Explainer
Why a KTP600 backup cannot change the PLC connection IP
Short answer
The PLC address a KTP600 dials is project data inside the HMI application, so a ProSave backup, the panel's own interface screen and the transfer-settings gateway field all leave it untouched. Give the PLC the address value the project already targets, or recover the editable project, change the connection and retransfer it.

On this page
You cannot change the PLC connection address of a KTP600 from a backup, from the panel's interface screen, or from the gateway field in Transfer Settings. That address is project data inside the HMI application, and only an editable project can rewrite it. With no project on hand and no back transfer available on this panel and software pairing, three legitimate routes remain: give the S7-1214C the address value the project already targets, recover or rebuild the project and retransfer it, or use a connection-change function if, and only if, your own application screens expose one. The gateway advice that circulates for this fault sends the new controller address into the transfer settings; that field routes traffic between subnets and never selects the runtime partner. This article separates the two addresses, shows why the backup cannot supply the edit, works the subnet change with real numbers, and ends with the decision for each situation.
Two addresses with two different jobs #
The panel's interface address identifies the KTP600 on the network. You set it on the panel's own Control Panel network screen or with the Assign IP address function in TIA Portal, and changing it touches nothing inside the application. The connection endpoint is a different setting: the controller address stored in the HMI project's S7 connection, built in the engineering tool — STEP 7 Professional V11 SP2 Update 5 here — and delivered to the panel at download. Every tag, alarm and screen the runtime serves travels through that one endpoint value.
The two fixes therefore live in different places. Interface addresses can be reassigned at any time. The endpoint changes only when a new application is transferred, or when the original programmer deliberately built a runtime function that writes it. After an address change, the failure signature — panel reachable, every runtime tag timing out — is the one the article on HMI comms errors after a PLC IP address change helps you trace; the job here is to make the change itself stick.
What the backup restores, and what it never becomes #
ProSave moves data between the panel and the engineering PC: Backup saves the operating system, the application and the data, and Restore puts that image back onto a panel. The panel ends in exactly the state it was backed up in, old endpoint included. Nothing in that file opens as an editable project.
On this panel and software pairing, the transfer menu offers no back transfer at all, so there is no route from the panel back to a source project, and repeating backups cannot create one. Keep the backup anyway: it is your rollback state before any reset or retransfer work, alongside a written record of the current interface settings. The restore-only trap is not unique to this panel; the article on why a psb backup is not an editable WinCC flexible project covers the same boundary for the WinCC flexible era.
Why the gateway field cannot repoint the HMI #
A default gateway has one job. When a device must send a packet to a destination whose network portion differs from its own, it hands that packet to the gateway; if the destination is on the local subnet, the gateway is never consulted. Typing the PLC's new address into the panel's transfer settings therefore fails twice: the runtime endpoint stays untouched, and the panel is told to route off-subnet traffic to a host that is not a router. On a flat machine network, where panel and controller share one subnet, the correct gateway entry is the subnet's router address if one exists and nothing at all if none does — never the PLC.
Transfer settings also serve a different channel: they describe how the engineering PC reaches the panel to download a project, not which controller the runtime reads process tags from. That is why the panel keeps calling the old address no matter what the transfer screen says.
Working the move from 192.168.0.x to 10.1.40.x #
The case pairs an S7-1214C, order number 6ES7 214-1HE30-0XB0, with a KTP600 mono PN, order number 6AV6 647-0AB11-3AX0, and records no actual addresses, so this plan uses example values. Old network: 192.168.0.0 with mask 255.255.255.0, PLC at 192.168.0.1, panel at 192.168.0.2, and the endpoint stored in the HMI project pointing at the PLC's value. New plan: one subnet, 10.1.40.0 with the same mask, PLC readdressed to 10.1.40.17 and panel to 10.1.40.2.
The rule is standard IPv4 subnetting: a device delivers a packet directly when the destination's network portion equals its own, the network portion being the address ANDed with the mask octet by octet, and otherwise hands the packet to the gateway. And the runtime's S7 requests go wherever the project's endpoint says, whatever the interface addresses are.
Panel 10.1.40.2 AND 255.255.255.0 gives 10.1.40.0. PLC 10.1.40.17 AND 255.255.255.0 also gives 10.1.40.0. Equal, so the two devices are local to each other and no gateway belongs in the path. The endpoint is another story: 192.168.0.1 AND 255.255.255.0 gives 192.168.0.0, which differs from the panel's own network portion. The runtime therefore treats its configured PLC as a remote host and hands every request to the gateway entry — which, on this isolated subnet, does not exist. Every tag read times out.
Result: both devices hold new, correct interface addresses, ping works in both directions, and the runtime is still dead, because the application keeps dialing the old endpoint.
The decision: if the addressing plan lets the controller keep its existing value on the new subnet, the endpoint still matches and the panel recovers with no project work — take that path first. If the controller must carry a new value such as the planned one, the application has to change through one of the paths below before the panel communicates again.
Four supported paths, and the decision for each #
- Keep the controller's existing address value. Assign the PLC its current address on the new subnet and change only the panel's interface address; the endpoint still matches, no project is needed and downtime is minutes. Take this path whenever the address plan allows the controller to keep its value.
- Recover the editable project and retransfer. Get the project from the machine owner, the builder or the integrator who commissioned the panel; open it in the engineering version that supports it — here STEP 7 Professional V11 SP2 Update 5; change the address in the HMI's S7 connection; compile; download. This is the correct path when the controller must take a new value and the source exists.
- Use a runtime connection change only if your application exposes one. Some applications deliberately build a service screen or a script that writes a connection address at runtime. Verify on your own screens what the function writes, which connection it changes and how the value survives a power cycle. A generic Control Panel network screen is not this function: it edits the panel's interface and transfer path, never the application's partner.
- Rebuild the application. When no project exists anywhere, recover the tags, alarms and screens, aim a new connection at the controller's address in use and download. The article on rebuilding a lost HMI project from PLC tags and logic walks that recovery, and the rebuild ends the dependence on restore-only backups, because you then hold editable source for the next change.
| Path | What it needs | It wins when |
|---|---|---|
| Keep the controller's address value | An address plan that lets the controller keep its value on the new subnet | No editable project exists and downtime must stay in minutes |
| Recover the project and retransfer | The editable source and a supported engineering version | The controller must take a new value and the source can be found |
| Runtime connection change | A function the original application deliberately exposes | Your own screens prove it writes the endpoint and survives a restart |
| Rebuild the application | Tag and screen records, or reads from the controller | No project can be recovered from anyone |
Commissioning order that keeps the downtime bounded #
- Record everything before touching anything: both interface addresses, masks, any gateway entries and the endpoint the application targets.
- Put the machine in a controlled state first. Alarms and operator actions run through the panel, so make the change with the line stopped and someone watching the process.
- Give the engineering PC an address on the destination subnet. An S7-1200 answers the tool only once the PC's adapter sits where the controller can reply; the walkthrough on making an S7-1200 reachable from the engineering tool covers that check step by step.
- Assign the new interface addresses with the Assign IP address function, confirming each device by order number before writing, so 6ES7 214-1HE30-0XB0 and 6AV6 647-0AB11-3AX0 never get swapped.
- Apply the endpoint change through the chosen path, compile clean and download to the panel.
- Prove it: read and write a real tag, power-cycle the panel once and confirm the connection returns on its own.
Questions asked
Why does the panel still fail after I assign new IP addresses in TIA Portal?
Assign IP address changes each device's interface address only. The S7 connection inside the HMI application keeps the endpoint value it was compiled with, so the runtime keeps calling the old address until an edited project is transferred again. The panel can answer ping at its new address while every runtime tag still times out.
Can a runtime screen on the panel change the PLC address without a new download?
Only if the original application deliberately exposes such a function, for example a script that writes a connection address or a connection-selection screen built at commissioning. Panels of this generation have no built-in screen for editing the application's connection partner; the panel's own network screens cover the interface settings and the transfer path.
Is anything in the ProSave backup file worth reading?
Treat it as rollback material, not as a source file. A backup restores the panel to the state it was backed up in; it is not a documented format you can open, search or edit. If the running application shows connection details on a service screen, read the endpoint there, otherwise take it from the project records.
What if no one can find the original project?
Plan a rebuild. Recover the tags, alarms and screens the panel actually uses, point a new connection at the controller's address in use and download the rebuilt application. Holding the editable source afterwards also ends the restore-only dependency, so the next address change becomes a short edit instead of a recovery problem.