Troubleshooting
Why a KTP 1000 screen fails at 244 configured items
Short answer
The error means exactly what it says: screen Ana_Ekran carries 244 configured screen items and the KTP 1000 PN/DP target allows 200 per screen, so at least 44 counted items must come off that one screen. Hiding objects, visibility animations and editor grouping do not lower the compiler's count; deleting objects, replacing static artwork with a single graphics object, or moving content to another screen does. Recompile after each change.
On this page
Nothing on the machine is failing — the screen is over budget. The compiler has already done the diagnosis: it counted 244 configured screen items on Ana_Ekran and reported that the KTP 1000 PN/DP target allows 200 per screen, so that one screen has to lose at least 44 counted items. No other screen, no tag and no memory figure is involved, which is why trimming other pages or the tag list will never clear this error. The two traps are that hiding objects, visibility conditions and editor grouping do not lower the count, and that a screen which looks tidy can still hold hundreds of configured lines, outlines and labels. Cut that screen to size, recompile after every change, and leave headroom below the allowance for the next revision.
What the diagnostic actually reports #
The message says it all: "Error : Number of configured screen items per screen 244 exceeds system limit of 200 on screen 'Ana_Ekran'."
| Part of the diagnostic | What it decides |
|---|---|
| per screen | The allowance applies screen by screen; every other screen keeps its own full allowance. |
| system limit | The figure belongs to the configured target's technical data, not to your project or your TIA Portal version. |
| the named screen | Exactly one screen is over its allowance; the rest of the project is irrelevant to this error. |
| a counted figure | This check moves only when configured objects move. Tag-count checks and memory checks produce their own diagnostics. |
The KTP1000 Basic is the 10.4-inch, 640 x 480 TFT Basic Panel, configured in TIA Portal, and its data sheet lists STEP 7 Basic as the configuration software. At every compile, the compiler reads that target's technical data and enforces it. Figures like items per screen are published per panel family, and WinCC HMI panels compared by their system limits collects them side by side. For contrast, WinCC Unified performance data lists 600 objects per screen and 300 screens for a Unified Basic Panel: a different panel generation with its own budget, not an upgrade path for this project. Read each target's allowance from its own diagnostic or documentation, and treat a tag-count fault such as the variables per device limit in TIA Portal HMI as a separate error with its own message.
Why hiding, grouping and visibility do not lower the count #
The count follows configuration, not presentation. A visibility condition decides only whether an object is shown at runtime; the object stays configured on the screen with all of its properties, so the compiler counts it whether the operator ever sees it or not. Presentation is exactly what WinCC visibility animations change when they hide and show objects at runtime — the configured screen underneath is untouched.
Grouping is an editing convenience, not a reduction: the objects inside a group remain configured, so treat every group as many items rather than one. If a project ever seems to prove otherwise, compile before and after ungrouping and let the diagnostic decide.
What lowers the count is changing what is configured: deleting an object, moving it to a screen with allowance left, replacing many static objects with one graphics object, or keeping one display object that swaps text or pictures by tag value instead of several fixed ones.
Worked reduction: Ana_Ekran from 244 configured items to the 200-item allowance #
Inputs: a reported count of 244 configured screen items on Ana_Ekran, taken from the compiler diagnostic, and a per-screen allowance of 200 configured items for the KTP 1000 PN/DP target, quoted by the same diagnostic. Both figures come from the failed compile, not from estimates.
Rule: the compiler accepts a screen only while its configured item count sits at or below the target's per-screen allowance, so the items to remove equal the reported count minus the allowance.
Arithmetic: 244 - 200 = 44 items. As a share of the screen, 44 ÷ 244 = 0.18, so about 18 percent of Ana_Ekran's configured items have to go.
Result: Ana_Ekran must lose at least 44 counted items before this target compiles that screen. The allowance is the pass threshold: above it the compile fails, at or below it the screen passes.
Decision: sit exactly on the allowance only if this screen will never grow again. For a screen that will be revised, stop lower — for example at 190, which banks 10 items of headroom — and recompile after each change so the diagnostic, not an estimate, tracks the total.
Cutting the excess without losing operator function #
Work in this order, compiling as you go:
- Copy the project and compile the copy once; the diagnostic should name the same screen and the same figures, which confirms you are measuring the right screen.
- Select everything on the screen and inventory it: hidden objects, overlapping objects, group contents, decoration, anything parked outside the view. The editor shows less than the compiler counts.
- Classify every assembly by function — static decoration, dynamic indication, operator input, navigation. Decoration with no function is the expendable share.
- Delete pure decoration first: borders, shadows, duplicate labels, redundant line segments in pipework. A removed outline is a counted item gone.
- Replace multi-object static artwork with a single graphics object wherever no element needs its own animation, touch action or text translation; a tank-and-pipe drawing built from dozens of lines and outlines can become one image object.
- Collapse state display: one object that swaps text or pictures by tag value replaces several fixed text or picture objects.
- Move real content to a second screen: an overview plus a detail screen reached by one navigation button carries more than a single overloaded screen.
- Compile after every change. The diagnostic's count is the only accepted measurement; if a change does not move it, the objects you touched were not part of the counted total.
If the screen climbs back over the allowance at every revision, the layout is carrying work it should not, and the durable fix is redesigning the screen around what the operator actually does — designing a touch HMI screen around real operator conditions covers that exercise.
Questions asked
Why does the diagnostic appear only now, when this screen compiled before?
The allowance has applied to this target all along; earlier revisions of the screen simply stayed under it. The count rises with every object you add, because each line, label, field and button counts, including the objects inside groups. So a screen that compiled cleanly yesterday can cross the allowance at the next revision. The check runs at compile time only, and it names just the screen that crossed.
How do I measure the item count when the editor shows no number?
Use the compiler as the counter. Compile once and read the count and the screen name from the diagnostic. Then change one thing at a time, such as deleting one decorative assembly or ungrouping one group, and compile again. If the reported figure drops, those objects were counted; if it does not, they were not. This also tells you how the target counts groups before you cut anything an operator needs.
Is there a project setting that raises the per-screen limit?
No. The figure is read from the target device's technical data and no project setting raises it. The options are fewer counted items on that screen, splitting the content across a second screen, or selecting a target generation with a larger documented per-screen allowance, which is a hardware decision rather than a compile option.
Do objects placed partly outside the visible screen area still count?
Yes. The count follows configuration, not the visible frame: an object parked off-screen is still configured, still loaded at runtime and still counted, exactly like a hidden one. Parking objects outside the view only tidies the editor. Delete them or move them to a screen that has allowance left.