Why a LOGO! 9 touch screen misses presses when calibration is accurate

HMI and touchscreens Published 5 min read By IMDTouch engineering team

Short answer

Accurate touch location with missed presses is a registration fault, not an alignment fault, so recalibrating the LOGO! 9 changes nothing; the resistive display needs firm pressure through a small contact point: run a press tally with a fingertip and a firm passive stylus, and if the stylus round is clean, commission the unit with the stylus. If both rounds miss, the unit's registration is faulty and it goes back to the vendor.

On this page
  1. Calibration cannot fix a missed press
  2. Sort the symptom before touching anything
  3. The ten-minute press test
  4. Read the tally and make the call
  5. Close the stop-access report before operators use it
  6. Reported quirks with no documented correction
  7. Questions asked

Your calibration changed nothing because calibration was never the problem. When a LOGO! 24RCE version 9 shows the touch position accurately yet buttons — the bottom system buttons above all — still miss presses, the unit has a registration fault: the press is not detected, not mis-mapped. The display is resistive, so it answers pressure through a small contact point, not capacitance. On units reported with this exact symptom, a deliberate press or a firm passive pen restored reliable operation where a fingertip and a soft phone stylus did not. Run the press tally below once: it takes minutes and decides whether the screen is healthy and needs a stylus, or the unit goes back to the vendor.

Calibration cannot fix a missed press #

Calibration builds a coordinate map between the glass and the screen positions. It cures a pointer that lands somewhere other than your finger. It has no access to the detection of the press itself, which is why calibrating from the device menu changed nothing on the reported unit. The two failure modes are physically separate:

  • Alignment fault: the pointer lands offset from the press. Calibration is the right tool; if the offset survives a calibration run, the causes and fixes in separating the real causes of touch calibration failure and drift apply.
  • Registration fault: the pointer lands exactly where you pressed, but some presses produce no response at all, intermittently. No calibration routine can reach this.

On a resistive display the front layer must be pushed into contact with the layer beneath it before anything registers. That makes pressure and contact area the whole game: a fingertip is large for a screen this size and lands across neighboring targets, while the soft tip of a phone stylus — tried on a reported unit and found too gentle — does not apply enough force to close the contact. A firm passive pen with a small tip does both jobs. If you also maintain capacitive panels, note that their missed presses come from different physics; the edge-of-screen causes in why capacitive touch buttons miss presses near screen edges do not apply to this display.

Sort the symptom before touching anything #

Put what you see into one bucket, because the buckets get different work:

  • The pointer lands offset from the press: alignment. Run the device calibration once and retest fixed targets.
  • The pointer is accurate but presses are missed, worst on the bottom system buttons: registration. Stop calibrating.
  • One navigation run seems to activate several pages: registration or contact-area trouble. This is reported on another unit with the root cause unconfirmed — record the exact page sequence that does it.
  • Misses happen only with a light touch and never with a deliberate press: the screen is healthy and the input device is wrong.

The ten-minute press test #

Use a screen that shows the bottom system buttons and a page you can navigate to and from. You need a log line for every miss and one tool: a firm passive stylus with a rounded tip that cannot mark the front film. Prove the tip on a screen corner before you start.

  1. Round one, fingertip: press each bottom control 20 times, deliberately, the way an operator would under time pressure.
  2. Round two, stylus: the same 20 presses per control with the firm passive pen.
  3. Log every miss with the control, the method, and whether one press triggered more than one page change.
  4. If the stylus round shows a miss, repeat that control's presses once more. A miss that repeats on the same control confirms the fault.

Read the tally and make the call #

Worked example with illustrative numbers. Say the bottom row has four controls. Four controls × 20 presses = 80 presses per round.

  • Round one, fingertip: 6 misses. 6 / 80 = 0.075, so 7.5% of presses lost.
  • Round two, stylus: 0 misses. 0 / 80 = 0%. No confirmation re-run needed.

Decision for this unit: registration is healthy and the contact point was the fault. Keep the unit, and make the firm passive stylus the specified operator input — tether it at the panel and write it into the operating procedure.

Second case: the stylus round loses 3 presses — 3 / 80 = 0.0375, so 3.75% — and one of them repeats on the same control in the confirmation re-run. Decision: the unit's touch registration is faulty. Stop recalibrating; it cannot reach this fault. Return or replace the unit through the vendor's support channel with the tally attached. The cutoff needs no percentage: these are the controls an operator reaches for to run and stop production, so any miss that reproduces on the bench is disqualifying.

Close the stop-access report before operators use it #

One report from a version 9 unit states that placing the controller in STOP did not request a password, even though an administrator password was assigned when the LOGO! program started. The observation is reported once and not independently confirmed, and it decides whether operators can generate production stoppages at will.

Before handover, set the intended password and protection in the LOGO! configuration software, download the project, then try to reach STOP from the screen exactly as an operator would. If no prompt appears, treat the touch stop as unprotected: state it in the operating procedure and do not rely on it as an access control.

Keep any safety-rated stopping function on hardwired devices selected through the machine's risk assessment under ISO 12100 and wired to the IEC 60204-1 stop categories. A touch screen is an operator convenience, never the safety function itself.

Reported quirks with no documented correction #

The same reports include items that have no setting, firmware correction or confirmed fix in the available documentation. Test each on the bench so nothing surprises you during commissioning:

  • Keyboard entry is reported difficult, with a character-completion timeout perceived as too short. Run every entry screen operators must use — setpoints, counters, messages — before handover.
  • The download workflow is reported more involved than on the previous version. Perform one full download and one program change on the bench first.
  • Pages activating together during navigation: if it persists with the stylus, add it to the same support case as the tally.

Questions asked

Does the LOGO! 9 screen need an active or capacitive stylus?

No. Detection is pressure-based, so the pen carries no electronics: any firm passive stylus or a gloved fingertip works, and an active pen adds nothing. What matters is a small, rounded, rigid tip that cannot scratch the front film and enough force to close the internal contact. A soft capacitive phone stylus fails on force, which matches the too-gentle result reported from the field.

Will repeating the calibration eventually improve the missed presses?

No. Each run only rewrites the coordinate map between the glass and the displayed positions, and a unit whose pointer already lands accurately gives the routine nothing to correct. The routine exposes no press-detection threshold, because there is none to change. Run it once to confirm alignment, record the result, and spend the remaining time on the press tally instead.

What belongs in the support case when the tally fails?

The unit's order code and firmware version, the tally with misses per control and input method, the confirmation re-run, and a note that touch position was accurate before and after calibration. That package separates registration from alignment for the vendor and shortens the exchange. Attach the navigation and keyboard-entry observations as well if they persist with the stylus.

Can operators just learn to live with the small screen?

Do not commission on that basis. One report describes fewer wrong touches after a few days of use, but an operator roster rotates, and the bottom system buttons are the controls people reach for under time pressure. Specify the tethered firm stylus and a clean tally as the acceptance result; a learning curve is not an acceptance criterion.

Keep reading

  • Troubleshooting

    Fixing a TP270 Touch Screen That Ignores Finger Presses

    When a TP270 6AV6545-0CC10-0AX0 keeps its picture and PLC traffic but takes no finger presses, the fault is in the panel's own flash, not the project: a corrupt calibration table or a damaged OS image. Back up, reset the operating system to factory settings with ProSave over the 6ES7 901-1BF00-0XA0 zero-modem RS232 cable, download the project again and calibrate. If the calibration still will not take, the touch front is worn out and the panel goes for service or replacement.

    HMI and touchscreens

  • How-to

    Calibrate a resistive touch overlay in its USB controller

    Windows stores its touch calibration on the PC, so it never reaches a machine controller. Run the touch board maker's driver utility instead, complete the nine-point calibration while the board is still connected to the PC, and let it write the correction into the board. The board then reports aligned coordinates to every host it is plugged into.

    HMI and touchscreens

  • Troubleshooting

    Touch calibration fails or drifts: separate the real causes

    If calibration fails repeatedly, the fault is usually the calibration tool, its driver or session state, not the touch sensor: a pass that stops with an error before the target pattern runs never changes stored coordinates. Calibration persists until firmware changes, so test several touch targets first — one dead button is an application-event fault, and only a whole-screen offset that keeps returning is true drift.

    HMI and touchscreens

Why a touchscreen stops responding after a power loss