Short answer

The message reports missing user rights, but on a project copied out of its engineering folder the real fault is project state: the copy still carries the identifiers of an integrated project, so the access-protection check fails on open. Verify SIMATIC HMI group membership first; if the account is in the group, stop chasing Windows permissions. Recover the project through the engineering tool, the Project Duplicator or the documented deintegration procedure, never by editing the configuration database.

On this page
  1. Read the message as two faults, then match your case
  2. First check: the SIMATIC HMI group
  3. Why a copied integrated project fails
  4. The documented ways back
  5. What not to do: no surgery on the configuration database
  6. Worked example: one variable at a time
  7. The decision
  8. Questions asked

When WinCC answers a project open with "Open WinCC project: The user does not have the rights to perform this action," the message is only sometimes about Windows rights. It has two real causes. The documented one: the logged-on account is not a member of the SIMATIC HMI user group, which WinCC has checked since V6.0 SP2. The misleading one: the folder you copied out of the STEP 7 project is still, by its stored identity, an integrated project, so the project-level access-protection check fails on open and the tool words that failure as a rights problem. Check the group first; it takes a minute. If the account is already a member, stop working on permissions — put the project back inside its engineering context or convert it by a documented procedure, and leave the configuration database closed.

Read the message as two faults, then match your case #

The text names the operation — opening a project — and blames the user, but authorization is evaluated at more than one layer and the message does not say which layer failed. Match your situation against these four:

  • The account is not in the SIMATIC HMI group. This is the documented cause of the message on every release since V6.0 SP2, and it applies to any project, integrated or not. Fix in the next section.
  • Membership is in place, standalone projects open, the copied integrated project does not. The copy still carries the identifiers of an integrated project but has lost its parent engineering context, so the access-protection check fails on open. No change to Windows will fix this one.
  • The copy opened yesterday and fails today. A raw file copy was never a valid conversion to a standalone project, and the first success did not validate the method. Note what changed in between — a fresh sign-in, a renamed computer, an update — and rebuild the copy the documented way.
  • A complete load to a runtime server failed, and the server project no longer opens. The deployed project on the target is incomplete or inconsistent. That is a deployment fault with its own recovery, not a rights fault; do not confuse it with the copied-folder case.

First check: the SIMATIC HMI group #

  1. On the computer that runs the engineering tools, open Computer Management, look under Local Users and Groups, and check the members of the SIMATIC HMI group. Check the account you actually log on with — the one that starts WinCC Explorer — not a second administrator account.
  2. If the account is missing, add it, then sign out and sign back in. Windows builds the session's access token at sign-in, so a desktop that has been open since before the change still runs with the old token.
  3. Retest the open. If the message is gone, the case is closed. If membership is present and the message stays, you are in the copied-project case below.

For a project that was never integrated — a plain WinCC project that was simply copied — that membership is normally the whole story, and the walkthrough of a WinCC 6.2 project rights error on copied projects shows that plain case end to end.

Why a copied integrated project fails #

An integrated WinCC project is created inside a STEP 7 project and stores identifiers that bind it to that parent: its engineering context and its S7 relationships live in the project's configuration database. On every start, WinCC reads the project's access-protection state from that database — on a failing machine, a SQL Server Profiler trace shows the startup query for S7Project.AccessProtectionEnabled in the CC_Prj_Options table. A folder copy preserves every one of those records but orphans them: the parent STEP 7 project stays behind, so the check cannot be satisfied, and the tool reports the failure with the only wording it has — user rights. The account never mattered.

The same fingerprint — a copied SIMATIC Manager project, correct group membership, the rights message on open — is worked through step by step in fix walkthrough for a copied SIMATIC Manager project that reports a user rights error. The direction works both ways: integration decides which tool may open the project, so a standalone project in turn refuses the integrated editor, as covered in why a standalone HMI project will not open in your integrated editor.

The documented ways back #

Work with runtime stopped and inside the maintenance window — an interrupted rebuild on a live server is how a misleading message becomes a dead runtime.

  1. Open the original, not the copy. The integrated project opens through SIMATIC Manager, in the engineering context its identifiers expect. If the test copy has served its purpose, delete it; no Windows change will ever make that folder open in WinCC Explorer.
  2. Archive the failing folder first. Copy it aside untouched before any recovery attempt. The recovery sequence for an HMI project that fails to open starts exactly there.
  3. Produce copies with the Project Duplicator, not with Explorer. It is the copying tool the vendor documents for WinCC, and in reported server recoveries the project was duplicated on a second WinCC station and reopened on the server from that duplicate. A duplicate keeps the identity of the original, so an integrated original duplicated this way is still an integrated project.
  4. Deintegrate when a standalone project is the goal. The vendor documents the procedure as support entry 109779031, and its stated precondition is that every SIMATIC application is closed first — SIMATIC Manager and WinCC included. Deintegration changes the project's identity to standalone; duplication does not. A copy that must live outside STEP 7 is a deintegration job, not a copy job.
  5. Treat migration as its own route. A classic integrated project of the S7-300/S7-400 era is migrated with TIA Portal V18 or an older release, then upgraded to the current format. Do not point a current release directly at the legacy folder.

What not to do: no surgery on the configuration database #

The shortcut that circulates — open the project database with SQL Server Management Studio and remove the records that mark the project as integrated — is not a vendor procedure, and it is not a recovery path. Those records are the access-protection state the startup query reads; delete them by hand and the engineering project, the configuration database and any deployed server no longer agree on what the project is, and the protection itself has been altered rather than satisfied. The vendor's own support article treats a formerly integrated project whose access protection cannot be unambiguously determined as a fault to resolve, not a value to edit. Every case above closes with a documented tool; the database editor closes none of them.

Worked example: one variable at a time #

Bench reproduction on the release of the reported case, WinCC 7.0 SP3 with update 1, with an OS project integrated in a STEP 7 project and an account already in SIMATIC HMI:

  1. Open the original from SIMATIC Manager. It opens.
  2. Copy the WinCC project folder out of the STEP 7 directory to D:\TestCopy\ and open that copy in WinCC Explorer, same account, same session. The rights message appears.
  3. Verify the group membership again. Present. Between steps 1 and 2 nothing about Windows changed; the only difference is how the second folder came into existence, so the copy method alone reproduces the fault.
  4. Delete the copy, duplicate the original with the Project Duplicator, open the duplicate in WinCC Explorer. It opens.

Read-out: the message follows how the folder was produced, not who opened it. That single-variable result is the entire diagnosis — fix the production method and the message disappears without touching one permission.

The decision #

  • New account or fresh workstation, message on any project: add the account to SIMATIC HMI on that computer, sign out and back in, done.
  • Membership present, message on a folder copied out of the STEP 7 project: the copy is not an openable standalone project. Discard it and open the original through SIMATIC Manager. When a standalone copy is genuinely required, deintegrate by the documented procedure with all SIMATIC applications closed, and make future copies with the Project Duplicator.
  • Server project dead after a failed complete load: stop retrying loads. Recover from the last good archive or from a duplicate made on a second WinCC station, with runtime stopped, then reload the server from the clean engineering baseline.
  • In no case open the configuration database to change protection records. That path trades a misleading message for real damage.

Questions asked

Why does the new group membership only take effect after signing out?

Windows builds a session's access token at sign-in, and group membership is part of that token. A desktop that stayed open across the change keeps running under the old token, so the engineering tools still see an account without the membership. Signing out and back in rebuilds the token; a reboot achieves the same thing on a shared station.

Can I remove the integration records from the project database myself to stop the message?

No. Those records are the project's access-protection state, and deleting them by hand is not a documented procedure on any release. It leaves the engineering project, the configuration database and a deployed server disagreeing about the project's identity, and it weakens the protection the records provide. Use the engineering tool, the Project Duplicator or the documented deintegration procedure instead.

Where is the deintegration procedure documented?

In the Siemens support database as entry 109779031, on separating an integrated WinCC project from STEP 7. Its stated precondition is that all SIMATIC projects and applications are closed first, SIMATIC Manager and WinCC included. Run it on the engineering station against the original project, then handle the result with the normal standalone-project tools.

The message appeared after a failed complete load on the server. Is that the same fault?

No. A failed or interrupted deployment can leave the runtime project on the server incomplete, and no Windows right repairs that. Preserve the load logs first, then recover from the last good archive or from a duplicate created on a second WinCC station, and reload the server from the clean engineering baseline afterwards.

Keep reading

  • Troubleshooting

    Fix WinCC HResult 0x8004610a when a project will not open

    Restore the Windows user rights the station had before the failures: in a documented WinCC V6.0 SP2 case, an IT rights change produced 0x8004610a on one project and 0x80046127 on another, and rolling the rights back cleared both. Check the read-only attribute on the project database when files came from CD, and the mcp.ini network entries for the vendor-documented network-card cause, before suspecting a damaged database.

    HMI and touchscreens

  • Troubleshooting

    Fixing an HMI Project Upload That Reports Communication Failed

    Treat a failed HMI project upload as three separate branches: the installer's parallel-port dongle driver message is a licensing fault, a "communication failed" report before any progress is a transfer-path mismatch, and a "file system error" after the panel answers is a storage or destination fault. Identify the layer from the message and the moment it appears, fix that layer only, and retest. A dongle fault never blocks the cable, and a successful ping never proves the transfer service is up.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC flexible 2008 reports a beta version flag on an HMI project

    The B 1.4 SP 1.0 – 1.17.3 rejection is a project-version or project-integrity fault, not an installation fault. Prove the installation opens healthy projects, compare the .hmi and .ldf timestamps, then recover through an isolated .hmi copy so Flexible regenerates the companion file.

    HMI and touchscreens

Keeping PanelView Plus User Passwords After an MER Download